Plan Review Details - Permit 02061268
Plan Review Stops For Permit 02061268
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-08 Cont ID  
Sent By dpalmer Date 2002-07-08 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2002-07-08 Time 15:56 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 15:01 Rev Time 0.00
Received By dpalmer Date 2003-01-30 Time 15:01 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-08 Cont ID  
Sent By rregueir Date 2003-02-08 Time 08:33 Rev Time 0.50
Received By rregueir Date 2003-02-08 Time 08:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-07-06 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 15:01 Rev Time 0.33
Received By hmoser Date 2002-07-06 Time 13:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-07-02 Cont ID  
Sent By jleech Date 2002-07-02 Time 17:30 Rev Time 0.33
Received By jleech Date 2002-07-02 Time 17:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-11-18 Cont ID  
Sent By lhatten Date 2002-11-18 Time 19:10 Rev Time 2.50
Received By lhatten Date 2002-11-15 Time 19:09 Sent To  
Notes
2002-11-18 00:00:00REVIEW & STAMPED PLANS 11/15/2002
 CALC. FEES & PRINT CARD 11/18/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-08-21 Cont ID  
Sent By jgomez Date 2002-08-21 Time 18:32 Rev Time 4.00
Received By jgomez Date 2002-08-21 Time 18:32 Sent To  
Notes
2002-08-21 00:00:00CHECKLIST:
 1-PROVIDE SURVEY.
 2-PROVIDE ENGINEERING ANALYSIS/CALCS AND
 COMPLETE SECTIONS/DETAILS/SPECS FOR
 DESIGN OF GABLE END AT FRONT ELEVATION
 CONSIDERING THAT THE CENTER OF GABLE
 IS MASONRY & ENDS ARE WOOD TRUSSES.
 HOW IS GABLE END WALL PUT TOGETHER TO
 TRANSFER ALL LOADS. SEE SECTIONS
 1606.2.4, 2117 AND 2313 FBC 2001.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-REVISE ATTIC ACCESS SIZE. 36" MIN. NOT
 30". SEE SEC. 2309.6 FBC 2001.
 5-34SH WINDOW DOESN'T PROVIDE 24" MIN.
 CLEAR HT. OPENING. SEC. 1005.4.4 FBC
 6-PROVIDE SOIL TEST REPORT.
 7-PROVIDE COMPLETE & CORRECT INFORMATION
 FOR STORM SHUTTERS OR SEPARATE PERMIT
 REQUIRED. CITY HURRICANE STANDARD.
 8-PROVIDE PRODUCT APPROVAL FOR:
 --SINGLE ENTRY DOOR W/ONE SIDELITE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 9-PROVIDE STRUCTURAL DETAIL FOR 2X BUCK
 AS REQ'D BY MULLION PRODUCT APPROVAL.
 10-PROVIDE COMPLETE UL LISTING AND SPECS
 FOR ONE HR FIRE RATED GLASS BLOCK
 ASSEMBLY AS REQUIRED BY TABLE 600 FBC.
 A)NOTE: GLASS BLOCK TO BE SAFETY GLASS
 IF UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEE SEC. 2405.2.2 FBC 2001.
 PROVIDE SPECS FOR GLASS THICKNESS.
 B)NOTE: GLASS BLOCK ASSEMBLY TO BE 1 HR
 FIRE RATED, NOT 3/4. TABLE 600 FBC.
 C)REVISE GLASS BLOCK DETAIL TO MATCH
 SPECS FOR 1HR FIRE RATED ASSEMBLY.
 11-SPECIFY SPACING FOR SUPPORTS OF WWM
 ON CONCRETE SLAB. SEC. 1909.3 FBC 2001
 12-PROVIDE COMPLETE DETAIL AT RECESSED
 WINDOWS TO ALLOW FOR STORM SHUTTER
 INSTALLATION.
 **NOTE: SEE PRODUCT APPROVAL FOR TRACK
 TO BE USED AND CONSIDER THE GLASS
 SEPARATION AND EDGE DISTANCE FOR
 PROPER INSTALLATION.
 13-ENERGY CALCULATIONS:
 A)REVISE UNDER ATTIC AREA. SEE SECTION
 602.1.ABC.1.2 CHAPTER 13 FBC 2001.
 B)OWNER/AGENT TO SIGN AND DATE FORM.
 14-WALL SECTIONS NOTE #14 AND VENT CALCS
 SIZE & SPACING DON'T MATCH. REVISE.
 15-SHEET S-2: UPDATE NOTE #3. USE FBC
 2001 FOR 140MPH, NOT ASCE 7-93 110MPH.
 16-SHEET S-1: CLARIFY DIMENSION OF
 4'-1 1/2" ON SEC. 5.
 17-IDENTIFY ON PLANS ROOF ZONE 3 SHOWN
 ON DIAPHRAGM SCHEDULE, SHEET S-2.
 18-SHEET S-1: REVISE LINTEL SCHEDULE TO
 MATCH PLANS. CHECK SIZE OF OPENINGS &
 LINTEL #. EG: L-7 AND L-19.
 19-REVISE TRUSS ANCHOR SCHEDULE: UPLIFT
 LOADS AND LATERAL LOADS TO MATCH USP
 SPECIFICATIONS ACCORDING TO TYPE OF
 ANCHOR & # OF FASTENERS USED. PROVIDE
 ENGINEERING CALCULATIONS FOR LOADS
 DIFFERENT THAN THOSE SHOWN ON USP
 CATALOGUE.
 **NOTE: SEE USP 2001 CATALOGUE PAGE 40
 FOR LIMITATIONS WHEN USING DOUBLE
 ANCHORS (EG: WHEN ISTALLED LESS THAN
 8"O.C.).
 20-SHEET S-2: CLARIFY WHY BLOCKING AT
 FRONT GABLE END IS SHOWN ON PARTIAL
 GABLE END AND NOT ALL THE WAY TO THE
 ENDS. SEC. 104.2.1.2 CITY AMENDMENTS.
 21-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 STRUCTURAL BUCK SPECS & REVISE DETAIL
 AS REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-07-01 Cont ID  
Sent By sgraham Date 2002-07-01 Time 15:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-06-24 Cont ID  
Sent By sgraham Date 2002-06-24 Time 10:16 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-06-24 00:00:00NEED SURVEY