Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-01 Cont ID  
Sent By pkrauss Date 2002-08-01 Time 12:19 Rev Time 0.30
Received By pkrauss Date 2002-08-01 Time 12:16 Sent To  
Notes
2002-08-01 00:00:00PROVISO:
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 EXHAUST FAN REQUIRED FOR BATHROOM AS
 PER 2001 FBC(M) 402.3.1.
  