2002-07-29 00:00:00 | BUILDING DENIED |
| |
| 1)FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| PLEASE INDICATE ON PLANS. |
| |
| 2)2305.2.2 FLOOR/CEILING ASSEMBLIES |
| SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| ING ASSEMBLIES SEPERATING USEABLE SPACE |
| INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| PING SHALL BE PROVIDED PARALLEL TO THE |
| MAIN FRAMING MEMBERS. PLEASE INDICATE |
| ON THE PLANS. |
| |
| 3) THE ENERGY CALCULATIONS LISTS FOUR |
| BEDROOMS AND THE PLANS INDICATE THREE |
| BEDROOMS. PLEASE CORRECT. |
| |
| 4) EXTERIOR WALLS AND THE GABLE ENDS OF |
| ROOFS WITHIN FIVE FEET OF PROPERTY LINES |
| MUST BE DESIGNED FOR FIRE RESISTANCE |
| BASED UPON BOTH INTERIOR AND EXTERIOR |
| FIRE EXPOSURE. 2001 FBC TABLE 600 |
| INDICATE HOW THE ONE HOUR RATING WILL BE |
| ACHIEVED AT THE GABLE WALL ON THE ZERO |
| LOT LINE. |
| |
| 5) PROVIDE CLARIFICATION AT CANTILEVER |
| BEAMS. THE PLANS DO NOT INDICATE WHERE |
| THE WALL ON THE RIGHT SIDE ENDS AND THE |
| CANT. BEAM BEGINS. THE FOUNDATION, WALL |
| AND VERTICAL REINFORCEMENT ON SHEETS |
| 1,2,& 3B FOR THE RIGHT WALL AT THE |
| COVERED PORCH DOES NOT MATCH ELEVATIONS. |
| PLEASE CORRECT. |
| |
| 6) THE POSITIVE WINDLOAD PRESSURE LISTED |
| FOR THE GARAGE DOOR (+39.8 PSF) EXCEEDS |
| THE POSTIVE DESIGN PRESSURE (+ 37 PSF) |
| FOR THE OVERHEAD GARAGE DOOR. PLEASE |
| SUBMIT AN APPROPRIATE PRODUCT APPROVAL. |
| |
| 7) THE INFORMATION IN THE WIND PRESSURE |
| SCHEDULE FOR THE WINDOWS AND DOORS |
| CONTAINS INCORRECT INFORMATION. PLEASE |
| CORRECT. |
| |
| 8) THE STORM PANEL SCHEDULE AND KEY PLAN |
| DIFFERS FROM THE PLANS AT THE SECOND |
| FLOOR WINDOWS ABOVE THE LIVING/DINING |
| AREA. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |