Plan Review Details - Permit 02060778
Plan Review Stops For Permit 02060778
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-02-03 Cont ID  
Sent By hpiskura Date 2003-02-03 Time 13:49 Rev Time 0.00
Received By hpiskura Date 2003-02-03 Time 12:11 Sent To  
Notes
2003-02-03 00:00:00REVISION DATED 1/27/03 REF A-1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-05 Cont ID  
Sent By hpiskura Date 2002-09-05 Time 15:12 Rev Time 0.00
Received By hpiskura Date 2002-09-05 Time 14:34 Sent To  
Notes
2002-09-05 00:00:00ARCHITECTS REVISION DATE 8/26/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-07-15 Cont ID  
Sent By jwitmer Date 2002-07-15 Time 14:09 Rev Time 1.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-07-15 00:00:00 
  
 BUILDING PLAN REVIEW
 PERMIT: 02060778
 ADD: 250 AUSTRALIAN AVE / 1504
 CONT: BURKHARDT CONSTRUCTION
 TEL: 659-1400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2) SHEET A-1 NOTE, MAILROOM # 26
 NEW LOCKING HDWR,TO COMPLY 1020.3(1)
 "THIS EXIT TO REMAIN UNLOCKED WHEN THIS
 BUILDING IS OCCUPIED".
  
 3) SHEET A-2 DOOR SCHEDULE NOTE# 2,
 PROVIDE SOLENOID ACTIVATED LATCH, PUSH
 BOTTON TO BE LOCATED AT RECEPTION DESK?
 ADDITONAL INFO.
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 14:10 Rev Time 0.25
Received By dpalmer Date 2003-02-04 Time 14:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-27 Cont ID  
Sent By dpalmer Date 2002-06-27 Time 08:00 Rev Time 0.00
Received By dpalmer Date 2002-06-27 Time 08:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-08-29 Cont ID  
Sent By mcarsill Date 2002-08-29 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2002-08-29 Time 15:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-07-16 Cont ID  
Sent By mcarsill Date 2002-07-16 Time 12:32 Rev Time 0.00
Received By mcarsill Date 2002-07-16 Time 12:31 Sent To  
Notes
2002-07-16 00:00:001) DOOR SCHEDULE INDICATES THAT A
 SOLENOID WILL BE CONNECTED TO THE
 DOOR LATCH. ONLY DELAYED EGRESS OR
 ACCESS CONTROLLED EGRESS WILL BE
 ALLOWED ON REQUIRED EXIT DOORS. PLEASE
 SEE NFPA 101, 2000 EDITION, CHAPTER 7.
  
 2) EXIT DOOR LOCKS SHALL NOT REQUIRE
 THE USE OF ANY KEYS, TOOLS, OR
 SPECIAL KNOWLEDGE TO OPERATE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-30 Cont ID  
Sent By btrobaug Date 2003-01-30 Time 14:46 Rev Time 0.00
Received By btrobaug Date 2003-01-30 Time 14:46 Sent To  
Notes
2003-01-30 00:00:00COM BOARD #2./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By pkrauss Date 2003-02-07 Time 13:51 Rev Time 0.35
Received By pkrauss Date 2003-02-07 Time 13:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 10:54 Rev Time 0.40
Received By pkrauss Date 2002-06-22 Time 10:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-02-05 Cont ID  
Sent By kstevens Date 2003-02-05 Time 16:00 Rev Time 0.75
Received By kstevens Date 2003-02-05 Time 16:00 Sent To  
Notes
2003-02-05 00:00:00REVISION OK - DELETE NEW SINK - ADD
 WATER LINE TO COFFEE MAKER - ICE MAKER
 PROVISO: WATER HAMMER ARRESTOR REQUIRED

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-09-05 Cont ID  
Sent By kstevens Date 2002-09-05 Time 18:36 Rev Time 0.00
Received By kstevens Date 2002-09-05 Time 18:36 Sent To  
Notes
2002-09-05 00:00:00PASSED/PROVISO
  
 FIELD INSPECTOR SHALL VERIFY NSF APPRO-
 VAL FOR FILTER AND LISTING FOR INSTA-HOT

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-28 Cont ID  
Sent By kstevens Date 2002-06-28 Time 18:09 Rev Time 0.00
Received By kstevens Date 2002-06-28 Time 18:09 Sent To  
Notes
2002-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) A DRINKING FOUNTAIN AND SERVICE SINK
 ARE REQUIRED PER TABLE 403.1. PLEASE IN-
 DICATE IF THESE ARE PROVIDED.
 2) SHT A-1 PROVIDE MANUFACTURE INFORMAT-
 ION FOR INSTA HOT AND WATER FILTER UNDER
 KITCHEN SINK. INSTA HOT MUST SHOW LIST-
 ING FROM AN APPROVED TESTING AGENCY, AND
 THE WATER FILTER MUST BE NSF APPROVED.
 3) SHT P-1 WATER RISER DIAGRAM. SHOW
 WATER HAMMER ARRESTOR NEAR FIXTURE IN
 AN "EFFICTIVE RANGE" NOT AT TOP OF DROP
 AS SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377