Plan Review Details - Permit 02071914
Plan Review Stops For Permit 02071914
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-07-31 Cont ID  
Sent By pkrauss Date 2002-07-31 Time 12:05 Rev Time 0.35
Received By pkrauss Date 2002-07-31 Time 11:58 Sent To  
Notes
2002-07-31 00:00:00BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
  
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.