Plan Review Stops For Permit 02061658 |
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-07-31 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2002-07-31 |
Time |
11:31 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-31 00:00:00 | RE-SUB APPR, PES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-07-08 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2002-07-08 |
Time |
14:39 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-08 00:00:00 | PLUMBING PLAN REVIEW, DENIED. PES | | REVIWED FBC 2000 | | (1) TYPE OF GAS, (LP OR NATURAL) | | (2) SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER THE STANDARD GAS | | CODE SECS. 402.4 THRU 402.4.4.7. | | (3) SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER THE STANDARD GAS CODE SECS | | 502 THRU 506 | | (4) INDICATE THE DELIVERY PRESSURE PSI | | PER FBC, SEC 402.2IF NATURAL GAS | | SPECIFY .5 PSI OR 2 PSI. | | (5) SUBMIT MANUFACTURE SHEETS FOR ALL | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC SEC 402.2 | | (6) SHOW PLAN VIEW TO VERIFY LOCATION OF | | APPLIANCES,FBC SEC 104.2 | | END OF COMMENTSPAUL SCHMITZ | | QUESTIONS561-659-8096X8233 |
|
|
|