Plan Review Details - Permit 02060568
Plan Review Stops For Permit 02060568
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-19 Cont ID  
Sent By pkrauss Date 2002-06-17 Time 16:18 Rev Time 0.00
Received By dpalmer Date 2002-06-19 Time 06:51 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-07 Cont ID  
Sent By hmoser Date 2002-12-07 Time 08:46 Rev Time 0.50
Received By hmoser Date 2002-12-07 Time 08:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-05 Cont ID  
Sent By pkrauss Date 2002-08-05 Time 09:53 Rev Time 0.30
Received By pkrauss Date 2002-08-05 Time 09:42 Sent To  
Notes
2002-08-05 00:00:00PROVISO:MECHANICAL PERMIT 02060612
  
 WHERE MULTIPLE AIR HANDLING SYSTEMS
 SHARE COMMON SUPPLY OR RETURN AIR DUCTS
 OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM, THE
 RETURN AIR & SUPPLY AIR SYSTEM SHALL BE
 PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH SECTION 606.2.1.
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-17 Cont ID  
Sent By pkrauss Date 2002-06-17 Time 16:16 Rev Time 0.35
Received By pkrauss Date 2002-06-17 Time 16:14 Sent To E
Notes
2002-06-17 00:00:00PROVISO:MECHANICAL PERMIT 02060612
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-02 Cont ID  
Sent By kstevens Date 2002-08-02 Time 17:28 Rev Time 0.00
Received By kstevens Date 2002-08-02 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-15 Cont ID  
Sent By jleech Date 2002-06-15 Time 09:31 Rev Time 0.33
Received By jleech Date 2002-06-15 Time 09:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-08-02 Cont ID  
Sent By rmcdouga Date 2002-08-02 Time 12:45 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-02 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A SOIL BEARING TEST REPORT
 PER CITY AMENDMENTS TO 2001 FBC SECTION
 1804.2.2, PRIOR TO POURING FOUNDATION.
  
 3) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS THAT WERE
 SUBMITTED CONTAIN ERRORS. PLEASE SUBMIT
 REVISED KEY AND SCHEDULE PRIOR TO
 INSTALLATION OF STORM PANELS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-07-09 Cont ID  
Sent By rmcdouga Date 2002-07-09 Time 14:27 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-09 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN 'A8'
 FLOOD ZONE, AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 3) PROVIDE A SOIL BEARING REPORT PER THE
 CITY OF WPB AMENDMENTS TO THE 2001 FBC
 SEC. 1804.2.2.
  
 4) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT AND THE BASIC WIND
 PRESSURE ON THE PLANS AS REQUIRED BY THE
 FBC SEC. 1606.1.7.
  
 5) PLEASE CORRECT #1 UNDER FOUNDATION
 NOTES ON C-1 TO 0.006 POLYETHELENE
 (6 MIL) AS REQUIRED BY THE 2001 FBC SEC.
 1909.2.
  
 6) THE WINDOW (H) IN THE FIRST FLOOR
 BATHROOM IS REQUIRED TO HAVE SAFETY
 GLAZING PER 2405.2.1.
  
 7) PLEASE CHANGE NOTE 6 UNDER GENERAL
 NOTES ON A-2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 8) THE NAIL SIZE AND SPACING GIVEN FOR
 THE SECOND STORY FLOOR DIAPHRAM AT
 SECTION 2 ON SHEET S-2 DOES NOT AGREE
 WITH THE FLOOR DIAPHRAM INFORMATION
 LISTED IN THE SCHEDULE.
  
 9) THE A/C AREA LISTED ON THE PLANS
 DIFFERS FROM THE CONDITIONED AREA LISTED
 ON THE ENERGY CALCULATIONS. PLEASE
 CORRECT.
  
 10) THE ENERGY FORM LISTS 180 SQ.FT. OF
 ADJACENT WOOD FRAME WALLS,HOWEVER,THERE
 ARE NONE SHOWN ON THE PLAN. PLEASE
 REVISE ENERGY FORMS.
  
 11) FIREBLOCKING IS REQUIRED AT THE TOP
 OF THE STAIR RUN BY FBC 2305.1.4. PLEASE
 INDICATE THE LOCATION AND MATERIAL THAT
 WILL BE USED FOR THIS ON THE PLANS.
  
 12) INDICATE THE LOCATIONS AND MATERIALS
 USED FOR THE REQUIRED DRAFTSTOPPING OF
 THE FLOOR/CEILING ASSEMBLY.
  
 13) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRONT DOUBLE DOOR WITHOUT SIDELITES
 - STRUCTURAL MULLIONS
 - SINGLE HUNG WINDOWS (THE COVER PAGE OF
 THOSE SUBMITTED HAS A DIFFERENT
 ACCEPTANCE NUMBER THAN THE OTHER PAGES)
  
 14) PROVIDE AN INSTALLATION SCHEDULE FOR
 THE STORM PANELS. INDICATE THE TYPE OF
 FASTENER AND MOUNTING OPTION THAT WILL
 BE USED (CIRCLE OR HIGHLIGHT THESE ON
 THE PRODUCT APPROVAL DRAWINGS). THIS
 INFORMATION IS REQUIRED AT THE TIME OF
 PERMIT OR A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE STORM PANELS WITH
 ADDITIONAL FEES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-14 Cont ID  
Sent By sgraham Date 2002-06-14 Time 07:35 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***