2002-08-01 00:00:00 | 1) ENTIRE BUILDING IS TO BE COMPLETELY |
| FIRE SPRINKLER PROTECTED. THIS INCLUDES |
| ALL ELECTRICAL, MECHANICAL, AND SERVICE |
| TYPE ROOMS. |
| |
| 2) THE FDV'S LOCATED BETWEEN 7 AND 8 |
| ON PAGES 2 AND 3 COULD POSSIBLY BE |
| BLOCKED BY PARKED VEHICLES. PLEASE |
| ADVISE AND REVISE AS REQUIRED. |
| |
| 3) ALL EXTERIOR FIRE SPRINKLER HEADS |
| ARE TO BE CORROSION RESISTANT. |
| |
| 4) IT IS BELIEVED THAT EXISTING FIRE |
| SPRINKLER HEADS BELOW THE CANOPY WAS |
| DEMOLISHED RECENTLY. THIS OFFICE WAS |
| ADVISED THAT NEW FIRE SPRINKLER HEADS |
| WOULD BE INSTALLED TO MATCH EXISTING |
| PROTECTION. SOME PROTECTION IS SHOWN |
| BUT IS IT IDENTICAL TO WHAT WAS THERE |
| PREVIOUSLY. ARE THE SIDEWALL HEADS SHOWN |
| ON PAGE 4 AT THE PROPER ELEVATION TO |
| SERVE THIS PURPOSE. |
| |
| 5) ARE ANY ROOF MANIFOLDS BEING |
| PROVIDED. |
| |
| 6) PLANS INDICATE FIRE SPRINKLER DESIGN |
| IS IN ACCORDANCE WITH NFPA 13, 2000 |
| EDITION. SHOULD READ 1999 EDITION. |
| |
| 7) PLEASE PROVIDE VERTICAL DETAILS OF |
| STANDPIPE SYSTEMS AND ANY VERTICAL |
| SHAFTS THAT REQUIRE FIRE SPRINKLER |
| PROTECTION. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 659-8096,EXT.8497 |
| 835-2910 |