Plan Review Details - Permit 02061879
Plan Review Stops For Permit 02061879
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-07-03 Cont ID  
Sent By rbrown Date 2003-07-03 Time 14:50 Rev Time 0.00
Received By rbrown Date 2003-07-03 Time 14:50 Sent To  
Notes
2003-07-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 THE ORIGINAL APPLICATION WAS FOR
 STRUCTURAL REPAIRS AS PER THE DETAILS
 PROVIDED BY BOTKIN PARSSI & ASSOCIATES,
 P.E.THE SUBMITTED 'REVISION' IS FOR
 THE CONSTRUCTION OF A NEW UTILITY ROOM
 ADDITION AND NEW CAR PORT TO DETAILS
 PROVIDED BY A DIFFERENT ENGINEER, WALTER
 KARPINIA, P.E.THIS WILL REQUIRE THE
 SUBMITTAL OF A SEPARATE PERMIT
 APPLICATION WITH FEES BASED ON THE
 VALUE OF THE NEW WORK.THE PLANS HAVE
 NOT BEEN REVIEWED.THE ELECTRICAL AND
 PLUMBING SUB-CONTRACTORS MUST 'SIGN-ON',
 OR SEPARATE SUB-PERMIT APPLICATIONS WILL
 BE REQUIRED.
  
 REPLACEMENT OF WINDOWS.THE SCOPE OF
 THE ISSUED PERMIT IS STRUCTURAL REPAIR.
 THIS WOULD NOT COVER GENERAL WINDOW
 REPLACEMENT.SUBMIT A COPY OF THE
 CONTRACT TOGETHER WITH A KEY PLAN AND
 SCHEDULE TO SHOW HOW MANY, AND WHICH,
 WINDOWS ARE TO BE REPLACED.
  
 NOTE THAT THE LEFT ELEVATION REFERS TO
 THE FAMILY ROOM AS 'NEW WOOD ADDITION'.
 AMEND THE PLANS TO CLARIFY BEFORE
 SUBMITTAL.
  
 FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-26 Cont ID  
Sent By rbrown Date 2003-03-26 Time 16:47 Rev Time 0.00
Received By rbrown Date 2003-03-26 Time 15:42 Sent To E
Notes
2003-03-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 *NOTE*: A HISTORIC HOLD WAS PUT ON THIS
 PROPERTY ON 2/21/03.ANY CHANGE IN THE
 SCOPE OF WORK WILL REQUIRE SUBMITTAL OF
 PLANS FOR APPROVAL BY HISTORIC.CONTACT
 SHERRY PILAND ON (561) 659 8031 EXT 8362
  
 1) THE PROPOSED 'REVISIONS' ARE OUTSIDE
 THE SCOPE OF THE ISSUED PERMIT, WHICH
 ONLY COVERS STRUCTURAL REPAIRS TO THE
 EXISTING RESIDENCE.A SEPARATE PERMIT
 APPLICATION, WITH ARCHITECTURAL AND/OR
 STRUCTURAL PLANS, WILL BE REQUIRED FOR
 THE NEW CAR PORT, FRONT AND REAR PORCHES
 AND NEW UTILITY ROOM. THE ELECTRICAL AND
 PLUMBING SUB-CONTRACTORS MUST 'SIGN-ON',
 OR SEPARATE SUB-PERMIT APPLICATIONS WILL
 BE REQUIRED.
  
 2) REPLACEMENT OF WINDOWS.THE SCOPE OF
 THE ISSUED PERMIT IS STRUCTURAL REPAIR.
 THIS WOULD NOT COVER GENERAL WINDOW
 REPLACEMENT.SUBMIT A COPY OF THE
 CONTRACT TOGETHER WITH A KEY PLAN AND
 SCHEDULE TO SHOW HOW MANY, AND WHICH,
 WINDOWS ARE TO BE REPLACED.
  
 3) THE SUBMITTED COPIES OF THE PREMDOR
 DOUBLE INSWING WOOD DOOR PRODUCT
 APPROVAL NOA# 01-1127.16 ARE MISSING
 DRAWING SHEET 1 OF 4.NOTE: THE LAYOUTS
 SUBMITTED WITH THE PROPOSED 'REVISION'
 DO NOT SHOW ANY DOUBLE INSWING DOOR.
 PLEASE CLARIFY.
  
