Plan Review Details - Permit 02060490
Plan Review Stops For Permit 02060490
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-20 Cont ID  
Sent By hpiskura Date 2002-12-20 Time 08:34 Rev Time 0.00
Received By hpiskura Date 2002-12-19 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-10-15 Cont ID  
Sent By hpiskura Date 2002-10-15 Time 16:12 Rev Time 0.00
Received By hpiskura Date 2002-10-15 Time 13:20 Sent To  
Notes
2002-10-15 00:00:00SHEET A-1.0"CONSTRUCTION TYPE"THE
 CONSTRUCTION TYPE OF THIS BUILDING IS
 TYPEI, FIRE SPRINKLERED NOT THE TYPE IV
 UNPROTECTED DECLARED.THE HEIGHT
 EXCEEDS 80'.
  
  
 PROVIDE AN ELEVATOR LOBBY IN ACCORDANCE
 WITH FBC 412.6.
  
 SHOW EXISTING ATRIUM FACILITIES AS
 COMPLYING WITH FBC 414 OR A SHAFT
 ENCLOSURE INACCORDANCE WITH FBC 705.2.2
 FOR THE AREA SHOWN AS "OPEN TO BELOW"

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-07-23 Cont ID  
Sent By jwitmer Date 2002-07-23 Time 08:09 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By dpalmer Date 2002-12-18 Time 14:19 Rev Time 0.50
Received By dpalmer Date 2002-12-18 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-10-02 Cont ID  
Sent By dpalmer Date 2002-10-02 Time 06:08 Rev Time 0.50
Received By dpalmer Date 2002-10-02 Time 06:08 Sent To  
Notes
2002-10-02 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE PLANS WERE REVIEWED
 AND PASSED ON PREVIOUS ELECTRICAL PLAN
 REVIEW. PLEASE NOTE ALL NEW ELECTRICAL
 SHEETS WERE SUBMITTED ALONG WITH ORIG
 SHEETS. PLEASE NOTE THERE ARE NO
 REVISIONS/CHANGES SHOWN. NO REVISION
 DATES?? PLEASE SUBMIT ONLY ONE SET FOR
 REVIEW. PLEASE TAKE OUT OLD SHEETS AND
 VOID.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-28 Cont ID  
Sent By dpalmer Date 2002-06-28 Time 08:35 Rev Time 0.00
Received By dpalmer Date 2002-06-28 Time 06:35 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-07-23 Cont ID  
Sent By lmartine Date 2002-07-23 Time 11:12 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-12-11 Cont ID  
Sent By mcarsill Date 2002-12-11 Time 15:49 Rev Time 0.00
Received By mcarsill Date 2002-12-11 Time 15:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-02 Cont ID  
Sent By mcarsill Date 2002-10-02 Time 10:45 Rev Time 0.00
Received By mcarsill Date 2002-10-02 Time 10:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-28 Cont ID  
Sent By mcarsill Date 2002-06-28 Time 16:51 Rev Time 0.00
Received By mcarsill Date 2002-06-28 Time 16:51 Sent To  
Notes
2002-06-28 00:00:001) PLEASE INDICATE WHAT "TEMPORARY"
 MEANS WITH REGARDS TO DURATION.
  
 2) PLASTIC MATERIAL PLANNED TO BE HUNG
 FROM FLOOR SLAB IF NOT FIRE RETARDANT
 WILL NOT BE PERMITTED.
  
 3) DEBRIS FROM DEMOLITION SHALL BE
 REMOVED FROM THE BUILDING DAILY.
  
 4) ALL EXITS AND EXIT ACCESS CORRIDORS
 ARE TO BE MAINTAINED AT ALL TIMES
 DURING CONSTRUCTION.
  
 5) ALL FIRE SAFETY EQUIPMENT ARE TO
 REMAIN IN OPERATION DURING DEMOLITION,
 RENOVATION, AND DEMOLITION.
  
 6) DEAD-END CORRIDORS AND TRAVEL
 DISTANCES TO EXITS ARE NOT TO BE
 EXCEEDED FOR ANY REASONS.
  
 7) PLEASE PROVIDE FLAMESPREAD DATA ON
 TEMPORARY ISOLATION WALLS.
  
 8) NO GASOLINE POWERED EQUIPMENT IS TO
 BE USED DUE TO INADEQUATE VENTILATION.
 CARBON MONOXIDE EXPOSURE BECOMES A
 SAFETY ISSUE.
  
 9) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 10) PLANS SHALL DELINEATE THE REQUIRED
 FORTY FOUR INCH WIDTH ESPECIALLY
 BETWEEN WORK STATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-03 Cont ID  
Sent By btrobaug Date 2002-12-03 Time 17:16 Rev Time 0.00
Received By btrobaug Date 2002-12-03 Time 17:16 Sent To  
Notes
2002-12-03 00:00:00COMM BOARD #21./WRT
 #17./WRT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By pkrauss Date 2002-12-18 Time 10:54 Rev Time 0.15
Received By pkrauss Date 2002-12-18 Time 10:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-09 Cont ID  
Sent By pkrauss Date 2002-10-09 Time 13:57 Rev Time 1.00
Received By pkrauss Date 2002-10-09 Time 12:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-12 Cont ID  
Sent By pkrauss Date 2002-06-12 Time 08:52 Rev Time 1.30
Received By pkrauss Date 2002-06-12 Time 08:08 Sent To  
Notes
2002-06-12 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.INDICATE LOCATIONS OF ANY NEW FIRE
 DAMPERS TO BE INSTALLED AS PER 2001
 FBC(M) 607.6.THE FOLLOWING ARE A
 LIST OF PENETRATIONS IN QUESTION.
 CORRIDOR 549 - PLANS SHEET A-2.1
 INDICATES 1HR. CONFERENCE RM 562 HR
 RATING.PLANS ARE UNCLEAR AS TO THE
 RATING OF MECHANICAL, ELECTRICAL &
 STORAGE ROOM.PLEASE CLARIFY.
  
 2.PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 3.AS PER 2001 FBC(M) 602.2.1 MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON-
 COMBUSTIBLE OR SHALL HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 25 &
 A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 50 WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84.
  
 4.PRESSURE DIFFIERENTIALS ACROSS
 CLOSED DOORS SHALL BE LIMITED TO
 .001 IN WC OR LESS.PROVIDE AIR
 TRANSFER PATHWAYS OR AIR DUCT PATH-
 WAYS FOR COMPLIANCE. 2001 FBC(M)
 601.4
  
 5.INDICATE DUCT SMOKE DETECTORS ON
 PLAN - NEW OR EXISTING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status N Date 2002-10-12 Cont ID  
Sent By kstevens Date 2002-10-12 Time 12:45 Rev Time 0.00
Received By kstevens Date 2002-10-12 Time 12:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-07-23 Cont ID  
Sent By lmartine Date 2002-07-23 Time 11:12 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2002-07-23 Cont ID  
Sent By lmartine Date 2002-07-23 Time 11:12 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***