Plan Review Details - Permit 02061405
Plan Review Stops For Permit 02061405
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-19 Cont ID  
Sent By rbrown Date 2002-09-19 Time 12:10 Rev Time 0.00
Received By rbrown Date 2002-09-19 Time 12:09 Sent To  
Notes
2002-09-19 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 A SEPARATE ROOFING PERMIT APPLICATION IS
 REQUIRED.
  
 --PROVISO--
 DRAWING SHEET 1 OF 5 FROM THE ALUMINUM
 AWNING WINDOW PRODUCT APPROVAL HAS BEEN
 REPEATEDLY COPIED/FAXED/REDUCED.SUBMIT
 A LEGIBLE COPY.ALSO, THE PLAN CALLS
 FOR TEMPERED GLASS FOR THE WINDOWS AT
 THE NEW MASTER BATH TUB, BUT THE PRODUCT
 APPROVAL ONLY REFERS TO ANNEALED GLASS
 TYPES.THESE WINDOWS MUST COMPLY WITH
 THE REQUIREMENT FOR SAFETY GLASS AT THIS
 LOCATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-01 Cont ID  
Sent By rbrown Date 2002-08-01 Time 14:04 Rev Time 0.00
Received By rbrown Date 2002-08-01 Time 14:04 Sent To  
Notes
2002-08-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC 1606.2.4.1 WIND-INDUCED UPLIFT AT
 CANTILEVER TRUSS OVERHANG ADJACENT NEW
 MASTER BATHROOM.VERIFY THAT THE 6'-0"
 ROOF OVERHANG AT THIS LOCATION WILL NOT
 RESULT IN UPLIFT EXCEEDING THE CAPACITY
 OF THE SPECIFIED 'SIMPSON MTS 18 (OR
 ALTERNATIVE MSTA 18)' STRAPS.
  
 4) FBC 1504SUBMIT PRODUCT APPROVALS
 FOR THE ROOF COVERING MATERIALS.
  
 5) FBC 1601.1.4SUBMIT PRODUCT
 APPROVALS FOR THE NEW WINDOWS AND
 EXTERIOR DOORS, AND ASSOCIATED HURRICANE
 MISSILE IMPACT PROTECTION SHUTTERS.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 FORM.THE FORM SHALL INCLUDE THE
 PROJECT NAME AND ADDRESS, PERMIT NUMBER
 (02061405), AND JURISDICTION NUMBER
 (604700).ALSO, CORRECT THE PERMITTING
 OFFICE TO READ 'CITY OF WEST PALM BEACH'
  
 7)FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 -WINDOWS IN LINK TO NEW MASTER SUITE
 -SHOWER ENCLOSURE DOOR
 -NEW SLIDING GLASS DOORS
 -WINDOWS AT THE NEW MASTER BATH TUB
 SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-10 Cont ID  
Sent By btrobaug Date 2002-07-10 Time 15:19 Rev Time 0.00
Received By btrobaug Date 2002-07-10 Time 11:52 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-07-17 Cont ID  
Sent By ndenmark Date 2002-07-17 Time 11:48 Rev Time 0.25
Received By ndenmark Date 2002-07-17 Time 11:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-09-12 Cont ID  
Sent By kstevens Date 2002-09-12 Time 10:05 Rev Time 0.00
Received By kstevens Date 2002-09-12 Time 10:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-07-11 Cont ID  
Sent By btrobaug Date 2002-07-10 Time 15:19 Rev Time 0.00
Received By kstevens Date 2002-07-11 Time 17:39 Sent To  
Notes
2002-07-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUBMING
  
 1) PLEASE SUBMIT A SANITARY RISER DIA-
 GRAM. SHOW WHERE IT TIES INTO EXISTING
 SABT. AND GIVE PIPE SIZES AND VENT SIZE.
 2) PLEASE PROVIDE A MANUFACTURE SUBMITT-
 AL FOR PRODUCT APPROVAL FOR TANKLESS
 WATER HEATER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-07-09 Cont ID  
Sent By sgraham Date 2002-07-09 Time 12:40 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-06-25 Cont ID  
Sent By sgraham Date 2002-06-25 Time 09:29 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-06-25 00:00:00NEED SITE PLAN


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved