Plan Review Details - Permit 02071681
Plan Review Stops For Permit 02071681
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-29 Cont ID  
Sent By hpiskura Date 2002-08-29 Time 14:26 Rev Time 0.00
Received By hpiskura Date 2002-08-29 Time 12:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-08-22 Cont ID  
Sent By hpiskura Date 2002-08-22 Time 11:32 Rev Time 0.00
Received By hpiskura Date 2002-08-22 Time 11:07 Sent To  
Notes
2002-08-22 00:00:00SHOW THE DESIGN FOR THE FIRE SUPPRESSION
 SYSTEMS ON THE PERMIT PLANS.SEE FBC
 104.3.1.1 ITEM #5, AND NFPA 13-99
 CHAPTER 8
  
 SEE THE COMMENTS DATED 8/7/02 RE: THE
 DECLARED PERMIT VALUATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-07 Cont ID  
Sent By hpiskura Date 2002-08-07 Time 09:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-08-07 00:00:00A FIRE RATED EXIT ACCESS CORRIDOR IS
 REQUIRED BY FBC 704.2.4 FOR OCCUPANCY B
 >30 OCCUPANTS. PROVIDE THE FIRE DESIGN
 NUMBER FOR THE PARTITIONS AND SHOW THE
 RATED OPENING PROTECTIVES.
  
 SHOW THE FIRE RATED TENANT SEPARATION IN
 ACCORDANCE WITH FBC 704.3.1.
  
 DOORS SHOWN NEAR THE TOILET ROOM
 SWINGING INTO THE CORRIDOR DO NOT
 COMPLY WITH FBC 1012.1.4.
  
 SAFETY GLAZING IS REQUIRED FOR THE
 WINDOWS IN OFFICES 6, 7 AND 8.SEE FBC
 2405.2.1 #3.
  
 THE $18000.00 DECLARED VALUATION IS TOO
 LOW FOR THIS SCOPE OF WORK.$50000.00
 IS MORE REALISTIC, PLEASE PAY AN
 ADDITIONAL $710.40 PERMIT FEE TO THE
 CITY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-27 Cont ID  
Sent By dpalmer Date 2002-08-27 Time 18:37 Rev Time 0.00
Received By dpalmer Date 2002-08-27 Time 18:37 Sent To  
Notes
2002-08-27 00:00:00**************** NOTED **************
  
 PLEASE NOTE THAT PLANS WERE NOTED, THAT
 DUE TO NEW ELECTRICAL SERVICE BEING
 ADDED TO SEPARATE BLDGS, IT WAS NOTED
 THAT ALL EXISTING ELECTRICAL FEEDS,
 LOW VOLTAGE AND HIGH VOLTAGE IS TO BE
 REMOVED AND TO COMPLETELY SEPARATE BLDG
 AND SEAL ALL PENATRATIONS.
  
 PLANS NOTED. 8/27/02 DV PALMER.
 MR RAYMOND NORDINE IS AWARE OF THIS
 REQ`MENT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-08-21 Cont ID  
Sent By dpalmer Date 2002-08-21 Time 19:22 Rev Time 0.75
Received By dpalmer Date 2002-08-21 Time 19:22 Sent To  
Notes
2002-08-21 00:00:00********** NOTE ************
  
 1)NOTE: NOTE, CALLED ENGINEER 8/21/02
 TO VERIFY ACTUAL A?C LOAD ON NEW
 PROPOSED SERVICE TO BE INSTALLED.
  
 PLEASE NOTE, WAITING ON INFORMATION,
 SEE DV PALMER FOR ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-08-02 Cont ID  
Sent By dpalmer Date 2002-08-02 Time 15:04 Rev Time 0.00
Received By dpalmer Date 2002-08-02 Time 15:03 Sent To  
Notes
2002-08-02 00:00:00*************** UNSAT ****************
  
 PLEASE NOTE THAT AS PER FEILD INSPECTION
 VALUE OF JOB EXCEEDS SUBMITTED APPLIED
 VALUE.
 PLEASE ALSO NOTE THAT A CORRECTION
 NOTICE WAS ISSUED FOR ELECTRICAL DEMO
 AND TEMP POWER FOR CONSTRUCTION.
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR THE ENTIRE SERVICE AND A BREAK
 DOWN ON EACH "MAINS" LOAD. SHOW EXISTING
 SERVICE ENTRANCE CONDUCTORS, SIZE AND
 TYPE. PLEASE NOTE THAT PER FIELD
 INSPECTION, CONDUCTOR AT POINT OF
 SERVICE HAS INSULATION DETERIORATING.
 PLEASE NOTE EXTENT OF WORK IN BLDG HAS
 FAR EXCEEDED ANY % FOR BRINGING UP TO
 CODE. PLEASE NOTE THAT SERVICE HAS
 MORETHAN 8' OF UNPROTECTED CONDUCTORS
 INSIDE THE BLDG.230-70
 PLEASE NOTE THAT MAIN ELECTRICAL ROOM
 NEEDS TO BE LOCKED AND ONLY OPENED FOR
 QUALIFIED PERSONNEL. PLEASE NOTE FIRE
 RATING FOR MAIN ELECTRICAL ROOM TO BE
 1 HR RATING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-31 Cont ID  
Sent By jleahy Date 2002-07-31 Time 15:24 Rev Time 0.45
Received By jleahy Date 2002-07-31 Time 15:23 Sent To  
Notes
2002-07-31 00:00:00NEED A LOAD CALCULATION ON THE 350 AMP
 MDP PANEL !!!!!!!!!!!!!!

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-08-22 Cont ID  
Sent By mcarsill Date 2002-08-22 Time 08:56 Rev Time 0.00
Received By mcarsill Date 2002-08-22 Time 08:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-02 Cont ID  
Sent By mcarsill Date 2002-08-02 Time 15:21 Rev Time 0.00
Received By mcarsill Date 2002-08-02 Time 15:21 Sent To  
Notes
2002-08-02 00:00:001) EXISTING STAIR TOWER LOCATED ON
 SOUTH SIDE OF BUILDING REQUIRES
 EMERGENCY LIGHTING.
  
 2) NEW FIRE ESCAPE CONNECTION ON THE
 NORTH SIDE IS REQUIRED TO BE COMPLETED,
 INSPECTED AND APPROVED PRIOR TO
 RECEIVING A C OF O.
  
 3) CLOSET DOORS SWING TOO FAR INTO
 CORRIDOR.
  
 4) THE CORRIDOR IS REQUIRED TO BE AT
 LEAST ONE HOUR FIRE RATED WITH RATED
 OPENING PROTECTIVES EQUIPPED WITH
 SELF-CLOSING DEVICES. THIS REQUIREMENT
 MUST BE MET SINCE NO FIRE SPRINKLER
 PROTECTION IS PRESENT WITHIN IT.
  
 5) SEPARATIONS BETWEEN TENANTS MUST
 COMPLY WITH BUILDING CODE REQUIREMENTS.
  
 6) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 7) ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING ARE REQUIRED FOR TENANT
 SPACES.
  
 8) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM SYSTEM. IT IS NOT KNOWN
 IF EXISTING SYSTEM IS OPERATIONAL.
  
 9) THE ELEVATOR SHAFTS ARE TO BE
 MARKED "SHAFTWAY" IN SIX HIGH LETTERS
 ON A WHITE BACKGROUND.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-08-29 Cont ID  
Sent By hpiskura Date 2002-08-29 Time 14:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-08-29 Cont ID  
Sent By hpiskura Date 2002-08-29 Time 14:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***