Plan Review Details - Permit 02061044
Plan Review Stops For Permit 02061044
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-19 Cont ID  
Sent By dpalmer Date 2002-06-19 Time 17:47 Rev Time 0.00
Received By dpalmer Date 2002-06-19 Time 17:47 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-18 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 16:22 Rev Time 0.00
Received By dpalmer Date 2002-06-18 Time 17:32 Sent To B
Notes
2002-06-18 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED BRANCH CIRCUIT ON PANEL
 SCHEDULE. PLEASE NOTE THAT ALL PREVIOUS
 PLANS ARE COMING IN AND SHOWING AS
 "ACI" PROTECTED OUTLETS. PLEASE NOTE
 THAT THE PROTECTION REQ`D IS FOR THE
 ENTIRE BRANCH CIRCUIT. PLEASE ALSO NOTE
 THAT IT IS "AFCI" NOT "ACI" 210-12.
 THEY DO NOT MAKE AN "AFCI" RECEPT.
  
 2)NOTE: PLEASE NOTE THAT THE RISER
 DIAGRAM DOES NOT CORRELATE WITH ITSELF
 AND PANEL SCHEDULES? PLEASE NOTE,RISER
 NOTE SAYS, TO BE A 225A MCB AND RISER
 SHOWS 200A? PANEL ALSO SHOWN AS 200A.
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE NOTE LOAD SHOWN FOR PANEL
 "B" EXCEEDS 60A FEED FOR THAT PANEL.
  
 4)NOTE: PLEASE NOTE PANEL "B" IS SHOWN
 AS 75A MLO? PLEASE NOTE THAT A 75A PANEL
 IS NOT A COMMON PANEL SIZE.?
  
 5)NOTE: PLEASE NOTE THAT ALL CODES REF
 THE "2001" NEC. PLEASE NOTE WE ARE UNDER
 THE "99" NEC.
  
 6)NOTE: PLEASE NOTE GFI RECEPT SPACING
 FOR MASTER BATH PER 210-52D. PLEASE NOTE
 GFI WITHIN 3' OF SINK.,
  
 7)NOTE: PLEASE CLARIFY OUTLET SPACING
 NEXT TO FRIG? COUNTER? 210-52(C)-1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-28 Cont ID  
Sent By hmoser Date 2003-01-28 Time 16:58 Rev Time 0.50
Received By hmoser Date 2003-01-28 Time 16:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 16:21 Rev Time 0.40
Received By pkrauss Date 2002-06-18 Time 16:10 Sent To E
Notes
2002-06-18 00:00:00PROVISO:MECHANICAL PERMIT 02061046
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-19 Cont ID  
Sent By kstevens Date 2002-06-19 Time 16:37 Rev Time 0.00
Received By kstevens Date 2002-06-19 Time 16:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-19 Cont ID  
Sent By kstevens Date 2002-06-19 Time 08:24 Rev Time 0.00
Received By kstevens Date 2002-06-19 Time 08:24 Sent To  
Notes
2002-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT FLOOR PLAN. TUB BATH TO BE PICKED
 UP BEFORE WASH MACHINE & LAUNDRY TRAY &
 HAS ONLY ONE LAV ON FLOOR PLAN. BATHROOM
 FOR BEDROOM #3 MISSING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-06-21 Cont ID  
Sent By lhatten Date 2002-06-21 Time 07:18 Rev Time 2.50
Received By lhatten Date 2002-06-20 Time 07:17 Sent To  
Notes
2002-06-21 00:00:00REVIEW & STAMPED PLANS 06/20/2002
 CALC. FEES & PRINT CARDS 06/21/2002