Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-26 Cont ID  
Sent By dpalmer Date 2002-07-26 Time 13:28 Rev Time 0.00
Received By dpalmer Date 2002-07-26 Time 13:28 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-10-10 Cont ID  
Sent By pkrauss Date 2002-10-10 Time 16:53 Rev Time 0.30
Received By pkrauss Date   Time   Sent To  
Notes
2002-10-10 00:00:00REVISION MECH PERMIT 02070341

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-09 Cont ID  
Sent By pkrauss Date 2002-08-09 Time 08:34 Rev Time 0.30
Received By pkrauss Date 2002-08-09 Time 08:32 Sent To  
Notes
2002-08-09 00:00:00MECHANICAL PERMIT 02070341
 ADDED FRESH AIR CALCS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-30 Cont ID  
Sent By pkrauss Date 2002-07-30 Time 09:44 Rev Time 0.25
Received By pkrauss Date   Time   Sent To  
Notes
2002-07-30 00:00:00MECH PERMIT 02070341

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-07-26 Cont ID  
Sent By pkrauss Date 2002-07-26 Time 07:45 Rev Time 0.35
Received By pkrauss Date 2002-07-26 Time 07:39 Sent To  
Notes
2002-07-26 00:00:00DENIED:MECHANICAL PERMIT 02070341
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 PLEASE NOTE ENERGY CALCS INDICATE A 4
 TON SYSTEM & PLANS INDICATE A 3.5 TON
 SYSTEM.THE CONDITIONED SPACE IS 1975
 SQ FT.PLEASE CORRLEATE THE EQUIPMENT
 SPECIFIED WITH THE ENERGY & MANUAL J
 CALCS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-07-20 Cont ID  
Sent By jleech Date 2002-07-20 Time 07:55 Rev Time 0.33
Received By jleech Date 2002-07-20 Time 07:54 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-07-29 Cont ID  
Sent By lhatten Date 2002-07-29 Time 17:09 Rev Time 2.50
Received By lhatten Date 2002-07-27 Time 17:08 Sent To  
Notes
2002-07-29 00:00:00REVIEW & STAMPED PLANS 07/27/2002
 CALC. FEES & PRINT CARDS 07/29/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-15 Cont ID  
Sent By sgraham Date 2002-07-15 Time 10:59 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***