Plan Review Details - Permit 02061051
Plan Review Stops For Permit 02061051
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-18 Cont ID  
Sent By jwitmer Date 2002-07-18 Time 18:01 Rev Time 0.33
Received By jwitmer Date 2002-07-18 Time 18:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-07-09 Cont ID  
Sent By btrobaug Date 2002-06-20 Time 10:02 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-07-09 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02061051
 ADD: 135 GREENWOOD DR
 CONT: TROPICAL CONCRETE RESTORATION
 TEL: 848-4767
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, DISCREP
 ANCY SHEET A-1 & A-2, A-1 INDICATES THE
 USE OF NEW (2- 3'X6'-8") DOORS 2 SETS &
 A SINGLE DOOR.SHEET A-2 STATES TO REUSE?
  
 2) SHEET A-2 DETAIL "A" INDICATES THE
 USE OF "HUGHES" STRAPS, NO LONGER IN
 BUSINESS.
  
 3)- SHEET A-3 2ND FLOOR INDICATES A
 STAIRWAY LEADING TO AN INTERMEDIATE
 LANDING, AT THIS LANDING THERE INDICATES
 A NARROW STAIRWAY 18" WIDE, TABLE 1004
 FOOTNOTE 5& 10 THE MINIMUM STAIRWIDTH
 FOR < THAN 50 PEOPLE IS 36" WIDE.
  
 4)SHEET A-2 MISSING INFO FOR SMOKE DECTE
 CTOR 905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
 B)905.2.1 RESIDENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1 IN FAMILY UNITS WITH
 MORE THAN ONE BEDROOM AREA OR WITH BED-
 ROOMS ON MORE THAN ONE FLOOR, MORE THAN
 ONE SMOKE DETECTOR IS REQUIRED.
 C) 905.2.2 WHERE THE DWELLING OR
 DWELLING UNIT CONTAINS MORE THAN ONE
 STORY, DETECTORS ARE REQUIRED ON EACH
 STORY, LOCATED IN CLOSE PROXIMITY TO THE
 STAIRWAY LEADING TO THE FLOOR ABOVE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-20 Cont ID  
Sent By btrobaug Date 2002-06-20 Time 10:02 Rev Time 0.00
Received By btrobaug Date 2002-06-20 Time 08:56 Sent To B
Notes
2002-06-20 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE NOTE ALL BRANCH CIRCUITS THAT
 SUPPLY 15-&20AMP,125 VOLT RECEPTACLE
 OUTLETS INSTALLED IN DWELLING UNIT
 BEDROOMS SHALL BE PROTECTED BY AN ARC
 FAULT CIRCUIT INTERRUPTER(S).PER 210-12.
  
 BILL TROBAUGH,ELECTRICAL PLAN REVIEW,
 CITY OF WEST PALM BEACH.561/659-8096
 EXT. 8392

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-07-12 Cont ID  
Sent By kstevens Date 2002-07-12 Time 16:28 Rev Time 0.00
Received By kstevens Date 2002-07-12 Time 16:28 Sent To  
Notes
***NONE***