Plan Review Details - Permit 02061262
Plan Review Stops For Permit 02061262
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-05 Cont ID  
Sent By hmoser Date 2002-06-29 Time 12:24 Rev Time 0.00
Received By btrobaug Date 2002-07-05 Time 06:24 Sent To R
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:48 Rev Time 0.00
Received By dpalmer Date 2003-01-30 Time 14:48 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-02-24 Cont ID  
Sent By hmoser Date 2003-02-24 Time 19:21 Rev Time 0.25
Received By hmoser Date 2003-02-24 Time 19:21 Sent To  
Notes
2003-02-24 00:00:00NOTES
 NEED FAN SHUTDOWN AND PROGRAMMABLE
 T.STAT FOR FINAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-29 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:49 Rev Time 0.50
Received By hmoser Date 2002-08-29 Time 18:15 Sent To  
Notes
2002-08-29 00:00:00PASS/PRIVISO
 1) NEED FRESH AIR CALCULATIONS FOR ROUGH
 INSPECTION
 2) RETURN AIR DUCT MUST BE SAME SIZE OR
 LARGER THAN SUPPLY DUCT SECTION 601.4
 FBC.2001
 3) NEED FAN SHUT DOWN FOR FINAL
 4) NEED PROGRAMMABLE T.STAT FOR FINAL
 PLAN REVIEW BY HAROLD MOSER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-29 Cont ID  
Sent By hmoser Date 2002-06-29 Time 12:24 Rev Time 0.33
Received By hmoser Date 2002-06-29 Time 12:24 Sent To E
Notes
2002-06-29 00:00:00PLAN DENIED
 1) NO DUCT SIZE ON R/A 2ED FLOOR
 2)REFER TO SECTION 601.4 BEFOR SIZEING
 RETUREN DUCT
 3) NEED FRESH AIR CALCULATION FOR ROUGH
 INSPECTION
 4) NEED PROGRAMMABLE T.STAT FOR FINAL
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-22 Cont ID  
Sent By jleech Date 2002-06-22 Time 11:57 Rev Time 0.33
Received By jleech Date 2002-06-22 Time 11:57 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-10-28 Cont ID  
Sent By lhatten Date 2002-10-28 Time 17:49 Rev Time 3.00
Received By lhatten Date 2002-10-27 Time 17:48 Sent To  
Notes
2002-10-28 00:00:00REVIEW & STAMPED PLANS 10/27/2002

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-08-30 Cont ID  
Sent By jgomez Date 2002-08-30 Time 17:40 Rev Time 3.00
Received By jgomez Date 2002-08-30 Time 17:40 Sent To  
Notes
2002-08-30 00:00:00SECOND CHECKLIST:
 1-SECOND FLOOR FRAMING PLAN: REVISE DET.
 5/S3. CONNECTOR SPECIFIED IS A LIGHT
 GAUGE PURLIN HANGER NOT A HANGER FOR
 A GIRDER TRUSS. ALSO, USP HL210 HAS NO
 UPLIFT CAPACITY. SEE USP CATALOGUE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 2-DETAIL 5/S3: PROVIDE COMPLETE SPECS
 FOR GABLE END INSTALLATION. SPECIFY
 ALL CONNECTORS AND HOW IS THE TRUSS
 ATTACHED TO PROVIDE CONTINUITY. SEE
 SECTION 2313.4 FBC 2001.
 ALSO, SEE TABLE 2306.1 CITY AMENDMENTS
 TO FBC FOR NAIL TYPE AND SPACING.
 (8D RING SHANK AT 25' MEAN ROOF HT.)
 3-REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH PUBLISHED VALUES BY USP.
 SCHEDULE WAS NOT PROPERLY REVISED. THE
 NAIL TYPE WAS CHANGED TO 10DX1 1/2 BUT
 VALUES GIVEN ARE FOR 10D NAILS.
 **PROVIDE ACTUAL ENGINEERING CALCS FOR
 UPLIFT VALUES NOT PUBLISHED BY USP.
 4-NEED RECORDED NOTICE OF COMMENCEMENT.
 5-WINDOW BY ENTRY PORCH TO BE SHOWN AS
 DOTTED LINES ON LEFT ELEVATION, SHEET
 A-4. OTHERWISE, IT REPRESENTS THAT THE
 WINDOW IS ON THE ZERO LOT LINE WALL.
 6-PROVIDE GENERAL SPECIFICATIONS FOR
 REQUIRED FIREBLOCKING AT ALL CONCEALED
 SPACES AS REQ'D BY SEC. 2305.1.4 FBC.
 7-PROVIDE COMPLETE AND CORRECT INFO. FOR
 STORM SHUTTERS OR APPLY FOR SEPARATE
 PERMIT.
 **KEY PLAN & INSTALLATION SCHEDULE DON'T
 MATCH PLANS.
 **PRODUCT APPROVAL SUBMITTED REQUIRES
 ENGINEER TO SIGN AND SEAL DRAWINGS AND
 REQUIRES ADDITIONAL ENGINEERING FOR
 SPECIFIC MOUNTING CONDITIONS. SEE
 LIMITATIONS ON PAGE 4 OF 4 OF PRODUCT
 APPROVAL REPORT.
 8-SHEET S3: ROOF SHEATHING SPECS SHOWN
 IN SECTION 5 AND DIAPHRAGM SCHEDULE
 DON'T MATCH. REVISE AS REQUIRED.
 9-GARAGE DOOR STRUCTURAL BUCK DETAIL:
 SPECIFY LENGTH OF ANCHOR BOLTS AND
 REQUIRED WASHER. SEC. 104.2.1.2 CITY
 AMENDMENTS AND SEC. 1606 FBC 2001.
 10-DRAWINGS SUBMITTED SHOW GARAGE ON THE
 RIGHT HAND SIDE, WHILE SURVEY SHOWS
 GARAGE ON THE LEFT HAND SIDE. CLARIFY
 TO AVOID CONFLICTS WITH ZONING.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-08-20 Cont ID  
Sent By btrobaug Date 2002-07-05 Time 06:54 Rev Time 4.00
Received By jgomez Date 2002-08-20 Time 18:47 Sent To  
Notes
2002-08-20 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-REVISE ENTRY DOORS SIZE TO PROVIDE THE
 32" MIN. CLEAR OPENING REQUIRED BY
 TABLE 1004 FBC 2001.
 3-WINDOW AT ENTRY PORCH EXCEEEDS MAX. %
 OF OPENINGS ALLOWED BY TABLE 600 FBC.
 4-SPECIFY FIREBLOCKING MATERIALS AND
 LOCATION AT STAIRS, INCLUDING AT TOP
 OF STAIRS. SEC. 2305.1.4 FBC 2001.
 **NOTE: PROVIDE GENERAL SPECS FOR REQ'D
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEEE SEC. 2305.1.4 FBC 2001.
 5-SPECIFY DRAFSTOPPING LOCATIONS AND
 MATERIAL @ 2ND FL. FRAMING PLAN AS
 REQUIRED BY SEC. 2305.2.2 FBC 2001.
 **NOTE: FIRESTOPPING TO BE PLACED SO
 AREAS DON'T EXCEED 500 S.F.
 6-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEC. 2305.4
 7-PROVIDE SOIL TEST REPORT.
 8-SPECIFY SPACING FOR WWM SUPPORTS. SEE
 SECTION 1909.3 FBC 2001.
 9-PROVIDE COMPLETE & CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FOR A
 SEPARATE PERMIT. CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION.
 10-PROVIDE PRODUCT APPROVALS FOR DOORS,
 WINDOWS AND WINDOW MULLIONS ASSEMBLIES
 AS SHOWN ON PLANS.
 11-REVISE STAIR KEY NOTE #1. HEIGHT OF
 STAIR HANDRAILING TO BE BET. 34" & 38"
 MAX. SEE SEC. 1007.5.1 FBC 2001.
 12-2ND FLLOR FRAMING PLAN:
 REVISE/CLARIFY AND PROVIDE DETAIL FOR
 USING USP HL210 HANGERS FOR DOUBLE
 GIRDER TRUSSES RESTING ON THE MASONRY
 WALL BY THE 2 SIDES OF STAIRWAY. SEE
 CONNECTOR SPECS/SIZE ON USP CATALOGUE.
 13-DETAIL 4/S3 DOESN'T APPLY. NEED GABLE
 END DETAIL (SEE SEC. 2117 FBC). ALSO,
 ROOF FRAMING PLAN CALLS FOR SEC. 5/S3,
 NOT 4/S3. CLARIFY/REVISE AS REQUIRED.
 14-NOTE ON BUCKET DETAILS SHEET S2 CALLS
 FOR 1/4" WELDING. ALL THE DETAILS CALL
 FOR 3/16" WELDING. CLARIFY/REVISE.
 15-REVISE TRUSS CONNECTOR SCHEDULE:
 # OF NAILS AND UPLIFT LOADS SPECIFIED
 DON'T MATCH THOSE ON USP CATALOGUE.
 PROVIDE ENGINEERING CALCULATIONS FOR
 LOADS DIFFERENT THAN THOSE SPECIFIED
 ON USP CATALOGUE.
 **NOTE: SEE USP LIMITATIONS WHEN USING
 DOUBLE ANCHORS AND CONNECTORS ARE LESS
 THAN 8" APART.
 16-SOME CONNECTORS ARE NOT SPECIFIED ON
 ROOF FRAMING PLAN. SPECIFY THEM.
 17-REVISE CONNECTOR TC-5. IT DOESN'T
 RESIST THE UPLIFT LOADS CALCULATED ON
 ROOF FRAMING PLAN.
 18-ROOF SHEATHING NOTE (DWG S3), SECTION
 4 OF S3 AND DIAPHRAGM SCHEDULE HAVE
 DIFFERENT SPECS FOR ROOF SHEATHING
 FASTENERS. REVISE AS REQUIRED.
 19-SHOW NAILING ZONES IN ROOF FRAMING
 PLAN. SEE TABLE 2306.1 CITY AMENDMENTS
 TO FBC 2001.
 20-DESIGN PRESSURES FOR ENTRY DOORS ARE
 DIFFERENT ON THE FLOOR PLAN AND ON EXT
 ELEVATION. REVISE AS REQUIRED.
 21-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK SPECS AND REVISE
 DETAIL AS REQUIRED.
 22-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ATTACHMENT OF DOUBLE 2X BUCK FOR ENTRY
 DOOR. SEC. 104.2.1.2 CITY AMENDMENTS.
 23-UPDATE DRAWING C-1 AS WELL.
  
 QUESTION?
 IS THERE ANY REASON WHY THESE PLANS ARE
 SHOWING GARAGE ON THE RIGHT HAND SIDE,
 BUT SURVEY SHOWS GARAGE ON THE OTHER
 SIDE?.(LOT 76 IS THE SAME MODEL AND ALL
 DWGS SHOW GARAGE ON LEFT HAND SIDE).

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-24 Cont ID  
Sent By sgraham Date 2002-06-24 Time 10:19 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***