Plan Review Details - Permit 02071609
Plan Review Stops For Permit 02071609
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-03-18 Cont ID  
Sent By lmartine Date 2003-03-18 Time 16:11 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-01-16 Cont ID  
Sent By jwitmer Date 2003-01-16 Time 08:58 Rev Time 1.25
Received By jwitmer Date 2003-01-16 Time 08:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-26 Cont ID  
Sent By jwitmer Date 2002-12-26 Time 14:41 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-05 Cont ID  
Sent By hpiskura Date 2002-11-05 Time 08:27 Rev Time 0.00
Received By hpiskura Date 2002-11-04 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-14 Cont ID  
Sent By jwitmer Date 2002-08-14 Time 18:29 Rev Time 1.25
Received By jwitmer Date 2002-08-14 Time 18:29 Sent To  
Notes
2002-08-14 00:00:00BUILDING PLAN REVIEW
 PERMIT:02071609
 ADD:1400 NORTHPOINT
 CONT: LTI DEVELOPMENT
 TEL: (561)478-1841
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) INDICATE BUILDING TYPE, PROTECTED OR
 NON-PROTECTED, FIRE SPRINKLERED? TABLE
 500 / OCCUPANCY VS SQ FT?
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) SHEET A-1.1 1 HR DIMISSING WALL DE-
 TAIL, DRYWALL NOR TRACK GO ALL THE WAY
 TO THE ROOF DECK. 705.6
  
 4) 705.7.1 FIRE RESISTANT JOINT SYSTEMS
 THE JOINT LEFT BETWEEN THE WALL AND
 THE FLOOR/CEILING ASSEMBLY OR CEILING/
 ROOF ASSEMBLY SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A TIME PERIOD NOT LESS THAN REQUIRED
 FOR THE WALL.
  
 5) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 6) 1005.2 DEAD END POCKETS. EXIT ACCESS
 SHALL BE SO ARRANGED THAT DEAD END POC-
 KETS OR HALLWAYS IN EXCESS OF 20 FT LONG
 SHALL NOT OCCUR.
  
 7) PROVIDE ADDITIONAL INFORMATION ON
 ELECTRIC LOCKING MECHANISMS, 1012.6.1.
 PROVIDE MANUFACTURERS SPEC.
  
 8) PROVIDE ROOM USAGE, PLEASE INDICATE
 ON FLOOR PLAN.
  
 9)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-03-21 Cont ID  
Sent By dpalmer Date 2003-03-21 Time 10:06 Rev Time 1.25
Received By dpalmer Date 2003-03-21 Time 10:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-03-18 Cont ID  
Sent By dpalmer Date 2003-03-18 Time 10:43 Rev Time 0.50
Received By dpalmer Date 2003-03-18 Time 10:43 Sent To  
Notes
2003-03-18 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SHOW AND NOTE REVISIONS
 ON ALL SHEETS. PLEASE SHOW AND LABEL
 ALL W/ CLOUDS OR TRIANGLES.
 PLEASE ALSO REVISE PANEL SCHEDULES TO
 CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2003-01-07 Time 18:06 Rev Time 1.00
Received By dpalmer Date 2003-01-07 Time 18:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-11-26 Cont ID  
Sent By dpalmer Date 2002-11-26 Time 07:04 Rev Time 0.50
Received By dpalmer Date 2002-11-26 Time 07:00 Sent To  
Notes
2002-11-26 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, NOTE FROM FIRST
 TWO REVIEWS WERE NOT MET.
 PLEASE NOTE, NO EQUIPMENT GROUNDING
 METHOD IS SHOWN BETWEEN MAINS/PANELS,
 TRANSFORMERS???? 250-24,250-30,250-122
 ETC.
  
 2) PLEASE TAKE OUT OLD SHEETS AND INSERT
 NEW SHEETS FOR TWO COMPLTE SETS FOR
 REVIEW. PLEASE NOTE, ONE OLD SET MAY BE
 SUBMITTED FOR REFERENCE IF NEEDED.
  
