Plan Review Details - Permit 02061860
Plan Review Stops For Permit 02061860
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-19 Cont ID  
Sent By dpalmer Date 2002-07-19 Time 16:33 Rev Time 0.00
Received By dpalmer Date 2002-07-19 Time 16:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-03 Cont ID  
Sent By dpalmer Date 2002-07-03 Time 06:20 Rev Time 0.00
Received By dpalmer Date 2002-07-02 Time 15:59 Sent To  
Notes
2002-07-03 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE ALSO SEE COMMENTS ON
 PERMIT #02061859.
 PLEASE CORRELATE SUBMITTED PLANS AND
 8 1/2X 14`S.
  
 2)NOTE: PLEASE NOTE PLANS NEED MORE
 INFORMATION OF LAY OUT OF NEW OUTLETS
 PER UPS SCHEDULE.
  
 3)NOTE: PLEASE NOTE MISSING INFORMATION
 FOR WIRE SIZES, CONDUIT SIZES ETC.
  
 4)NOTE: PLEASE SUBMIT A COPY OF CONTRACT
 TO VERIFY VALUE FOR COMPLETE SCOPE OF
 WORK. PLEASE NOTE PER FAC/ FEES ARE
 BASED ON VALUE, INCLUDING ALL LABOR AND
 MATERIALS. INCLUDING ANY OWNER SUPPLIED
 EQUIPMENT IF HARDWIRED.
 104.6.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372