Plan Review Details - Permit 02060571
Plan Review Stops For Permit 02060571
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-24 Cont ID  
Sent By btrobaug Date 2002-10-24 Time 17:44 Rev Time 0.50
Received By btrobaug Date 2002-10-24 Time 17:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-07-15 Cont ID  
Sent By pkrauss Date 2002-06-19 Time 07:38 Rev Time 0.00
Received By btrobaug Date 2002-06-19 Time 16:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:49 Rev Time 0.00
Received By dpalmer Date 2003-01-30 Time 14:49 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-02-24 Cont ID  
Sent By hmoser Date 2003-02-24 Time 19:52 Rev Time 0.25
Received By hmoser Date 2003-02-24 Time 19:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-28 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:49 Rev Time 0.30
Received By pkrauss Date 2002-10-28 Time 13:03 Sent To R
Notes
2002-10-28 00:00:00MECHANICAL PERMIT 02060595

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-19 Cont ID  
Sent By pkrauss Date 2002-06-19 Time 07:32 Rev Time 0.30
Received By pkrauss Date 2002-06-19 Time 07:32 Sent To E
Notes
2002-06-19 00:00:00PROVISO:MECHANICAL PERMIT 02060595
  
 PLAN SHEET MP-1 FRONT ROOM DOES NOT HAVE
 RETURN AIR DUCT OR TRANSFER AIR.PLEASE
 REVISE.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-02 Cont ID  
Sent By kstevens Date 2002-11-02 Time 06:17 Rev Time 0.25
Received By kstevens Date 2002-11-02 Time 06:17 Sent To  
Notes
2002-11-02 00:00:00NEW PLANS/RESTAMP

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-15 Cont ID  
Sent By jleech Date 2002-06-15 Time 11:09 Rev Time 0.33
Received By jleech Date 2002-06-15 Time 11:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-10-24 Cont ID  
Sent By pkrauss Date 2002-10-28 Time 13:19 Rev Time 2.50
Received By jgomez Date 2002-10-24 Time 10:08 Sent To  
Notes
2002-10-24 00:00:00APPROVED WITH PROVISO:
 1-REVISE ENERGY CALCULATIONS: RAISED WD,
 AND ADJACENT WALLS ARE INCORRECT. SEE
 PLANS AND REVISE AS REQUIRED.
 2-ARCHITECT TO CORRECT TOATAL A/C AREA
 ON DWGS C-1 AND A-1.
 3-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT. SEE CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION FOR SITE SPECIFIC CONDITION
 4-SHEET A-5: REVISE HEIGHT OF HANDRAIL.
 SEE SEC. 1007.5.1 FBC 2001.
 5-SHEET A-6: A)SPECIFY FIREBLOCKING AT
 SECTION A/A6. SEC. 2305.1.4 FBC 2001.
 B)SEE PRODUCT APPROVAL FOR GARAGE DOOR
 AND REVISE BUCK DETAIL AS REQUIRED.
 SPECIFY ANCHOR EMBEDMENT AND WASHER.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-SPECIFY HOW LONG ARE THE ANCHOR BOLTS
 FOR WOOD COLUMN BOTTOM CONNECTOR. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-SHEET S-2: CLARIFY SIZE OF BOND BEAM
 REINFORCEMENT SPECIFIED ON TYPICAL
 CONCRETE MASONRY WALL DETAIL. IS IT
 1#5 OR 1#7?. SEC. 104.2.1.2 CITY AMEND
 8-SHEET S-3: ROOF SHEATHING & NAILING
 NOTE AND DIAPHRAGM SCHEDULE SPECS DO
 NOT MATCH. CLARIFY SIZE OF NAIL AND
 SPACING. SEC. 104.2.1.2 AND TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE COMPLETE STRUCTURAL DETAIL AT
 RECESSED WINDOW TO RECEIVE STORM
 SHUTTERS. SEE STORM SHUTTERS PRODUCT
 APPROVAL FOR LIMITATIONS & ADDITIONAL
 ENGINEERING IF REQUIRED. TAKE INTO
 CONSIDERATION THE EDGE DISTANCE FOR
 STORM SHUTTERS AND GLASS SEPARATION
 REQUIRED.SEC. 104.2.1.2 CITY AMEND-
 MENTS TO FBC 2001.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-08-07 Cont ID  
Sent By rmcdouga Date 2002-08-07 Time 15:43 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-07 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A SOIL BEARING REPORT PER
 CITY AMENDMENTS TO THE 2001 FBC 1804.2.2
  
 3) THE CONDITIONED AREA ON THE PLANS IS
 DIFFERENT FROM THE AREA LISTED ON THE
 ENERGY CALC. FORM. PLEASE CORRECT.
  
 4) THE AREA UNDER ATTIC LISTED ON THE
 ENERGY CALCS. DOES NOT INCLUDE THE BONUS
 ROOM. THE AREA OF THE WOOD FRAME WALLS
 OF THE BONUS ROOM ADJACENT TO THE
 UNCONDITIONED GARAGE IS NOT LISTED ON
 THE ENERGY CALC. FORM. PLEASE CORRECT.
  
