Plan Review Details - Permit 02061260
Plan Review Stops For Permit 02061260
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-28 Cont ID  
Sent By dpalmer Date 2002-06-28 Time 06:46 Rev Time 0.00
Received By dpalmer Date 2002-06-28 Time 06:46 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-10-15 Cont ID  
Sent By pkrauss Date 2002-10-15 Time 11:08 Rev Time 0.30
Received By pkrauss Date 2002-10-15 Time 11:08 Sent To  
Notes
2002-10-15 00:00:00MECHANICAL PERMIT 02061292

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-29 Cont ID  
Sent By hmoser Date 2002-08-29 Time 18:40 Rev Time 0.50
Received By hmoser Date 2002-08-29 Time 18:40 Sent To  
Notes
2002-08-29 00:00:00PASS/PRIVISO
 NEED REVISED PLANS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-08-12 Cont ID  
Sent By hmoser Date 2002-06-26 Time 19:51 Rev Time 0.50
Received By hmoser Date 2002-06-26 Time 19:51 Sent To  
Notes
2002-08-12 00:00:00PLAN DENIED
 1) RETURN AIR NUST BE SAME SIZE OR
 LARGER THAN SUPPLY
 2) CHECK CFM.ON LIVING ROOM DUCT
 3) CHECK SIZE OF A/C 1719 S.F 5 TON
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-22 Cont ID  
Sent By jleech Date 2002-06-22 Time 12:18 Rev Time 0.33
Received By jleech Date 2002-06-22 Time 12:18 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-09-03 Cont ID  
Sent By jgomez Date 2002-09-03 Time 11:10 Rev Time 4.00
Received By jgomez Date 2002-09-03 Time 08:58 Sent To  
Notes
2002-09-03 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-FLOOD ZONE A8: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 2-PROVIDE COMPLETE UL LISTING AND SPECS
 FOR 1 HR. FIRE RATED GLASS BLOCK.
 REVISE DETAIL SEE UL SPECS.
 **NOTE: GLASS BLOCK TO BE SAFTEY GLASS
 IF UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEE SEC. 2405.2 FBC 2001.
 **NOTE: PROVIDE LEGIBLE PRODUCT APPROVAL
 AND DRAWINGS ALSO.
 3-WOOD COLUMN DETAILS: A)SPECIFY HOW
 MUCH EMBEDMENT FOR 1/2" ANCHOR BOLTS.
 B)CLEARLY IDENTIFY TOP CONNECTORS AND
 CLARIFY HOW ARE STRAPS USED RESISTING
 FOR LATERAL LOADS AND HOW ARE TO WOOD
 MEMBERS RESTING ON THE COLUMN BEING
 SUPPORTED BY THE METAL STRAPS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE SOIL TEST REPORT.
 5-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 **NOTE: NEED ORIGINAL SIGNED AND SEALED
 DRAWINGS AS REQUIRED BY THE ENGINEER.
 ALSO, NEED ADDITIONAL ENGINEERING FOR
 CERTAIN MOUNTING CONDITIONS. SEE SHEET
 4 OF 4 OF PRODUCT APPROVAL REPORT.
 6-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK SPECIFICATIONS AND
 REVISE DETAIL AS REQUIRED.
 **NOTE: SPECIFY SIZE OF WASHER. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-SPECIFY FIREBLOCKING @ STAIRS INCLUD'G
 AT TOP. SEE SEC. 2305.1.4 FBC 2001.
 **NOTE: PROVIDE GENERAL SPECIFICATIONS
 FOR FIREBLOCKING AT ALL CONCEALED
 SPACES. SEE SEC. 2305.1.4 FBC 2001.
 8-PROVIDE STRUCTURAL FRAMING DETAIL FOR
 INSTALLATION OF OVAL WINDOW. KEEP IN
 MIND THAT NEED 2X BUCK FOR ATTACHMENT
 OF WINDOW. SEC. 104.2.1.2 CITY AMENDM.
 9-REVISE STAIR KEY NOTE #1. HANDRAILS TO
 BE BET. 34" AND 38". SEC. 107.5.1 FBC.
 *NOTE: HANDRAILS & GUARDRAILS ARE NOT
 THE SAME.
 10-REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH USP PUBLISHED VALUES. OR PROVIDE
 ENGINEERING CALCULATIONS FOR DIFFERENT
 UPLIFT VALUES. NOTE: VALUES TO MATCH
 TYPE OF NAIL USED.
 11-SHOW NAILING ZONES ON ROOF PLAN.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 12-ROOF PLAN: CLARIFY WHY THERE IS NOT
 BLOCKING SHOWN ON INTERIOR GABLE END.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 13-DETAIL R19: SPECIFY ALL FASTENERS.
 THERE IS NOT STRAP SPECIFIED ON ROOF
 PLAN. ALSO, PROVIDE COMPLETE SPECS
 SHOWING HOW IS TRUSS DESIGNED TO BE
 CONTINUOUS AT LATERAL SUPPORT. SEE
 SECTION 2117 AND 2313 FBC 2001.
 **NOTE: ALSO, PROVIDE COMPLETE DETAIL/
 SPECS FOR INTERIOR GABLE END SHOWING
 CONTINUITY AT LATERAL SUPPORT. SEC.
 2313 FBC 2001.
 14-PROVIDE FIRECUT REQUIREMENTS IN
 STRUCTURAL WALL SECTIONS. SEC. 2305.4

