Plan Review Details - Permit 02061790
Plan Review Stops For Permit 02061790
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-07-18 Cont ID  
Sent By rmcdouga Date 2002-07-18 Time 13:09 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-01 Cont ID  
Sent By btrobaug Date 2002-08-01 Time 13:04 Rev Time 0.00
Received By btrobaug Date 2002-07-16 Time 14:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-01 Cont ID  
Sent By kstevens Date 2002-08-01 Time 14:56 Rev Time 0.00
Received By kstevens Date 2002-08-01 Time 14:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-07-15 Cont ID  
Sent By kstevens Date 2002-07-15 Time 17:52 Rev Time 0.00
Received By kstevens Date 2002-07-15 Time 17:52 Sent To  
Notes
2002-07-15 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 PLUMBING
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) - TWO DRAINS SHOWN ON PIPING
 SCHEMATIC, BUT ONLY ONE SHOWN ON POOL
 LAYOUT SHEET. PLEASE CLAIRFY.
 2) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-01 Cont ID  
Sent By sgraham Date 2002-07-01 Time 11:07 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved