Plan Review Details - Permit 02071763
Plan Review Stops For Permit 02071763
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-19 Cont ID  
Sent By jwitmer Date 2002-08-19 Time 10:53 Rev Time 1.25
Received By jwitmer Date 2002-08-19 Time 10:53 Sent To  
Notes
2002-08-19 00:00:00***BUILDING PROVISO***
  
 1) SOILS REPORT TO INDICATE THAT A MIN-
 IMUM SAFE BEARING VALUE OF 2500 LBS HAS
 BEEN ACHIEVED. REPORT TO BE SUBMITTED TO
 THIS OFFICE BEFORE THE FOUNDATION IS
 POURED.
  
 2) ANCHORAGE NOTE SHEET #I F.B.C. 2507
 ISA NOTE FOR FLAT LATH NAILING 1 1/2"
 INTO HORIZONTAL MEMBERS.
 2504.2.2- ASTM C-1063 HI-RIB LATH IS
 TO BE NAILED OR STAPLED @ 4"O.C. /W
 1 3/4" PENETRATION INTO HORIZONTAL WOOD
 FRAMING MEMBERS.
  
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-13 Cont ID  
Sent By dpalmer Date 2002-08-13 Time 16:48 Rev Time 0.00
Received By dpalmer Date 2002-08-13 Time 16:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-09 Cont ID  
Sent By mcarsill Date 2002-08-09 Time 09:43 Rev Time 0.00
Received By mcarsill Date 2002-08-09 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-05 Cont ID  
Sent By pkrauss Date 2002-09-05 Time 10:34 Rev Time 0.35
Received By pkrauss Date 2002-09-05 Time 10:34 Sent To  
Notes
2002-09-05 00:00:00PROVISO:MECHANICAL PERMIT 02071944
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-14 Cont ID  
Sent By kstevens Date 2002-08-14 Time 10:03 Rev Time 0.00
Received By kstevens Date 2002-08-14 Time 10:03 Sent To  
Notes
2002-08-14 00:00:00PASSED/PROVISO
  
 WASH MACHINE C/O SHALL BE 4' ABOVE
 FINISHED FLOOR

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-01 Cont ID  
Sent By sgraham Date 2002-08-01 Time 09:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***