Plan Review Details - Permit 02060563
Plan Review Stops For Permit 02060563
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-26 Cont ID  
Sent By btrobaug Date 2002-06-26 Time 13:10 Rev Time 0.00
Received By btrobaug Date 2002-06-26 Time 18:33 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-31 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 13:13 Rev Time 0.00
Received By btrobaug Date 2002-10-31 Time 13:12 Sent To M
Notes
2002-10-31 00:00:00 
 TO "M" IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-02-19 Cont ID  
Sent By rregueir Date 2003-02-19 Time 17:07 Rev Time 0.50
Received By rregueir Date 2003-02-19 Time 17:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-06 Cont ID  
Sent By hmoser Date 2002-11-06 Time 17:42 Rev Time 0.50
Received By hmoser Date 2002-11-06 Time 17:42 Sent To B
Notes
2002-11-06 00:00:00PASS/PROVISO
 1) CONDENSOR MODEL NUMBER ON PLAN AND
 CONDENSOR MODEL NUMBER ON MANUAL (J)
 DO NOT MATCH
 2) NEED FRESH AIR CALCULATION FOR ROUGH
 INSPECTION
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-24 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 13:13 Rev Time 0.50
Received By hmoser Date 2002-11-06 Time 17:33 Sent To  
Notes
2002-06-24 00:00:00PLAN DENIED
 1) VERFY TYPE OF VENTILATION USED FOR
 FRESH AIR
 2) NEED CALCULATIONS FOR TYPE OF
 VENTILATION USED
 3) ENERGY CALCS AND MANUAL J DO NOT
 MATCH PLANS
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-20 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 13:11 Rev Time 0.33
Received By jleech Date 2002-06-20 Time 17:43 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-11-07 Cont ID  
Sent By jgomez Date 2002-11-07 Time 14:41 Rev Time 2.00
Received By jgomez Date 2002-11-07 Time 14:41 Sent To  
Notes
2002-11-07 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-STORM SHUTTERS:
 A)DESIGN PRESSURES SPECIFIED HAVE LIMI-
 TATIONS ON PANEL SPAN. SEE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT
 AND REVISE SCHEDULE AS REQUIRED. ALSO,
 CLARIFY ANCHOR USED.
 B)MARK ON DRAWINGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE & SPACING
 TO BE USED.
 2-SPECIFY SIZE OF ANCHOR BOLT AND WASHER
 FOR GARAGE STRUCTURAL BUCK DETAIL.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 3-DETAIL 5/S3 IS MISSING THE CONNECTOR
 TYPE AND SPACING. TRUSS ANCHOR SCHE-
 DULE DOESN'T SPECIFY ANY CONNECTOR AT
 THIS GABLE END AREA.
 4-ROOF SHEATHING & NAILING STATEMENT AND
 DIAPHRAGM SCHEDULE DON'T MATCH. REVISE
 AS REQUIRED. ALSO, REVISE SECTIONS/
 DETAILS TO MATCH AS WELL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-07-09 Cont ID  
Sent By jgomez Date 2002-07-09 Time 19:00 Rev Time 0.00
Received By jgomez Date 2002-07-09 Time 19:00 Sent To  
Notes
2002-07-09 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-ENTRY DOORS DON'T PROVIDE THE 32" MIN.
 CLEAR OPENING REQUIRED BY TABLE 1004
 3-ENERGY CALCULATIONS: A)WRONG MODEL.
 B)THERE ARE NOT ADJACENT FRAMED WALLS.
 C)OWNER/AGENT TO DATE BOTTOM OF FORM TOO
 4-WINDOW BY ENTRY PORCH EXCEEDS THE MAX.
 PERCENTAGE OF OPENINGS ALLOWED BY
 TABLE 600 FBC 2001. REVISE AS REQUIRED
 5-SURVEY IS MISSING SOME SETBACK
 DIMENSIONS (SEE SIDE SETBACKS).
 6-SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AT STAIRS. SEC. 2305 FBC 2001
 **NOTE: FIREBLOCKING & DRAFSTOPPING ARE
 2 DIFFERENT THINGS.
 7-SPECIFY FIRECUT AT MASONRY WALL AS
 REQUIRED BY SEC. 2305.4 FBC 2001.
 8-SPECIFY ON 2ND FL. FRAMING PLAN THE
 LOCATION & MATERIAL FOR DRAFSTOPPING
 AS REQUIRED BY SEC. 2305.2.2 FBC 2001.
 9-PROVIDE SOIL TEST REPORT.
 10-STORM SHUTTERS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 AND KEY PLAN. SEE CITY SAMPLE.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE & STRUCTURE TO BE ATTACHED TO
 (CONCRETE BLOCK OR CONCRETE).
  
 11-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS AS SHOWN ON PLANS.
 B)COMPLETE PANAMERICAN WINDOW MULLION
 PRODUCT APPROVAL.
 C)SINGLE HUNG WINDOWS PRODUCT APPROVAL
 REPORT DOESN'T MATCH DRAWINGS.
 D)GARAGE SIDE SWING DOOR.
 12-PROVIDE UPDATED ORIGINAL LETTER FOR
 MASONRY UNITS USED ADDRESSED TO CITY
 OF W.P.B AND THE CONTRACTOR. AND
 SPECIFY PROJECT.
 13-SHEET C-1 IS MISSING THE INTERNAL
 PRESSURE COEFFICIENT AS REQUIRED BY
 SEC. 1606.1.7 FBC 2001.
 14-PROVIDE COMPLETE GABLE END WALL
 DETAILS FOR GABLE ENDS SHOWN AT FRONT
 ELEVATION. SEE SEC. 2117 FBC 2001.
 15-SEE PLANS FOR COMMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By sgraham Date 2002-06-18 Time 07:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***