 3)NOTE: PLEASE SEE ATTACHED LETTER PER
 FS. 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, PLEASE CALL. IF A MEETING
 WOULD BE REQ`D TO GO OVER PLANS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 11:08 Rev Time 1.00
Received By dpalmer Date 2002-10-31 Time 11:07 Sent To  
Notes
2002-10-31 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE NOTE/CLARFIY MISSING
 EQUIPMENT GROUNDIGN CONDUCTORS BETWEEN
 PANELS/MAINS/TRANSFORMERS ETC. 250-142
 250-122,250-30
  
 2)NOTE: PLEASE NOTE PANEL "B" IS NOT
 SHOWN AS BEING FED FROM ANYWHERE?
 PLEASE SHOW.
  
 3)NOTE: PLEASE NOTE NO MAIN ON LOAD SIDE
 OF TRANSFORMER INTO PANEL "A". LIGHTING
 AND APPL PANELBOARD.384-16,
  
 4)NOTE: PLEASE SHOW WHERE GRND IS BEING
 ATTACHED FOR TRANSFORMER. 250-30
 AND FOR MAIN DISC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-08-02 Cont ID  
Sent By jleahy Date 2002-08-02 Time 16:26 Rev Time 1.00
Received By jleahy Date 2002-08-02 Time 16:22 Sent To  
Notes
2002-08-02 00:00:00CONDUIT TO TRANSFORMER HAS TWO SETS OF
 WIRES SHOWN 4-#3 AND 4-#8 ????????????
  
 FOURTH WIRE IS IT A NEUTRAL OR A GROUND?
  
 PANELS ON THE SECONDARY OF THE TRANSFORM
 HAVE NO MAINS SEE 384-16 E!!!!!!!!!!!!!A

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-03-27 Cont ID  
Sent By mcarsill Date 2003-03-27 Time 16:44 Rev Time 0.00
Received By mcarsill Date 2003-03-27 Time 16:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-01-08 Cont ID  
Sent By nmccray Date 2003-01-08 Time 15:04 Rev Time 0.00
Received By nmccray Date 2003-01-08 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-14 Cont ID  
Sent By mcarsill Date 2002-11-14 Time 09:02 Rev Time 0.00
Received By mcarsill Date 2002-11-14 Time 09:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-02 Cont ID  
Sent By mcarsill Date 2002-08-02 Time 17:11 Rev Time 0.00
Received By mcarsill Date 2002-08-02 Time 17:11 Sent To  
Notes
2002-08-02 00:00:001) PLEASE INDICATE ON THE PLANS WHERE
 THE TENANT DEMISING WALLS ARE LOCATED.
  
 2) PLANS DO INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 3) IT APPEARS THAT NOT ENOUGH
 ILLUMINATED EXIT SIGNS OR EMERGENCY
 LIGHTING EQUIPMENT ARE PRESENT WITHIN
 THE SPACE.
  
 4) SOME DEAD-ENDS EXIST THAT MAY EXCEED
 BUILDING CODE REQUIREMENTS.
  
 5) ROOMS SHOULD BE LABELED ON THE
 FLOOR PLAN.
  
 6) NO MENTION OF FIRE SPRINKLERS, FIRE
 ALARM OR FIRE EXTINGUISHER EQUIPMENT
 WITHIN THE TENANT SPACE. PLEASE ADVISE
 AND REVISE AS NECESSARY.
  
 7) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS.
  
 8) PLEASE PROVIDE MORE INFORMATION ON
 ELECTRONIC LATCHES. SECURITY DEVICES
 SHALL NOT INTERFERE WITH ANY EXITING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-03-20 Cont ID  
Sent By sthyng Date 2003-03-20 Time 11:13 Rev Time 0.00
Received By sthyng Date 2003-03-20 Time 11:13 Sent To  
Notes
2003-03-20 00:00:00TO COMM BOARD #41
 ELECTRICAL REVISIONS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-10 Cont ID  
Sent By dpalmer Date 2003-03-10 Time 12:33 Rev Time 0.00
Received By dpalmer Date 2003-03-10 Time 12:33 Sent To  
Notes
2003-03-10 00:00:00TO COMM BOARD #29 ALL TRADES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 17:51 Rev Time 0.00
Received By dpalmer Date 2003-01-02 Time 17:51 Sent To  
Notes
2003-01-07 00:00:00TO COMM BOARD #19.
  