 5) THE PRODUCT APPROVALS SUBMITTED FOR
 THE DOUBLE DOORS AT THE FRONT ENTRY ARE
 NOT LEGIBLE. PLEASE SUBMIT CLEAR COPIES.
  
 6) THE PRODUCT APPROVALS SUBMITTED FOR
 THE SINGLE HUNG WINDOWS ARE NOT
 ACCEPTABLE. THE COVER SHEET DOES NOT GO
 WITH THE OTHER PAGES, WHICH ARE EXPIRED.
 PLEASE SUBMIT CURRENT AND COMPLETE
 PRODUCT APPROVALS.
  
 7) FIREBLOCKING IS REQUIRED AT THE TOP
 OF THE STAIR RUN. PLEASE INDICATE THIS
 ON DETAIL 2 OF SHEET A-7.
  
 8)THERE ARE DISCREPANCIES IN THE OPENING
 SIZES BETWEEN THOSE LISTED ON THE KEY
 PLAN AND THE INSTALLATION SCHEDULE AND
 THE ARCHITECTURAL PLANS. PLEASE REVISE
 SO THAT ALL LIST THE SAME SIZES FOR THE
 SAME OPENING.
  
 9) THE ARE SEVERAL SHEETS MISSING FROM
 THE PLANS. PLEASE SUBMIT (2) COMPLETE
 SETS OF PLANS. (A-3,A-4,A-5)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-07-15 Cont ID  
Sent By rmcdouga Date 2002-07-15 Time 14:47 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-15 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A SOIL BEARING REPORT PER
 CITY AMENDMENTS TO THE 2001 FBC 1804.2.2
  
 3) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT AND THE BASIC WIND
 PRESSURE ON THE PLANS AS REQUIRED BY THE
 FBC SEC. 1606.1.7.
  
 4) THE CONDITIONED AREA ON THE PLANS IS
 DIFFERENT FROM THE AREA LISTED ON THE
 ENERGY FORM. PLEASE CORRECT.
  
 5) THE AREA UNDER ATTIC LISTED ON THE
 ENERGY CALCS DOES NOT APPEAR TO INCLUDE
 THE BONUS ROOM. THE ADJACENT WOOD FRAME
 WALL AREA IS INCORRECT. PLEASE REVIEW
 AND CORRECT.
  
 6) PLEASE CORRECT #1 UNDER FOUNDATION
 NOTES TO 0.006 POLYETHELENE (6 MIL.) AS
 REQUIRED BY FBC 1909.2.
  
 7) OPENINGS FROM A GARAGE DIRECTLY INTO
 A ROOM USED FOR SLEEPING PURPOSES IS NOT
 PERMITTED PER FBC 411.2.8.
  
 8) THE WINDOW (H) IN THE FIRST BATH ROOM
 IS REQUIRED TO HAVE TEMPERED GLASS PER
 FBC 2405.2.1.
  
 9) PLEASE CHANGE NOTE 6 UNDER NOTES ON
 SHEET A-2 TO REFERENCE THE FLORIDA
 PLUMBING CODE.
  
 10) THE NAIL SIZE AND SPACING LISTED FOR
 THE SECOND FLOOR DIAPHRAGM IN SECTION 2
 SHEET S-2 DOES NOT CORRESPOND WITH THE
 DIAPHRAGM SCHEDULE. PLEASE CORRECT.
  
 11) INDICATE ON THE PLANS THAT THE BONUS
 ROOM WALLS ARE INSULATED.
  
 12) INDICATE HOW THE FIREBLOCKING THAT
 IS REQUIRED BY FBC 2305.1.4 AT THE TOP
 OF THE STAIR RUN WILL BE ACHIEVED.
  
 13) INDICATE THE DRAFTSTOPPING LOCATIONS
 AND MATERIAL FOR THE ROOF/CEILING
 ASSEMBLY AS REQUIRED BY FBC 2305.2.2.
  
 14) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - DOUBLE FRONT DOORS WITHOUT SIDELITES
 - STRUCTURAL MULLIONS (EXPIRED)
 - SINGLE HUNG WINDOWS (THE COVER PAGE
 DOES NOT GO WITH THE REST OF THE PAGES)
  
 15) PROVIDE AN INSTALLATION SCHEDULE AND
 KEY PLAN FOR THE STORM PANELS. INDICATE
 THE TYPE FASTENER AND MOUNTING OPTIONS
 THAT WILL BE USED (CIRCLE OR HIGHLIGHT
 THE APPROPRIATE ITEMS ON THE APPROVED
 DRAWINGS). THIS INFORMATION IS REQUIRED
 AT TIME OF PERMIT OR A SEPARATE PERMIT
 WITH ADDITIONAL FEES WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By sgraham Date 2002-06-18 Time 07:48 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***