 4) DRAWING SHEETS 1 THRU 3 OF 3, OF THE
 SOUTHEASTERN METALS MANUFACTURING STEEL
 STORM PANEL SHUTTER PRODUCT APPROVAL
 NOA# 02-0809.02 ARE NOT LEGIBLE DUE TO
 POOR COPY QUALITY.SUBMIT LEGIBLE
 COPIES.ALSO AN INSTALLATION SCHEDULE
 AND KEY PLAN SHALL BE SUBMITTED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-09 Cont ID  
Sent By sthyng Date 2003-03-21 Time 10:59 Rev Time 0.00
Received By rbrown Date 2002-08-09 Time 09:39 Sent To  
Notes
2002-08-09 00:00:00PER LUIS MARTINEZ

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-01 Cont ID  
Sent By dpalmer Date 2003-07-01 Time 07:36 Rev Time 0.75
Received By dpalmer Date 2003-07-01 Time 06:50 Sent To M
Notes
2003-07-01 00:00:00********** NOTE ************
  
 REDLINED 210-52D/210-11C-3
 BATH TO BE 20A/#12, SHOWN AS 15A/#14

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-06-27 Time 10:40 Rev Time 0.50
Received By dpalmer Date 2003-04-03 Time 04:15 Sent To P
Notes
2003-04-03 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PLANS, RISER
 AND PANEL SCHEDULE. NOTES, MENTION 200A
 PANEL W/ 200A MCB AND THE REST SHOW 150A
 ???
  
 2)NOTE: PLAN SHOWS WHAT APPEARS TO BE
 A METER/MAIN COMBO AND RISER SHOWS A
 SEPARATE DISC?
  
 3)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT(S) PER 210-52D/210-11C-3
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12 ON PANEL
 SCHEDULE.
 5)NOTE: PLEASE SEE NOTES ON PLANS, THEY
 MENTION ALL WORK TO BE DONE PER PALM
 BEACH COUNTY, PLEASE NOTE, WORK ADDRESS
 IS IN CITY OF WEST PALM BEACH.
  
 6)NOTE: PLEASE SIZE OCP FOR AHU PER
 424-3. SHOWN AS 50A, MIN FOR 10KW IS
 60A.
  
 7)NOTE: PLEASE SEE MISSING RECEPT FOR
 PENINSULAR PER 210-52C-1,2,3,ETC.
 PLEASE NOTE, ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECTED
 PER 210-8-A-6, NOT JUST RECEPTS W/IN 6'
 OF SINK AS MENTIONED IN ELEC. NOTE #3.
  
 8)NOTE: PLEASE SEE MISSING SD AT THE
 BOTTOM OF STAIRS REQ`D PER NFPA-72
 8-1.4.2
  
 9)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL. SIZE PER 250-122
  
 10)NOTE: CLOSET LTS ARE SHOWN TOO CLOSE
 TO CLOTHES/STORAGE RACK PER 410-8
  
 PLEASE NOTE, PLANS WERE ORIG BROUGHT IN
 FOR MISC STRUCTURE REPAIRS, AND NOW
 ARE COMING IN W/ COMPLETE REDO OF P
 PLEASE ADJUST VALUE FOR SCOPEOF WORK
 NOW BEING DONE. PER 104.6.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-27 Time 10:40 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 10:40 Sent To E
Notes
2003-06-27 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-21 Cont ID  
Sent By sthyng Date 2003-03-21 Time 10:59 Rev Time 0.00
Received By sthyng Date 2003-03-21 Time 10:59 Sent To B
Notes
2003-03-21 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-19 Cont ID  
Sent By sthyng Date 2003-03-19 Time 09:43 Rev Time 0.00
Received By sthyng Date 2003-03-19 Time 09:43 Sent To B
Notes
2003-03-19 00:00:00SENT TO TOM MOORE'S DESK - HEARING
 TOMORROW, OUR SET OF PLANS NOT IN
 DRAWER TO CONFIRM TRADES SIGNED ONTO
 ORIGINAL PERMIT

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-04-03 Cont ID  
Sent By kstevens Date 2003-04-03 Time 17:38 Rev Time 0.33
Received By kstevens Date 2003-04-03 Time 17:38 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2002-08-09 Cont ID  
Sent By rbrown Date 2002-08-09 Time 09:38 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***