Plan Review Details - Permit 02070816
Plan Review Stops For Permit 02070816
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-08 Cont ID  
Sent By jwitmer Date 2002-08-08 Time 13:27 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-08-08 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02070816
 ADD: 6087 UNITED STREET
 CONT: CONTINENTAL HOMES
 TEL: (954)428-4854
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 *****PROVISO*****
  
 PERMITS: 02070816 6087 UNITED ST
 02070818 6091 UNITED ST
 02070820 6997 UNITED ST
 02070823 6101 UNITED ST
 PROVIDE SITE SPECIFIC ENGINEERING FOR
 THE FOLLOWING PRODUCTS BEFORE BUCK
 INSPECTION:
 1) CERTIFIED TESTING LABS
 NORANDEX SERIES 437 ALUM HORIZONTAL
 SLIDERS
 2) FENESTRATION TESTING LABS
 NORANDEX SERIES 500 ALUM SLIDING
 GLASS DOORS.
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-29 Cont ID  
Sent By dpalmer Date 2002-07-29 Time 15:11 Rev Time 0.00
Received By dpalmer Date 2002-07-29 Time 15:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-08 Cont ID  
Sent By mcarsill Date 2002-08-08 Time 17:21 Rev Time 0.00
Received By mcarsill Date 2002-08-08 Time 17:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-07 Cont ID  
Sent By pkrauss Date 2002-08-07 Time 16:18 Rev Time 0.35
Received By pkrauss Date 2002-08-07 Time 15:14 Sent To  
Notes
2002-08-07 00:00:00PROVISO:MECHANICAL PERMIT 02070890
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 REFRIGERANT LINES SHALL BE TESTED AS PER
 2001 FBC(M) 1108.1.TEST SHALL BE PER-
 FORMED WITH AN INERT DRIED GAS (SUCH AS
 NITROGEN) 2001 FBC(M) 1108.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-07-26 Cont ID  
Sent By kstevens Date 2002-07-26 Time 09:44 Rev Time 0.00
Received By kstevens Date 2002-07-26 Time 09:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-19 Cont ID  
Sent By sgraham Date 2002-07-19 Time 15:03 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***