Plan Review Details - Permit 02060361
Plan Review Stops For Permit 02060361
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2003-01-09 Cont ID  
Sent By dpalmer Date 2003-01-09 Time 12:39 Rev Time 0.00
Received By dpalmer Date 2003-01-09 Time 12:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-19 Cont ID  
Sent By hmoser Date 2002-07-06 Time 06:57 Rev Time 0.00
Received By dpalmer Date 2002-06-19 Time 06:14 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-07-20 Cont ID  
Sent By hmoser Date 2002-07-20 Time 06:39 Rev Time 0.50
Received By hmoser Date 2002-07-20 Time 06:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-07-06 Cont ID  
Sent By hmoser Date 2002-07-06 Time 06:58 Rev Time 0.50
Received By hmoser Date 2002-07-06 Time 06:58 Sent To  
Notes
2002-07-06 00:00:00PLAN DENIED
 1) ENERGY CALCS AND PLANS DO NOT MATCH
 ON A/C EQUIPMENT SEER
 2) NEED LETTER FROM MANUFACTURE STATING
 THAT UNDER ANY CONDITION THE
 AIRHANDLER WILL NOT PRODUCE 2000 CFM
 3) REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 4) VARIFY TYPE OF VENTILATION USED FOR
 FRESH AIR SECTION 402 NATURAL OR
 SECTION 403 MECHANICAL FBC.2001
 5) CALCULATION FOR TYPE OF VENTILATION
 USED
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-18 Cont ID  
Sent By pkrauss Date 2002-06-18 Time 12:56 Rev Time 0.35
Received By hmoser Date 2002-06-18 Time 12:48 Sent To E
Notes
2002-06-18 00:00:00 
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-15 Cont ID  
Sent By jleech Date 2002-06-15 Time 07:17 Rev Time 0.33
Received By jleech Date 2002-06-15 Time 07:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-07-01 Cont ID  
Sent By lsmith Date 2002-07-01 Time 12:23 Rev Time 2.30
Received By lsmith Date   Time   Sent To  
Notes
2002-07-01 00:00:00BUILDING PLAN PROOVISO: REVIEW NOTES:
  
 1. PROPERTY IS IN FLOOD ZONE "AO" NEED
 ELEVATION CERTIFICATE BEFORE C/O
  
 2. NEED IMPACT FEES PAID TO PBC &
 STAMPED & RECEIPT BEFORE ISSUE OF
 PERMITS. OK 7/12/02 REC#02024898 PD
 7/3/02

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-01 Cont ID  
Sent By lsmith Date 2002-07-01 Time 15:14 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2002-07-01 00:00:00PER SG 7/1/02 LS