 CHECKED OFF FOR BLDG,ELEC FIRE AND PLUMB
 SEE NEW SHEETS REVISEING FLAME SPREAD
 INFO AND FLOOR PLAN.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-25 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 18:03 Rev Time 0.00
Received By btrobaug Date 2002-11-25 Time 18:03 Sent To  
Notes
2002-11-25 00:00:00TO
 COMM BOARD # 31./WRT

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-03-18 Cont ID  
Sent By pkrauss Date 2003-03-18 Time 11:24 Rev Time 0.30
Received By pkrauss Date 2003-03-18 Time 11:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-01-16 Cont ID  
Sent By pkrauss Date 2003-01-16 Time 12:53 Rev Time 0.10
Received By pkrauss Date 2003-01-16 Time 12:53 Sent To  
Notes
2003-01-16 00:00:00APPROVED MECHANICAL PERMIT 02101430

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-23 Cont ID  
Sent By pkrauss Date 2002-12-23 Time 09:22 Rev Time 0.50
Received By pkrauss Date 2002-12-23 Time 09:22 Sent To  
Notes
2002-12-23 00:00:00PROVISO:
  
 AS PER 2001 FBC 1511.7, ROOF MOUNTED
 MECHANICAL UNITS SHALL BE MOUNTED ON
 CURBS RAISED A MINIMUM OF 8" ABOVE THE
 ROOF SURFACE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-10-30 Cont ID  
Sent By pkrauss Date 2002-10-30 Time 11:41 Rev Time 0.40
Received By pkrauss Date 2002-10-30 Time 11:16 Sent To  
Notes
2002-10-30 00:00:00DENIED:
  
 1.PLEASE PROVIDE EQUIPMENT SCHEDULE
 ON PLAN.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 3.PLEASE INDICATE DUCT SMOKE DETECTORS
 AS PER 2001 FBC(M) 606.2.1 & 606.2.2
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-08-13 Cont ID  
Sent By pkrauss Date 2002-08-13 Time 07:47 Rev Time 0.40
Received By pkrauss Date 2002-08-13 Time 07:47 Sent To  
Notes
2002-08-13 00:00:00DENIED:
  
 1. THE "SYSTEM SIZING SUMMARY" INDICATES
 SYSTEMS 1A, 2 & 3.PLAN INDICATES
 SYSTEMS 1A & B, 2A, B, & C, AND 3.
 PLEASE PROVIDE SCHEDULE FOR THE RTU
 EQUIPMENT.
  
 2. PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) TABLE 403.3 OR ASHRAE
 62-89.
  
 3. RETURN AIR DUCTS & GRILLES ARE NOT
 SIZED.
  
 4. AREA SERVED BY RTU #3 APPEARS TO HAVE
 A RETURN AIR PLENUM. PLEASE NOTE
 AS PER 2001 FBC(M) 602.2.1, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON-
 COMBUSTIBLE OR SHALL HAVE A FLAME
 SPREAD INDEX IF NOT MORE THAN 25 & A
 SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 50 WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 7 Status P Date 2003-03-24 Cont ID  
Sent By kstevens Date 2003-03-24 Time 11:04 Rev Time 0.25
Received By kstevens Date 2003-03-24 Time 11:04 Sent To  
Notes
2003-03-24 00:00:00REVISION OK - REMOVED F.S. AND W/HEATER
 INCREASED SIZE OF OTHER W/HEATER