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-08-13 Cont ID  
Sent By rmcdouga Date 2002-08-13 Time 12:53 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-13 00:00:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE TOTAL AREA LISTED ON SHEETS C1 &
 A1 IS INCORRECT. CHECK THE ADDITION AND
 CORRECT.
  
 3)ONE HOUR RATED GLASS BLOCK IS REQUIRED
 AT THE ZERO LOT LINE. PROVIDE UL
 SPECIFICATIONS FOR A ONE HOUR FIRE RATED
 GLASS BLOCK ASSEMBLY. THE GLASS BLOCK IS
 ALSO LOCATED IN A HAZARDOUS LOCATION AND
 MUST COMPLY WITH FBC 2405.2.2 AND HAVE A
 MINIMUM UNIFORM FACE THICKNESS OF 0.25".
 PLEASE SUBMIT MANUFACTURER'S SPECS. THAT
 INDICATE FACE THICKNESS OF GLASS BLOCK.
  
 4)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
 PLEASE INDICATE THIS ON THE PLANS.
  
 5) PLEASE CHANGE NOTE 6 ON A-2 TO REFER
 TO THE 2001 FLORIDA PLUMBING CODE.
  
 6) NUMBER 14 UNDER SECTION AND DETAILS
 ON SHEET A-5 INDICATES 3"X24" SCREEN
 VENTS AND THE SOFFIT VENT CALCS ON A-3
 LIST 6"X24" VENTS. PLEASE CLARIFY.
  
 7) NOTE 3 ON S-2 IS FOR A 110 MPH WIND
 VELOCITY AND THE CITY OF WPB IS LOCATED
 IN A 140 MPH WIND ZONE. PLEASE CORRECT.
  
 8) THE FOUNDATION THICKNESS IS SHOWN ON
 THE SECTIONS ON A-5 AS 18". THE FOOTING
 SCHEDULE ON S-2 LISTS IT AS 16". PLEASE
 CLARIFY.
  
 9) SHEET S-2 HAS A TAG FOR F14, WHICH IS
 FOR A STEEL COLUMN AND SHOULD BE F16.
  
 10) ON SHEET S-2, THERE IS A F5 TAG,
 HOWEVER, THERE IS NO F5 SECTION GIVEN.
  
 11) PROVIDE SOIL BEARING TEST PER FBC
 SECTION 1804.2.2.
  
 12) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE HUNG WINDOWS (COVER SHEET DOES
 NOT BELONG WITH THE OTHER PAGES, WHICH
 ARE EXPIRED)
 - STRUCTURAL MULLIONS (EXPIRED)
  
 13) STORM PANELS: THERE IS NO
 INSTALLATION SCHEDULE. THE OPENING SIZES
 ON THE KEY PLAN DO NOT ALL CORRESPOND
 WITH THOSE ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-12 Cont ID  
Sent By rmcdouga Date 2002-08-12 Time 17:42 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-12 00:00:00OK PER D.R. 6-21-02