2002-06-18 00:00:00 | *************** UNSAT ****************** |
| |
| 1)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROTECTED BRANCH CIRCUIT ON PANEL |
| SCHEDULE. PLEASE NOTE THAT ALL PREVIOUS |
| PLANS ARE COMING IN AND SHOWING AS |
| "ACI" PROTECTED OUTLETS. PLEASE NOTE |
| THAT THE PROTECTION REQ`D IS FOR THE |
| ENTIRE BRANCH CIRCUIT. PLEASE ALSO NOTE |
| THAT IT IS "AFCI" NOT "ACI" 210-12. |
| THEY DO NOT MAKE AN "AFCI" RECEPT. |
| |
| 2)NOTE: PLEASE NOTE THAT THE RISER |
| DIAGRAM DOES NOT CORRELATE WITH ITSELF |
| AND PANEL SCHEDULES? PLEASE NOTE,RISER |
| NOTE SAYS, TO BE A 225A MCB AND RISER |
| SHOWS 200A? PANEL ALSO SHOWN AS 200A. |
| PLEASE CORRELATE. |
| |
| 3)NOTE: PLEASE NOTE LOAD SHOWN FOR PANEL |
| "B" EXCEEDS 60A FEED FOR THAT PANEL. |
| |
| 4)NOTE: PLEASE NOTE PANEL "B" IS SHOWN |
| AS 75A MLO? PLEASE NOTE THAT A 75A PANEL |
| IS NOT A COMMON PANEL SIZE.? |
| |
| 5)NOTE: PLEASE NOTE THAT ALL CODES REF |
| THE "2001" NEC. PLEASE NOTE WE ARE UNDER |
| THE "99" NEC. |
| |
| 6)NOTE: PLEASE NOTE GFI RECEPT SPACING |
| FOR MASTER BATH PER 210-52D. PLEASE NOTE |
| GFI WITHIN 3' OF SINK., |
| |
| 7)NOTE: PLEASE CLARIFY OUTLET SPACING |
| NEXT TO FRIG? COUNTER? 210-52(C)-1. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRCIAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |