Plan Review Stops For Permit 02072011 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-08-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-08-02 |
Time |
07:36 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-08-13 |
Time |
13:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-08-02 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-08-02 |
Time |
07:26 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
FIRE |
|
Notes |
2002-08-02 00:00:00 | PROVISO: | | | | EXHAUST TERMINATION SHALL BE LOCATED NOT | | LESS THAN 10 FT HORIZONTALLY FROM PARTS | | OF THE SAME OR ADJACENT BUILDINGS, | | PROPERTY LINES & AIR INTAKE OPENINGS AS | | PER 2001 FBC(M) 506.3.14.3. | | | | PLEASE PROVIDE MANUFACTURER INSTALLATION | | INSTRUCTIONS ON THE 1 HR FIRE WRAP ON | | THE JOBSITE AT THE TIME OF INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
|