Review Stop P PLUMBING
Rev No 6 Status F Date 2003-03-22 Cont ID  
Sent By kstevens Date 2003-03-22 Time 07:19 Rev Time 0.50
Received By kstevens Date 2003-03-22 Time 07:19 Sent To  
Notes
2003-03-22 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 3.1 FLOOR SINK NOT VENTED. SEE
 PROVISO WHEN PERMIT ISSUED.
 2) SHT 3.2 SANITARY RISER DIAGRAM, NO
 FLOOR SINK SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 5 Status N Date 2003-01-11 Cont ID  
Sent By kstevens Date 2003-01-11 Time 15:55 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-01-11 Cont ID  
Sent By kstevens Date 2003-01-11 Time 15:37 Rev Time 1.00
Received By kstevens Date 2003-01-11 Time 15:36 Sent To  
Notes
2003-01-11 00:00:00PASSED/PROVISO
  
 SHT'S 3.1 & 3.2, REVISION REQUIRED FOR
 FLOOR SINK NOT SHOWN FOR ROOM 106. SEE
 RED LINE CORRECTIONS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-12-17 Cont ID  
Sent By kstevens Date 2002-12-16 Time 18:44 Rev Time 1.00
Received By kstevens Date 2002-12-16 Time 18:44 Sent To  
Notes
2002-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW:
 COVER SHEET INDICATES WAREHOUSE AND
 SHOWROOM. PLEASE SHOW SQUARE FOOTAGE FOR
 OFFICE, WAREHOUSE, AND SHOWROOM INDIVID-
 UALLY. PLEASE INDICATE PRODUCT THAT WILL
 BE ON SALES ROOM FLOOR AND WAREHOUSE.
 2) FROM PREVIOUS REVIEW:
 PLEASE SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLE 403.1, AND TABLE
 1003.1 (BLDG. CODE). SHOW NUMBER OF PER-
 SONS REQUIRED FOR EACH OCCUPANCY.
 3) FROM PREVIOUS REVIEW:
 PLEASE SUBMIT DETAILS FOR SHOWERS IN RMS
 #104, 105, & 126. SEE SECTION 11-4.21
 SHOWER STALLS. SHOW COMPLIANCE FOR ALL
 SUBSECTIONS, 4.21.2 SIZE/CLEARANCES,
 4.21.3 SEAT, 4.21.4 GRAB BARS, 4.21.5
 CONTROLS, 4.21.6 SHOWER UNIT, 4.21.7
 CURBS. FIGURES 35(A) OR (B), & FIGURE
 57(A) OR (B). - IF BATHING FACILITIES
 ARE PROVIDED ON A SITE, THEN EACH SUCH
 PUBLIC OR COMMON USE BATHING FACILITY
 SHALL COMPLY WITH 11-4.23. SECTION
 11-4.1.2(6).
 4) SHT 3.2 OF 11, SANITARY RISER DIAGRAM
 FLOOR SINK NOT VENTED, AND SINK IN ROOM
 #106 IS NOT SHOWN ON RISER DIAGRAM.
 5) MANUF. INFO. REQUIRED FOR INSTA HOT
 BEING USED. REQUIRES A LISTING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-11-06 Cont ID  
Sent By kstevens Date 2002-11-06 Time 08:41 Rev Time 2.50
Received By kstevens Date 2002-11-06 Time 08:40 Sent To  
Notes
2002-11-06 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) COVER SHEET INDICATES WAREHOUSE AND
 SHOWROOM. PLEASE SHOW SQUARE FOOTAGE FOR
 OFFICE, WAREHOUSE, AND SHOWROOM INDIVID-
 UALLY. PLEASE INDICATE PRODUCT THAT WILL
 BE ON SALES ROOM FLOOR AND WAREHOUSE.
