Plan Review Details - Permit 02060408
Plan Review Stops For Permit 02060408
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-15 Cont ID  
Sent By bstaples Date 2002-07-15 Time 11:47 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-07-02 Cont ID  
Sent By bstaples Date 2002-07-02 Time 11:47 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2002-07-02 00:00:001. PROVIDE FLORDIA ENERGY SHEETS
 INCLUDING MANUAL J.
 2. NEW DOOR 105 PROVIDE PRODUCT APPROVAL
 INFORMATION FOR WIND LOAD AND IMPACT
 PROTECTION IF GLAZED.
 3. SUBMIT PLANS TO PALM BEACH COUNTY
 IMPACT FEE OFFICE FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-13 Cont ID  
Sent By dpalmer Date 2002-09-13 Time 06:58 Rev Time 0.25
Received By dpalmer Date 2002-09-13 Time 06:57 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-15 Cont ID  
Sent By dpalmer Date 2002-07-15 Time 12:25 Rev Time 0.00
Received By dpalmer Date 2002-07-15 Time 12:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-19 Cont ID  
Sent By dpalmer Date 2002-06-19 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2002-06-19 Time 16:34 Sent To  
Notes
2002-06-19 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE SHOWN EXCEEDS RATING
 OF SERVICE ENTRANCE CONDUCTORS. PLEASE
 NOTE SIZINGPER 310-16.
 SHOWS 2-SETS OF 500MCM, RATED AT 380A`S
 EACH= 760AMPS. PLEASE NOTE 769A SHOWN
 ON LOAD CALCS AND HAS ONLY AN EST FOR
 FUTURE TENANT "OUTREACH".
 PLEASE SHOW A COMPLETE LOAD CALCULATION
 FOR BLDG. PER 220
  
 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 LABELING OF DISCONNECTING MEANS OF
 GENERATOR. INSIDE ELECTRICAL ROOM AND
 OUTSIDE BY MAIN SERVICE. 230-2 E
  
 PLEASE JUST NOTE A MISPRINT FOR PANEL "G
 , PLEASE NOTE SHOWN AS "GP" ON RISER
 DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-09-13 Cont ID  
Sent By dpalmer Date 2002-09-13 Time 06:58 Rev Time 0.00
Received By mcarsill Date 2002-09-13 Time 09:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-12 Cont ID  
Sent By mcarsill Date 2002-07-12 Time 17:35 Rev Time 0.00
Received By mcarsill Date 2002-07-12 Time 17:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-21 Cont ID  
Sent By mcarsill Date 2002-06-21 Time 17:10 Rev Time 0.00
Received By mcarsill Date 2002-06-21 Time 17:10 Sent To  
Notes
2002-06-21 00:00:001) ADDITIONAL EMERGENCY LIGHTING
 FIXTURES APPEAR TO BE NEEDED. OPERATIONS
 AND CORRIDOR DO NOT HAVE ANY EMERGENCY
 LIGHT FIXTURES.
  
 2) EXIT SIGN LOCATED IN KITCHEN IS
 NOT REQUIRED.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW GENERATOR AND FUEL TANK.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-12 Cont ID  
Sent By pkrauss Date 2002-06-12 Time 07:38 Rev Time 0.40
Received By pkrauss Date 2002-06-11 Time 15:28 Sent To  
Notes
2002-06-12 00:00:00MECHANICAL PERMIT 02060523

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-09-17 Cont ID  
Sent By kstevens Date 2002-09-17 Time 15:36 Rev Time 0.00
Received By kstevens Date 2002-09-17 Time 15:36 Sent To  
Notes
2002-09-17 00:00:00REVISION OK SANT RISER DIAGRAM - WATER
 RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-17 Cont ID  
Sent By kstevens Date 2002-07-17 Time 13:44 Rev Time 0.00
Received By kstevens Date 2002-07-17 Time 13:44 Sent To  
Notes
2002-07-17 00:00:00PASSED/PROVISO
  
 WATER COOLER SHALL COMPLY WITH ARI-1010
 INDIRECT WASTE SHALL BE DRAINED TO A
 FLOOR SINK, NOT FLOOR DRAIN.
 VISIBLE AIR GAP REQUIRED FOR T/P DIS-
 CHARGE

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-28 Cont ID  
Sent By kstevens Date 2002-06-28 Time 14:17 Rev Time 0.00
Received By kstevens Date 2002-06-28 Time 14:17 Sent To  
Notes
2002-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) A DRINKING FOUNTAIN AND A SERVICE
 SINK ARE REQUIRED PER TABLE 403.1
 SEE 11-4.15 AND 11-4.1.3(10) PROVIDE
 DETAILS FOR DRINKING FOUNTAIN.
 2) SHT A3 DETAIL #4, SINK TO COMPLY WITH
 11-4.24 PROVIDE DETAILS.
 3) SHT A3 DETAIL #3, URNAL SHALL COMPLY
 WITH 11-4.18.2, MAX HEIGHT 17". SHOW ON
 DETAIL.
 4) SHT P-1 KEYNOTE (2) 2-1/2" AND SMALL-
 ER PIPE SHALL BE RUN AT 1/4" PER FOOT
 PER TABLE 704.1. PLEASE CHANGE NOTE.
 5) SHTS P-1/P-2 WATER HEATER DETAIL, PER
 504.7.1 THE RELIEF (T/P) DISCHARGE LINE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. PROVIDE DETAILS.
 6) SHT P-1 WATER ISOMETRIC SHOWS TWO 1/2
 INCH COLD LINES RUN TO A SINK NOT SHOWN
 ON THE FLOOR PLAN. PLEASE CLAIRFY.
 7) SHT P-1 WATER ISOMETRIC, AIR CHAMBERS
 ARE NOT APPROVED. WATER HAMMERS ARE RE-
 QUIRED FOR ALL QUICK CLOSING VALVES PER
 604.9. (SEE SHT P-2 PLUMBING SYMBOLS &
 ABBREVIATIONS)
 8) SHT P-1 SANITARY ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN. FLOOR DRAINS
 PRIOR TO BACK TO BACK URNAL AND WATER
 CLOSET ARE NOT SHOWN ON SANT. ISO.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377