Plan Review Details - Permit 02071746
Plan Review Stops For Permit 02071746
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-08-12 Cont ID  
Sent By hpiskura Date 2002-08-12 Time 13:42 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-07 Cont ID  
Sent By hpiskura Date 2002-08-07 Time 11:11 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-08-07 00:00:00SHEET C2.WHERE WILL THE CONDUIT/COAX
 TERMINATE?WILL IT BE INTERIOR OR
 EXTERIOR TO THE BUILDING?MULTIPLE
 FLOOR PENETRATIONS?
  
 SHEET C5. FBC 705.6.1.2 REQUIRES THE
 FIRE STOP SYSTEM TO HAVE A T RATING OF
 ONE HOUR FOR ROOF PENETRATION AND TWO
 HOURS FOR FLOOR PENETRATION IN TYPE I
 AND II CONSTRUCTION.THE ASSEMBLY
 SHOWN DECLARES A MAXIMUM OF 3/4 HOUR.
 PLEASE REVISE AS NECESSARY.
  
 SHEET S1.ANTENNAS AND THEIR
 CONNECTION ARE NOT DETAILED.IF THE
 WORK IS NOT SHOWN ON THE PLANS A
 SEPARATE PERMIT, PLANS, ENGINEERING AND
 FEES WILL BE REQUIRED.SEE FBC 104.1.3.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-07 Cont ID  
Sent By dpalmer Date 2002-08-07 Time 06:23 Rev Time 0.00
Received By dpalmer Date 2002-08-07 Time 06:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-31 Cont ID  
Sent By sgraham Date 2002-07-31 Time 12:47 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***