2002-06-18 00:00:00 | 1) PLANS INDICATE THAT DUCT SMOKE | | DETECTORS WILL BE CAUSE A TROUBLE | | SIGNAL WHICH IS NOT ACCEPTABLE. | | ACTIVATION OF THE DUCT SMOKE DETECTORS | | ARE TO CAUSE THE FIRE ALARM SYSTEM TO | | ACTIVATE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
|