Plan Review Stops For Permit 02071681 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-08-29 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-08-29 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-08-29 |
Time |
12:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-08-22 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-08-22 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-08-22 |
Time |
11:07 |
Sent To |
|
|
Notes |
2002-08-22 00:00:00 | SHOW THE DESIGN FOR THE FIRE SUPPRESSION | | SYSTEMS ON THE PERMIT PLANS.SEE FBC | | 104.3.1.1 ITEM #5, AND NFPA 13-99 | | CHAPTER 8 | | | | SEE THE COMMENTS DATED 8/7/02 RE: THE | | DECLARED PERMIT VALUATION. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-08-07 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-08-07 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-08-07 00:00:00 | A FIRE RATED EXIT ACCESS CORRIDOR IS | | REQUIRED BY FBC 704.2.4 FOR OCCUPANCY B | | >30 OCCUPANTS. PROVIDE THE FIRE DESIGN | | NUMBER FOR THE PARTITIONS AND SHOW THE | | RATED OPENING PROTECTIVES. | | | | SHOW THE FIRE RATED TENANT SEPARATION IN | | ACCORDANCE WITH FBC 704.3.1. | | | | DOORS SHOWN NEAR THE TOILET ROOM | | SWINGING INTO THE CORRIDOR DO NOT | | COMPLY WITH FBC 1012.1.4. | | | | SAFETY GLAZING IS REQUIRED FOR THE | | WINDOWS IN OFFICES 6, 7 AND 8.SEE FBC | | 2405.2.1 #3. | | | | THE $18000.00 DECLARED VALUATION IS TOO | | LOW FOR THIS SCOPE OF WORK.$50000.00 | | IS MORE REALISTIC, PLEASE PAY AN | | ADDITIONAL $710.40 PERMIT FEE TO THE | | CITY. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2002-08-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-08-27 |
Time |
18:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-08-27 |
Time |
18:37 |
Sent To |
|
|
Notes |
2002-08-27 00:00:00 | **************** NOTED ************** | | | | PLEASE NOTE THAT PLANS WERE NOTED, THAT | | DUE TO NEW ELECTRICAL SERVICE BEING | | ADDED TO SEPARATE BLDGS, IT WAS NOTED | | THAT ALL EXISTING ELECTRICAL FEEDS, | | LOW VOLTAGE AND HIGH VOLTAGE IS TO BE | | REMOVED AND TO COMPLETELY SEPARATE BLDG | | AND SEAL ALL PENATRATIONS. | | | | PLANS NOTED. 8/27/02 DV PALMER. | | MR RAYMOND NORDINE IS AWARE OF THIS | | REQ`MENT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2002-08-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-08-21 |
Time |
19:22 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2002-08-21 |
Time |
19:22 |
Sent To |
|
|
Notes |
2002-08-21 00:00:00 | ********** NOTE ************ | | | | 1)NOTE: NOTE, CALLED ENGINEER 8/21/02 | | TO VERIFY ACTUAL A?C LOAD ON NEW | | PROPOSED SERVICE TO BE INSTALLED. | | | | PLEASE NOTE, WAITING ON INFORMATION, | | SEE DV PALMER FOR ANY QUESTIONS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-08-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-08-02 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-08-02 |
Time |
15:03 |
Sent To |
|
|
Notes |
2002-08-02 00:00:00 | *************** UNSAT **************** | | | | PLEASE NOTE THAT AS PER FEILD INSPECTION | | VALUE OF JOB EXCEEDS SUBMITTED APPLIED | | VALUE. | | PLEASE ALSO NOTE THAT A CORRECTION | | NOTICE WAS ISSUED FOR ELECTRICAL DEMO | | AND TEMP POWER FOR CONSTRUCTION. | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | FOR THE ENTIRE SERVICE AND A BREAK | | DOWN ON EACH "MAINS" LOAD. SHOW EXISTING | | SERVICE ENTRANCE CONDUCTORS, SIZE AND | | TYPE. PLEASE NOTE THAT PER FIELD | | INSPECTION, CONDUCTOR AT POINT OF | | SERVICE HAS INSULATION DETERIORATING. | | PLEASE NOTE EXTENT OF WORK IN BLDG HAS | | FAR EXCEEDED ANY % FOR BRINGING UP TO | | CODE. PLEASE NOTE THAT SERVICE HAS | | MORETHAN 8' OF UNPROTECTED CONDUCTORS | | INSIDE THE BLDG.230-70 | | PLEASE NOTE THAT MAIN ELECTRICAL ROOM | | NEEDS TO BE LOCKED AND ONLY OPENED FOR | | QUALIFIED PERSONNEL. PLEASE NOTE FIRE | | RATING FOR MAIN ELECTRICAL ROOM TO BE | | 1 HR RATING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-07-31 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2002-07-31 |
Time |
15:24 |
Rev Time |
0.45 |
Received By |
jleahy |
Date |
2002-07-31 |
Time |
15:23 |
Sent To |
|
|
Notes |
2002-07-31 00:00:00 | NEED A LOAD CALCULATION ON THE 350 AMP | | MDP PANEL !!!!!!!!!!!!!! |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-08-22 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-08-22 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-08-22 |
Time |
08:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-08-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-08-02 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-08-02 |
Time |
15:21 |
Sent To |
|
|
Notes |
2002-08-02 00:00:00 | 1) EXISTING STAIR TOWER LOCATED ON | | SOUTH SIDE OF BUILDING REQUIRES | | EMERGENCY LIGHTING. | | | | 2) NEW FIRE ESCAPE CONNECTION ON THE | | NORTH SIDE IS REQUIRED TO BE COMPLETED, | | INSPECTED AND APPROVED PRIOR TO | | RECEIVING A C OF O. | | | | 3) CLOSET DOORS SWING TOO FAR INTO | | CORRIDOR. | | | | 4) THE CORRIDOR IS REQUIRED TO BE AT | | LEAST ONE HOUR FIRE RATED WITH RATED | | OPENING PROTECTIVES EQUIPPED WITH | | SELF-CLOSING DEVICES. THIS REQUIREMENT | | MUST BE MET SINCE NO FIRE SPRINKLER | | PROTECTION IS PRESENT WITHIN IT. | | | | 5) SEPARATIONS BETWEEN TENANTS MUST | | COMPLY WITH BUILDING CODE REQUIREMENTS. | | | | 6) PORTABLE FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | 7) ILLUMINATED EXIT SIGNS AND EMERGENCY | | LIGHTING ARE REQUIRED FOR TENANT | | SPACES. | | | | 8) PROVIDE SEPARATE PLANS AND PERMITS | | FOR FIRE ALARM SYSTEM. IT IS NOT KNOWN | | IF EXISTING SYSTEM IS OPERATIONAL. | | | | 9) THE ELEVATOR SHAFTS ARE TO BE | | MARKED "SHAFTWAY" IN SIX HIGH LETTERS | | ON A WHITE BACKGROUND. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2002-08-29 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-08-29 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2002-08-29 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-08-29 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|