Plan Review Details - Permit 02060671
Plan Review Stops For Permit 02060671 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-07-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-07-22 |
Time |
11:44 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-07-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-07-14 |
Time |
16:16 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-14 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 02060671 | | ADD: 6162 UNITED ST | | CONT:CONTINENTAL | | TEL: | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1) FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORT, SBCCI OR DADE COUNTY | | REPORT ARE ACCEPTED. | | | | 2)SITE SPECIFIC ENGINEERING (PRODUCT | | APPROVAL) REQUIRES THE WET SIGNATURE, | | DATE AND EMBOSSED SEAL OF THE ENGINEER | | CERTIFYING THE PRODUCT AND SIGNATURE | | AND SEAL OF THE DESIGN PROFESSIONAL | | OF RECORD. | | A) CERTIFIED TESTING LABS | | B) FENESTRATION | | REQUIRES SITE SPECIFIC TESTING |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-09-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-09-04 |
Time |
13:49 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2002-09-04 |
Time |
13:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-07-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-25 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-07-01 |
Time |
07:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-06-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-06-28 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-06-28 |
Time |
11:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2002-06-25 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-25 |
Time |
12:01 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-06-25 |
Time |
11:39 |
Sent To |
E |
|
Notes |
2002-06-25 00:00:00 | PROVISO:MECHANICAL PERMIT 02060847 | | UNIT - CL | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | AREA BEING VENTILATED) OR TABLE 403.3 | | FOR MECHANICAL VENTILATION. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | OVERFLOW PROTECTION REQUIRED AS PER | | 2001 FBC(M) 307.2.3. | | | | THE MAXIMUM DEVELOPED LENGTH FOR THE | | DRYER VENT SHALL NOT EXCEED 25 FT WITH | | THE 5 FT REDUCTION FOR EACH 90 DEGREE | | BEND & A 2 1/2 FT REDUCTION FOR EACH 45 | | DEGREE BEND. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2002-06-22 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2002-06-22 |
Time |
08:02 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2002-06-22 |
Time |
08:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2002-07-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-07-22 |
Time |
11:52 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-07-22 00:00:00 | OK PER DR 6/20/02 |
|
|
|