 2) RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE TO BLDG.
 3) PLEASE SUBMIT CALCULATIONS FOR MINIM-
 UM FACILITIES PER TABLE 403.1, AND TABLE
 1003.1 (BLDG CODE). SHOW NUMBER OF PER-
 SONS REQUIRED FOR EACH OCCUPANCY.
 4) WHAT WILL BULL PEN BE USED FOR?
 5) PLEASE SUBMIT DETAILS FOR SHOWERS IN
 #104, 105, & 126. SEE SECTION 11-4.21
 SHOWER STALLS. SHOW COMPLIANCE FOR ALL
 SUBSECTIONS, 4.21.2 SIZE/CLEARANCES,
 4.21.3 SEAT, 4.21.4 GRAB BARS, 4.21.5
 CONTROLS, 4.21.6 SHOWER UNIT, 4.21.7
 CURBS. FIGURS 35(A) OR (B), & FIGURE
 57(A) OR (B)
 6) SHTS 3.1 OF 11 AND 3.2 OF 11, P/T
 FROM WATER HEATERS SHALL DRAIN TO A
 FLOOR SINK. FLOOR DRAIN ARE NOT AN APPRO
 VED INDIRECT WASTE RECEPTOR.
 7) SHT 3.2 OF 11, SANITARY AND WATER
 RISER DIAGRAMS DO NOT REFLECT THE FLOOR
 PLAN. URNALS ARE ON WALL BEHIND MOP SINK
 NOT ON THE OTHER SIDE OF ROOM. W/C'S AND
 LAVS. MISSING OFF BOTH RISERS. WATER
 HAMMER ARRESTOR LOCATION SHALL BE NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE NOT
 AT THE TOP OF RISER IN CEILING PER PDI-
 WH 201 AND MANUFACTURE INSTALLATION IN-
 STRUCTIONS. WATER HAMMER ARRESTORS ARE
 REQUIRED PER 604.9. AIR CHAMBERS ARE NOT
 APPROVED.
 8) SHT 3.2 OF 11 WATER RISER DIAGRAM,
 WATER PIPING TO WATER HEATER BY MOP SINK
 NOT SHOWN ON RISER.
 9) THERMAL EXPANSION CONTROL REQUIRED
 PER 607.3 AND 607.3.2. PLEASE GIVE DE-
 TAIL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-12 Cont ID  
Sent By kstevens Date 2002-08-12 Time 15:18 Rev Time 0.00
Received By kstevens Date 2002-08-12 Time 15:18 Sent To  
Notes
2002-08-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1 ROOM 106 PRIVATE BATHROOM,
 PLEASE SHOW DETAILS FOR SHOWER. BACKING
 REQUIRED FOR GRAB BARS, AND SEAT FOR
 SHOWER. CURB TO BE MAX 1/2", CONTROLS
 SHALL BE WITHIN 38" TO 48" OFF FLOOR,
 SHOW WHICH WALL CONTROL AND SHOWER HEAD
 ARE ON. LAV SHALL HAVE A REMOVABLE VANI-
 TY OR BE CENTERED (2') ON THE 48"X30"
 CLEAR FLOOR SPACE. (PARALLEL APPROACH)
 PLEASE PROVIDE DETAILS FOR ADAPTABLE
 BATHROOM. 11-4.21 & ALL SUBSECTIONS
 2) SHT A-1 BOTTLED WATER COOLER SHALL
 COMPLY WITH ARI-1010. PLEASE PROVIDE
 MANUF. INFORMATION.
 3) SHT A-6.1 SANITARY RISER DIAG. FIX-
 TURES IN ROOM #114 (HDCP W/C, JANITOR
 SINK, URNALS, ECT SHALL NOT DRAIN INTO
 THE VENT FOR THE W/C IN THE FIRST STALL.
 PLEASE DRAIN THESE FIXTURES DOWNSTREAM
 OF THE VENT FOR THAT W/C. ALSO CHANGE
 SHT A-5 FLOOR PLAN.
 4) SHT A-6.1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 FIXTURES IN AN "EFFECTIVE RANGE" NOT AT
 THE TOP OF DROPS AS SHOWN. PDI-WH 201
 AND MANUF. INSTALL. INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377