Plan Review Details - Permit 02061370
Plan Review Stops For Permit 02061370
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-14 Cont ID  
Sent By lmartine Date 2002-11-14 Time 17:56 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-07-25 Cont ID  
Sent By jwitmer Date 2002-07-25 Time 07:40 Rev Time 1.00
Received By jwitmer Date 2002-07-25 Time 07:40 Sent To  
Notes
2002-07-25 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02061370
 ADD: 345 SUMMA ST
 CONT: WHITING TURNER
 TEL: (561)832-4995
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE INTERACTIVE WATER FEATURE AS PER
 FL ADMINISTRATIVE CODE 64E-9, INTER-
 ACTIVE WATER FEATURES ARE TO HAVE STATE
 DEPARTMENT OF HEALTH, PALM BEACH COUNTY
 UNIT APPROVAL BEFORE SUBMITTAL TO
 BUILDING DEPARTMENT.
  
 2)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) DEFINITION OF (FAC 64E-9) "DECK"
 TO BE OF A NON SKID SURFACE, TYPE?
  
 5)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 6) ADDITIONAL INFORMATION ON EQUIPMENT
 ROOM, FOR 140 WIND ZONE?
  
 7) IS ALL THE EQUIPMENT SHOWN ON 6 OF 6
 TO FIT IN THE EQUIPMENT ROOM ON 4OF 6?
  
 8) HOW WILL IT BE SECURED FOR AUTHORIZED
 PEOPLE ONLY?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2002-11-14 Cont ID  
Sent By lmartine Date 2002-11-14 Time 18:20 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-11-14 00:00:00ELECTRIC INFO IS PERMITTED WITH SITE
 #02090084, OK BY DEWEY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-18 Cont ID  
Sent By dpalmer Date 2002-07-18 Time 16:32 Rev Time 0.00
Received By dpalmer Date 2002-07-18 Time 16:32 Sent To  
Notes
2002-07-18 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTENO ELECTRICAL DETAIL
 WAS SUBMITTED FOR COMPLETE REVIEW.
  
 PLEASE SUBMIT INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-11-18 Cont ID  
Sent By mamini Date 2002-11-18 Time 09:53 Rev Time 0.00
Received By mamini Date 2002-11-18 Time 09:53 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-07-19 Cont ID  
Sent By mamini Date 2002-07-19 Time 11:39 Rev Time 1.00
Received By mamini Date 2002-07-19 Time 11:39 Sent To  
Notes
2002-07-19 00:00:00FAILED :
 1. PLEASE PROVIDE STANDARD DETAILS FOR
 SEWER LATERALS AND BACKFLOW, METER
 CONNECTIONS, ALL INSTALLATIONS AND
 CONNECTIONS MUST BE CITY STANDARD AND
 REQUIREMENT.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By mcarsill Date 2002-08-06 Time 14:14 Rev Time 0.00
Received By mcarsill Date 2002-08-06 Time 14:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-18 Cont ID  
Sent By kstevens Date 2002-11-18 Time 10:19 Rev Time 0.25
Received By kstevens Date 2002-11-18 Time 10:19 Sent To  
Notes
2002-11-18 00:00:00PASSED PER HEALTH DEPT. LETTER TO KEN
 REARDON. SEE PLANS FOR COPY.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-07-22 Cont ID  
Sent By kstevens Date 2002-07-22 Time 08:48 Rev Time 0.00
Received By kstevens Date 2002-07-20 Time 18:32 Sent To  
Notes
2002-07-22 00:00:00DENIED
 REFERENCE: FBC-2001 SECTION 424
  
 1) ROUTE PLANS TO PALM BEACH COUNTY
 HEALTH DEPT. PRIOR TO RESUBMITTING FOR
 PLAN REVIEW.
 2) RINSE SHOWER, A MINIMUM OF ONE RINSE
 SHOWER SHALL BE PROVIDED ON THE POOL
 DECK OF ALL OUTDOOR POOLS WITHIN 20 FEET
 OF THE NEAREST POOL WATER'S EDGE.
 64E-9.006(2)(G)
 3) OVERFLOW SHALL BE DRAINED TO STORM
 4) BACKWASH AND DRAIN SHALL BE DRAINED
 TO SANITARY.
 5) BACKFLOW REQUIRED FOR MAKE UP WATER
 LINE
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-03 Cont ID  
Sent By sgraham Date 2002-07-03 Time 12:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***