Plan Review Details - Permit 02071381
Plan Review Stops For Permit 02071381
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-30 Cont ID  
Sent By hpiskura Date 2002-09-30 Time 13:41 Rev Time 0.00
Received By hpiskura Date 2002-09-30 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By hpiskura Date 2002-08-06 Time 10:41 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-09-19 Cont ID  
Sent By dpalmer Date 2002-09-19 Time 11:57 Rev Time 0.25
Received By dpalmer Date 2002-09-19 Time 11:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-25 Cont ID  
Sent By dpalmer Date 2002-07-25 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2002-07-25 Time 13:24 Sent To  
Notes
2002-07-25 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE CIRCUITING NEEDS TO
 BE SHOWN ON PLANS AND CORRELATE WITH A
 SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE CLARIFY NEW OR/ EXISTING
 EM LTS? EXIT LTS ARE SHOWN AS NEW.
  
 3)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 RECEPTS PER 210-62
  
 4)NOTE: PLEASE CLARIFY SIGN CIRCUIT
 REQ`D PER 600-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-08-06 Cont ID  
Sent By hpiskura Date 2002-08-06 Time 10:41 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-09-24 Cont ID  
Sent By mcarsill Date 2002-09-24 Time 13:14 Rev Time 0.00
Received By mcarsill Date 2002-09-24 Time 13:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-02 Cont ID  
Sent By mcarsill Date 2002-08-02 Time 15:34 Rev Time 0.00
Received By mcarsill Date 2002-08-02 Time 15:34 Sent To  
Notes
2002-08-02 00:00:001) PLEASE CLEARLY ILLUSTRATE ALL
 ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHT FIXTURES.
  
 2) ALL ELECTRICAL, MECHANICAL, AND
 SERVICE ROOMS ARE REQUIRED TO BE AT
 LEAST ONE HOUR FIRE RATED WITH RATED
 OPENING PROTECTIVE DEVICES IF FIRE
 SPRINKLERS ARE NOT PRESENT.
  
 3) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED WITHIN TENANT SPACES.
  
 4) SECURITY DEVICES INSTALLED ON INGRESS
 AND EGRESS DOORS SHALL NOT INTERFERE
 WITH EXITING.
  
 5) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED FOR WALLS AND
 CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-25 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 17:47 Rev Time 0.00
Received By btrobaug Date 2002-11-25 Time 17:47 Sent To M
Notes
2002-11-25 00:00:00IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-08-06 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 17:47 Rev Time 0.00
Received By tjonseck Date 2002-10-28 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-10-02 Cont ID  
Sent By pschmitz Date 2002-10-02 Time 10:53 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-10-02 00:00:00PROVISO: SEE SHT 4. PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-07-26 Cont ID  
Sent By kstevens Date 2002-07-26 Time 10:47 Rev Time 0.00
Received By kstevens Date 2002-07-26 Time 10:46 Sent To  
Notes
2002-07-26 00:00:00PASSED/PROVISO
  
 WATER COOLER REQUIRED - SHALL COMPLY
 WITH ARI-1010 - INSPECTOR TO SEE CAPPED
 SANITARY/WATER LINES BEFORE COVERING.

Review Stop Z ZONING
Rev No 1 Status N Date 2002-09-19 Cont ID  
Sent By hpiskura Date 2002-09-19 Time 09:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***