Plan Review Details - Permit 02071700
Plan Review Stops For Permit 02071700
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-16 Cont ID  
Sent By btrobaug Date 2002-08-16 Time 07:05 Rev Time 0.00
Received By btrobaug Date 2002-08-16 Time 06:36 Sent To R
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-14 Cont ID  
Sent By pkrauss Date 2002-08-14 Time 12:22 Rev Time 0.35
Received By pkrauss Date 2002-08-14 Time 11:53 Sent To  
Notes
2002-08-14 00:00:00PROVISO:MECHANICAL PERMIT 02071719
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-10-07 Cont ID  
Sent By jleech Date 2002-10-07 Time 15:59 Rev Time 0.25
Received By jleech Date 2002-10-07 Time 15:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By jleech Date 2002-08-06 Time 18:15 Rev Time 0.33
Received By jleech Date 2002-08-06 Time 18:15 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By btrobaug Date 2002-08-16 Time 07:05 Rev Time 2.50
Received By lhatten Date 2002-08-25 Time 17:54 Sent To  
Notes
2002-08-27 00:00:00REVIEW & STAMPED PLANS 08/25/2002
 PRINT CARD 08/27/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-31 Cont ID  
Sent By sgraham Date 2002-07-31 Time 13:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***