Plan Review Stops For Permit 02060490 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-12-20 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-12-20 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-12-19 |
Time |
10:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-10-15 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-10-15 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2002-10-15 |
Time |
13:20 |
Sent To |
|
|
Notes |
2002-10-15 00:00:00 | SHEET A-1.0"CONSTRUCTION TYPE"THE | | CONSTRUCTION TYPE OF THIS BUILDING IS | | TYPEI, FIRE SPRINKLERED NOT THE TYPE IV | | UNPROTECTED DECLARED.THE HEIGHT | | EXCEEDS 80'. | | | | | | PROVIDE AN ELEVATOR LOBBY IN ACCORDANCE | | WITH FBC 412.6. | | | | SHOW EXISTING ATRIUM FACILITIES AS | | COMPLYING WITH FBC 414 OR A SHAFT | | ENCLOSURE INACCORDANCE WITH FBC 705.2.2 | | FOR THE AREA SHOWN AS "OPEN TO BELOW" |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2002-07-23 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-07-23 |
Time |
08:09 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-12-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-12-18 |
Time |
14:19 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-12-18 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-10-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-10-02 |
Time |
06:08 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2002-10-02 |
Time |
06:08 |
Sent To |
|
|
Notes |
2002-10-02 00:00:00 | **************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE PLANS WERE REVIEWED | | AND PASSED ON PREVIOUS ELECTRICAL PLAN | | REVIEW. PLEASE NOTE ALL NEW ELECTRICAL | | SHEETS WERE SUBMITTED ALONG WITH ORIG | | SHEETS. PLEASE NOTE THERE ARE NO | | REVISIONS/CHANGES SHOWN. NO REVISION | | DATES?? PLEASE SUBMIT ONLY ONE SET FOR | | REVIEW. PLEASE TAKE OUT OLD SHEETS AND | | VOID. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-06-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-28 |
Time |
08:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-28 |
Time |
06:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-07-23 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2002-07-23 |
Time |
11:12 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2002-12-11 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-12-11 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-12-11 |
Time |
15:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-10-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-10-02 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-10-02 |
Time |
10:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-06-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-06-28 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-06-28 |
Time |
16:51 |
Sent To |
|
|
Notes |
2002-06-28 00:00:00 | 1) PLEASE INDICATE WHAT "TEMPORARY" | | MEANS WITH REGARDS TO DURATION. | | | | 2) PLASTIC MATERIAL PLANNED TO BE HUNG | | FROM FLOOR SLAB IF NOT FIRE RETARDANT | | WILL NOT BE PERMITTED. | | | | 3) DEBRIS FROM DEMOLITION SHALL BE | | REMOVED FROM THE BUILDING DAILY. | | | | 4) ALL EXITS AND EXIT ACCESS CORRIDORS | | ARE TO BE MAINTAINED AT ALL TIMES | | DURING CONSTRUCTION. | | | | 5) ALL FIRE SAFETY EQUIPMENT ARE TO | | REMAIN IN OPERATION DURING DEMOLITION, | | RENOVATION, AND DEMOLITION. | | | | 6) DEAD-END CORRIDORS AND TRAVEL | | DISTANCES TO EXITS ARE NOT TO BE | | EXCEEDED FOR ANY REASONS. | | | | 7) PLEASE PROVIDE FLAMESPREAD DATA ON | | TEMPORARY ISOLATION WALLS. | | | | 8) NO GASOLINE POWERED EQUIPMENT IS TO | | BE USED DUE TO INADEQUATE VENTILATION. | | CARBON MONOXIDE EXPOSURE BECOMES A | | SAFETY ISSUE. | | | | 9) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | 10) PLANS SHALL DELINEATE THE REQUIRED | | FORTY FOUR INCH WIDTH ESPECIALLY | | BETWEEN WORK STATIONS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-12-03 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-12-03 |
Time |
17:16 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-12-03 |
Time |
17:16 |
Sent To |
|
|
Notes |
2002-12-03 00:00:00 | COMM BOARD #21./WRT | | #17./WRT |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2002-12-18 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-12-18 |
Time |
10:54 |
Rev Time |
0.15 |
Received By |
pkrauss |
Date |
2002-12-18 |
Time |
10:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-10-09 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-10-09 |
Time |
13:57 |
Rev Time |
1.00 |
Received By |
pkrauss |
Date |
2002-10-09 |
Time |
12:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-06-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-12 |
Time |
08:52 |
Rev Time |
1.30 |
Received By |
pkrauss |
Date |
2002-06-12 |
Time |
08:08 |
Sent To |
|
|
Notes |
2002-06-12 00:00:00 | *******************DENIED*************** | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW. | | | | 1.INDICATE LOCATIONS OF ANY NEW FIRE | | DAMPERS TO BE INSTALLED AS PER 2001 | | FBC(M) 607.6.THE FOLLOWING ARE A | | LIST OF PENETRATIONS IN QUESTION. | | CORRIDOR 549 - PLANS SHEET A-2.1 | | INDICATES 1HR. CONFERENCE RM 562 HR | | RATING.PLANS ARE UNCLEAR AS TO THE | | RATING OF MECHANICAL, ELECTRICAL & | | STORAGE ROOM.PLEASE CLARIFY. | | | | 2.PLEASE PROVIDE OUTSIDE AIR CALCS AS | | PER 2001 FBC(M) TABLE 403.3 OR | | ASHRAE 62-89. | | | | 3.AS PER 2001 FBC(M) 602.2.1 MATERIALS | | EXPOSED WITHIN PLENUMS SHALL BE NON- | | COMBUSTIBLE OR SHALL HAVE A FLAME | | SPREAD INDEX OF NOT MORE THAN 25 & | | A SMOKE-DEVELOPED INDEX OF NOT MORE | | THAN 50 WHEN TESTED IN ACCORDANCE | | WITH ASTM E 84. | | | | 4.PRESSURE DIFFIERENTIALS ACROSS | | CLOSED DOORS SHALL BE LIMITED TO | | .001 IN WC OR LESS.PROVIDE AIR | | TRANSFER PATHWAYS OR AIR DUCT PATH- | | WAYS FOR COMPLIANCE. 2001 FBC(M) | | 601.4 | | | | 5.INDICATE DUCT SMOKE DETECTORS ON | | PLAN - NEW OR EXISTING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2002-10-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-10-12 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-10-12 |
Time |
12:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2002-07-23 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2002-07-23 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2002-07-23 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2002-07-23 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|