Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-06-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2002-06-27 |
Time |
14:02 |
Rev Time |
1.00 |
Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-06-27 00:00:00 | DENIED | | | | 1) THE BASIC WIND SPEED INDICATED ON THE | | ASCE 7-98 CHART IS INNCORRECT. THE BASIC | | WIND SPEED FOR THE CITY OF WPB IS 140MPH | | PLEASE CORRECT. | | | | 2) THE PRODUCT APPROVAL SUBMITTED IS NOT | | FOR ACCORDION SHUTTERS. PLEASE SUBMIT | | (2) COPIES OF PRODUCT APPROVALS FOR | | ACCORDION SHUTTERS. | | | | 3) THE APPROVED DRAWINGS STATE THAT | | SHUTTER SPANS LESS THAN 32" ARE NOT | | ACCEPTABLE. THERE ARE THREE OPENINGS | | WITH SPANS LESS THAN 32". PLEASE | | REVISE. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)659-8096 EXT.8202 |
|
|
|