Plan Review Details - Permit 02061849
Plan Review Stops For Permit 02061849
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-30 Cont ID  
Sent By jwitmer Date 2002-08-30 Time 15:01 Rev Time 0.99
Received By jwitmer Date   Time   Sent To  
Notes
2002-08-30 00:00:00STORM SHUTTER REPORT KEY PLAN & SCHEDULE

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 09:41 Rev Time 0.00
Received By dpalmer Date 2003-01-24 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-01-23 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 06:24 Rev Time 0.25
Received By dpalmer Date 2003-01-23 Time 06:24 Sent To  
Notes
2003-01-23 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE "A",
 PLEASE NOTE, SUB-PANEL IS NOT LISTED,
 PLEASE LIST W/ OCP LOAD ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-18 Cont ID  
Sent By btrobaug Date 2002-07-18 Time 17:38 Rev Time 0.00
Received By btrobaug Date 2002-07-18 Time 17:21 Sent To R
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-07-17 Cont ID  
Sent By hmoser Date 2002-07-17 Time 17:54 Rev Time 0.50
Received By hmoser Date 2002-07-17 Time 17:53 Sent To  
Notes
2002-07-17 00:00:00PASS/PROVISO
 1) NEED EVAPORATOR COIL FOR FINAL
 INSPECTION
 2) NEED FAN SHUTDOWN FOR FINAL SECTION
 606.2.2 FBC.(M) 2001
 PLAN REVIEW BY HAROLD MOSER 7/17/02

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-07-06 Cont ID  
Sent By jleech Date 2002-07-06 Time 11:23 Rev Time 0.33
Received By jleech Date 2002-07-06 Time 11:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-08-26 Cont ID  
Sent By jwitmer Date 2002-08-26 Time 06:31 Rev Time 2.25
Received By jwitmer Date 2002-08-26 Time 06:31 Sent To  
Notes
2002-08-26 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02061849
 ADD: 3093 BOLLARD RD
 CONT: INTELI HOMES
 TEL: (561)432-9022
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 *****BUILDING PROVISO*****
  
 1) TABLE 600 0 TO 3' FROM PROPERTY LINE,
 NO OPENINGS IN ZERO LOT LINE SIDE OF
 UNIT, GLASS BLOCK SHALL BE A FULL 1 HR.
 RATING, PROVIDE MANUFACTURERERS SPEC ON
 GLASS BLOCK BEFORE BUCK INSPECTION.
  
 2) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.MISSING SCHEDULE & KEY PLAN
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 FAILURE TO PRODUCE A KEY PLAN AND ATTACH
 MENT SCHEDULE BEFORE BUCK INSPECTION
 SHALLRESULT IN REQUIRING A SEPERATE
 PERMIT FOR STORM SHUTTERS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-08-01 Cont ID  
Sent By btrobaug Date 2002-07-18 Time 17:38 Rev Time 2.00
Received By jwitmer Date 2002-08-01 Time 18:20 Sent To  
Notes
2002-08-01 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02061849
 ADD: 3093 BOLLARD RD
 CONT: INTELI HOMES
 TEL: (561)432-9022
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SOILS REPORT REFRENCES THE 1997 SBC
 AND AMENDMENTS, CURRENT CODE IS 2001
 FLORIDA BUILDIING CODE, PL;EASE REVISE.
  
 2) GLASS BLOCK VS ZERO-LOT LINE, TABLE
 600 REQUIRES STRUCTURES 0-3' FROM THE
 PROPERTY LINE TO HAVE NO OPENINGS, AND
 A 1-HR RATING, GLASS BLOCK CAN BE USED
 THE 45 MIN OPENING PROTECTIVE DOES NOT
 APPLY TO THIS TYPE OF APPLICATION.
  
 3)2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING PRODUCT
 TESTING REPORT FOR:
 A) MULLIONS- CLIPPED
  
 5)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 6)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
 SHEET A-6 BUCK DETAILS FOR WINDOW,
 DOOR AND GARAGE DOOR DO NOT INDICATE
 THE DIAMETER OF THE TAPCON TO BE USED?
  
 7) ATTIC ACCESS PANEL MISSING INSULATION
  
 8) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 9)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
  
 10)PERMIT VALUE LOW, CALCULATED VALUE
 IS $289,904.00. PERMIT FEE ADJUSTMENT
 IS $900.84.
  
 11)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
  
 12)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-01 Cont ID  
Sent By jwitmer Date 2002-08-01 Time 18:43 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-08-01 00:00:00OK PER S. GRAHAM 7/03/02