Plan Review Details - Permit 02061278
Plan Review Stops For Permit 02061278
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-03-12 Cont ID  
Sent By dpalmer Date 2003-03-12 Time 06:04 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 18:19 Sent To  
Notes
2003-03-12 00:00:00OK PER BT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-06 Cont ID  
Sent By btrobaug Date 2002-08-06 Time 10:42 Rev Time 0.00
Received By btrobaug Date 2002-08-06 Time 10:12 Sent To B
Notes
2002-08-06 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 THE GROUNDING ELECTRODE MUST BE
 CONNECTED AT THE FIRST MEANS OF
 DISCONNECT OR AT THE METER,NOT IN THE
 PANEL WHERE IT COULD PRODUCE A PARALLEL
 GROUND PATH WITH THE NEUTRAL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-07-08 Cont ID  
Sent By btrobaug Date 2002-07-08 Time 08:59 Rev Time 0.00
Received By btrobaug Date 2002-07-08 Time 08:24 Sent To R
Notes
2002-07-08 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE NOTE THE FOLLOWING DISCREPANCIES
 ON THE DRAWINGS, MAKE ANY NECESSARY
 CHANGES AND RESUBMIT FOR REVIEW.
  
 1} THE GROUNDING SYSTEM SHOWN AT "A"
 PANEL SHOULD BE AT THE FIRST MEANS OF
 DISCONNECT PER 250-24(A)(1).
  
 2} PLEASE NOTE THAT THE #2/0 FEEDERS TO
 PANEL "B" ON THE RISER DIAGRAM DO NOT
 CORRELATE WITH THE #6'S SHOWN ON PANEL
 SCHEDULE "A".
  
 3} THE #2 FEEDERS FROM THE MAIN
 DISCONNECT TO PANEL "A" DO NOT COMPLY
 WITH 310-15(B)(6) FOR A 200 AMP OCP.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-27 Cont ID  
Sent By sthyng Date 2003-03-27 Time 14:51 Rev Time 0.00
Received By sthyng Date 2003-03-27 Time 14:51 Sent To M
Notes
2003-03-27 00:00:00REVISION TO MECH IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-12 Cont ID  
Sent By dpalmer Date 2003-03-12 Time 06:04 Rev Time 0.00
Received By dpalmer Date 2003-03-07 Time 06:04 Sent To M
Notes
2003-03-12 00:00:00REV WAS IN RESUBS
 TO HM'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-10 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 11:52 Rev Time 0.00
Received By dpalmer Date 2003-02-10 Time 11:52 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-03-28 Cont ID  
Sent By rregueir Date 2003-03-28 Time 07:44 Rev Time 0.33
Received By rregueir Date 2003-03-28 Time 07:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2003-03-26 Cont ID  
Sent By sthyng Date 2003-03-27 Time 14:51 Rev Time 0.50
Received By rregueir Date 2003-03-26 Time 17:52 Sent To  
Notes
2003-03-26 00:00:00MECHANICAL PLAN REVIEW: FAILED
 EQUIPMENT AND DUCT SIZES SHOWN ON PLAN
 DO NOT MATCH PLAN AS MARKED IN FIELD.
 REVISE PLAN AND ENERGY CALCS TO
 ACCURATELY REFLECT EXISTING CONDITIONS
 AND FIELD-MODIFIED PLAN. ANY QUESTIONS
 PLEASE CALL RONALD J REGUEIRO
 561-659-8096 X8512

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-03-15 Cont ID  
Sent By rregueir Date 2003-03-15 Time 07:27 Rev Time 0.33
Received By rregueir Date 2003-03-15 Time 07:27 Sent To  
Notes
2003-03-15 00:00:00REVISED PLAN REVIEW FAILED
 SEER SHOWN ON ENERGY CALCS DOES NOT
 MATCH SEER SHOWN ON EQUIPMENT LISTED
 ON REVISED PLAN.REVISE ENERGY CALCS
 AND RESUBMIT WITH REVISED PLAN.
 REVIEWED BY: RONALD J REGUEIRO
 561-659-8096 X8512

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-01 Cont ID  
Sent By dpalmer Date 2003-03-12 Time 06:04 Rev Time 0.25
Received By jleech Date 2003-03-01 Time 10:50 Sent To B
Notes
2003-03-01 00:00:00RESTAMP.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-07-06 Cont ID  
Sent By kstevens Date 2003-02-10 Time 14:20 Rev Time 0.50
Received By hmoser Date 2002-07-06 Time 12:01 Sent To  
Notes
2002-07-06 00:00:00PRIVISO/PASS
 1) NEED FRESH AIR CALCULATIONS FOR ROUGH
 INSPECTION
 2) NEED FAN SHUTDOWN FOR FINAL
 3) PROGRAMMABLE T.STAT FOR FINAL
 4) SEEMECHANICAL NOTES #9
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-10 Cont ID  
Sent By kstevens Date 2003-02-10 Time 14:20 Rev Time 0.50
Received By kstevens Date 2003-02-10 Time 14:20 Sent To M
Notes
2003-02-10 00:00:00RESTAMP OF ISSUED PLANS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-27 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 11:53 Rev Time 0.33
Received By jleech Date 2002-06-27 Time 19:15 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By btrobaug Date 2002-07-08 Time 08:59 Rev Time 2.50
Received By lhatten Date 2002-08-05 Time 19:07 Sent To  
Notes
2002-08-06 00:00:00REVIEW & STAMPED PLANS08/05/2002
 CALC. FEES & PRINT CARD08/06/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-24 Cont ID  
Sent By sgraham Date 2002-06-24 Time 10:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***