Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-27 Cont ID  
Sent By mcarsill Date 2002-06-27 Time 16:04 Rev Time 0.00
Received By mcarsill Date 2002-06-27 Time 16:03 Sent To  
Notes
2002-06-27 00:00:001) ARE THERE ANY OTHER FIRE ALARM
 DEVICES LOCATED WITHIN THE TENANT
 SPACE.
  
 2) ARCHITECTURAL TITLE BLOCK APPEARS
 ON THE DRAWINGS. PLANS NOT SIGNED AND
 SEALED.
  
 3) THE NEW DUCT SMOKE DETECTOR IS TO
 BE CONNECTED TO THE FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497