Plan Review Details - Permit 02071663
Plan Review Stops For Permit 02071663
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-09 Cont ID  
Sent By jwitmer Date 2002-09-09 Time 06:31 Rev Time 0.25
Received By jwitmer Date 2002-09-09 Time 06:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-19 Cont ID  
Sent By jwitmer Date 2002-08-19 Time 16:12 Rev Time 1.25
Received By jwitmer Date 2002-08-19 Time 16:12 Sent To  
Notes
2002-08-19 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02071663
 ADD: 802 SOUTHERN BLVD
 CONT: MHS CONTRACTING INC
 TEL: (561)586-7063
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 (1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) SWING DOORS
 B) STOREFRONT
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 4)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 5) 11-4.1.6(H) IF A PARTICULAR
 ENTRANCE IS NOT MADE ACCESSIBLE, APPRO-
 PRIATE ACCESSIBLE SIGNAGE INDICATING THE
 LOCATION OF THE NEAREST ACCESSIBLE
 ENTRANCE(S) SHALL BE INSTALLED AT OR
 NEAR THE INACCESSIBLE ENTRANCE, SUCH
 THAT A PERSON WITH DISABILITIES WILL
 NOT BE REQUIRED TO RETRACE THE APPROACH
 ROUTE FROM THE INNACCESSIBLE ENTRANCE.
  
 JIM WITMER
 BUILDING PLAN REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-31 Cont ID  
Sent By jleahy Date 2002-07-31 Time 10:24 Rev Time 0.45
Received By jleahy Date 2002-07-31 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-02 Cont ID  
Sent By mcarsill Date 2002-08-02 Time 16:24 Rev Time 0.00
Received By mcarsill Date 2002-08-02 Time 16:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-22 Cont ID  
Sent By ndenmark Date 2002-08-22 Time 07:58 Rev Time 0.33
Received By ndenmark Date 2002-08-22 Time 07:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-09-10 Cont ID  
Sent By kstevens Date 2002-09-10 Time 14:09 Rev Time 0.00
Received By kstevens Date 2002-09-10 Time 14:09 Sent To  
Notes
2002-09-10 00:00:00REVISION REQUIRED - DRINKING FOUNTAIN
 SHALL NOT DRAIN INTO WET VENT FOR TOILET
 ROOMS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-09 Cont ID  
Sent By kstevens Date 2002-08-09 Time 19:45 Rev Time 0.00
Received By kstevens Date 2002-08-09 Time 19:45 Sent To  
Notes
2002-08-09 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PER TABLE 403.1 A SERVICE SINK IS
 REQUIRED.
 2) SUBMIT A SANITARY AND A WATER RISER
 DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377