Plan Review Details - Permit 02061859
Plan Review Stops For Permit 02061859
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-10 Cont ID  
Sent By dpalmer Date 2002-07-10 Time 07:07 Rev Time 0.00
Received By dpalmer Date 2002-07-10 Time 07:07 Sent To  
Notes
2002-07-10 00:00:00*********** NOTE **********
  
 NOTE : NEW PLANS TO FOLLOW FOR 02061860

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-03 Cont ID  
Sent By dpalmer Date 2002-07-03 Time 06:04 Rev Time 0.00
Received By dpalmer Date 2002-07-03 Time 06:04 Sent To FIRE
Notes
2002-07-03 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT TWO SETS OF
 PLANS WERE SUBMITTED.?? PLEASE ALSO NOTE
 RISER DIAGRAMS DO NOT CORRELATE. PLEASE
 NOTE 8 1/2X 14`S NEED MORE INFORMATION,
 IF THOSE ARE GOING TO BE USED.
 NEEDS CONDUIT, WIRE SIZES, AIC RATING
 FOR ALL NEW EQUIPMENT.
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR RELOCATIONOF FIRE ALARM DEVICES.
  
 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 DO NOT CORRELATE?
  
 MECH NOT TO BE REVIEW PER ELECTRICAL
 CONT.7/2/02
  
 PLEASE SUBMIT AND CLARIFY PLANS AND
 SUBMIT INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372