Plan Review Details - Permit 02071831
Plan Review Stops For Permit 02071831
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-13 Cont ID  
Sent By dpalmer Date 2002-08-13 Time 07:11 Rev Time 0.00
Received By dpalmer Date 2002-08-13 Time 07:00 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-19 Cont ID  
Sent By rregueir Date 2003-02-19 Time 17:43 Rev Time 0.33
Received By rregueir Date 2003-02-19 Time 17:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-12 Cont ID  
Sent By hmoser Date 2002-08-12 Time 19:53 Rev Time 0.33
Received By hmoser Date 2002-08-12 Time 19:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By jleech Date 2002-08-06 Time 17:25 Rev Time 0.33
Received By jleech Date 2002-08-06 Time 17:25 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-10-28 Cont ID  
Sent By lhatten Date 2002-10-28 Time 18:55 Rev Time 3.00
Received By lhatten Date 2002-10-26 Time 18:54 Sent To  
Notes
2002-10-28 00:00:00REVIEW & STAMPED PLANS 10/26/2002
 CALC. FEES & PRINT CARD 10/28/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-08-23 Cont ID  
Sent By jgomez Date 2002-08-23 Time 17:46 Rev Time 3.00
Received By jgomez Date 2002-08-23 Time 17:46 Sent To  
Notes
2002-08-23 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS AND
 COMPLETE SECTIONS/DETAILS/SPECS FOR
 DESIGN OF GABLE END AT FRONT ELEVATION
 CONSIDERING THAT THE CENTER OF GABLE
 IS MASONRY & ENDS ARE WOOD TRUSSES.
 HOW IS THE GABLE END WALL PUT TOGETHER
 TO TRANSFER ALL LOADS. SEE SECTIONS
 1606.2.4, 2117 AND 2313 FBC 2001.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-REVISE ATTIC ACCESS SIZE. 36" MIN. NOT
 30". SEC. 2309.6 FBC 2001.
 4-34SH WINDOW DOESN'T PROVIDE 24" MIN.
 CLEAR HT. OPENING. SEC. 1005.4.4 FBC.
 5-PROVIDE SOIL TEST REPORT.
 6-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS OR SEPARATE PERMIT
 REQUIRED.
 7-PROVIDE PRODUCT APPROVAL FOR SINGLE
 ENTRY DOOR W/ SIDELITE SINGLE ASSEMBLY
 AS SHOWN ON PLANS.
 8-PROVIDE STRUCTURAL DETAIL FOR 2X BUCK
 AS REQ'D BY MULLION PRODUCT APPROVAL.
 OR PROVIDE SPECS FOR ALTERNATE SYSTEM.
 SEE PRODUCT APPROVAL FOR INSTALLATION.
 9-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR ONE HR FIRE RATED GLASS BLOCK
 ASSEMBLY REQUIRED BY TABLE 600 FBC.
 A)NOTE: GLASS BLOCK TO BE SAFETY GLASS
 IF UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEE SEC. 2405.2.2 FBC 2001.
 B)NOTE: GLASS BLOCK ASSEMBLY TO BE ONE
 HR FIRE RATED, NOT 45". TABLE 600 FBC.
 C)REVISE GLASS BLOCK DETAIL TO MATCH UL
 SPECIFICATIONS FOR ONE HR ASSEMBLY.
 10-SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEC. 1909.3 FBC 2001
 11-PROVIDE COMPLETE DETAIL AT RECESSED
 WINDOWS TO ALLOW FOR STORM SHUTTERS
 INSTALLATION.
 **NOTE: SEE PRODUCT APPROVAL FOR TRACK
 TO BE USED AND CONSIDER THE GLASS
 SEPARATION AND EDGE DISTANCE FOR
 APPROVED INSTALLATION.
 12-ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA. SEE SECTION
 602.1.ABC.1.2 CHAPTER 13 FBC 2001.
 B)OWNER/AGENT TO SIGN AND DATE FORM.
 13-WALL SECTIONS NOTE #14 AND VENT CALCS
 SIZE & SPACING DON'T MATCH. REVISE.
 14-SHEET S2: UPDATE NOTE #3. DESIGN TO
 BE UNDER FBC 2001 FOR 140MPH, NOT ASCE
 7-93 FOR 110MPH.
 15-SHEET S1: CLARIFY DIMENSION OF
 4'-1 1/2" ON SECTION 5.
 16-IDENTIFY ON PLANS ROOF ZONE 3 SHOWN
 DIAPHRAGM SCHEDULE ON SHEET S2.
 17-SHEET S1: REVISE LINTEL SCHEDULE TO
 MATCH PLANS. CHECK SIZE OF OPENINGS
 & LINTEL #. EG: SEE L-7 AND L-19.
 18-REVISE TRUSS ANCHOR SCHEDULE. UPLIFT
 LOADS AND LATERAL LOADS TO MATCH USP
 SPECIFICATIONS ACCORDING TO TYPE OF
 ANCHOR & # OF FASTENERS USED. PROVIDE
 ENGINEERING CALCULATIONS FOR LOADS
 DIFFERENT THAN THOSE SHOWN ON USP
 CATALOGUE.
 19-SHEET S2: CLARIFY WHY BLOCKING AT
 FRONT GABLE END IS SHOWN ON PARTIAL
 GABLE END AND NOT ALL THE WAY TO THE
 ENDS. SEC. 104.2.1.2 CITY AMENDMENTS.
 20-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 STRUCTURAL BUCK SPECS & REVISE DETAIL
 AS REQUIRED.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-31 Cont ID  
Sent By sgraham Date 2002-07-31 Time 16:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***