Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-13 Cont ID  
Sent By rbrown Date 2002-09-13 Time 14:14 Rev Time 0.00
Received By rbrown Date 2002-09-13 Time 14:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-16 Cont ID  
Sent By btrobaug Date 2002-09-12 Time 17:21 Rev Time 0.00
Received By rbrown Date 2002-08-16 Time 15:45 Sent To  
Notes
2002-08-16 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 4) THE SUBMITTED PRO-PANEL II PRODUCT
 APPROVAL IS FOR A WALL SYSTEM AND IS NOT
 APPLICABLE TO THE PROPOSED PRO-PANEL II
 METAL ROOFING.SUBMIT AN APPROPRIATE
 ROOFING PRODUCT APPROVAL.
  
 5) FRENCH DOOR PRODUCT APPROVAL, NOTICE
 OF ACCEPTANCE # 99-0902.04 STATES THAT
 A HURRICANE PROTECTION SYSTEM IS
 REQUIRED.SPECIFY EITHER IMPACT
 RESISTANT DOORS OR HURRICANE MISSILE
 IMPACT PROTECTION SHUTTERS.IF SHUTTERS
 ARE TO BE USED, HOW WILL THE OCCUPANTS
 GET BACK INTO THE BUILDING AFTER
 INSTALLATION?
  
 6) CASEMENT WINDOWS G, L AND M.TWO
 DIFFERENT PRODUCT APPROVALS, BOTH PGT
 (NOA # 00-0804.03 AND 01-1108.07), WERE
 SUBMITTED AS SINGLE COPIES.ADVISE
 WHICH IS TO BE USED AND SUBMIT AN
 ADDITIONAL COPY.
  
 7) SINGLE HUNG WINDOW PRODUCT APPROVAL
 NOTICE OF ACCEPTANCE # 01-0629.08 OFFERS
 TWO GLAZING OPTIONS, BOTH SINGLE GLAZED.
 THE WINDOW SCHEDULE PROPOSES DOUBLE
 GLAZED UNITS FOR WINDOWS I AND J.THESE
 ARE OUTSIDE THE SCOPE OF THE SUBMITTED
 PRODUCT APPROVAL.
  
 8) FBC 2101.3.1SPECIFY WINDOW AND DOOR
 LINTELS.
  
 9) FBC 2405.2THE FRENCH DOOR GLAZING
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 10) FBC 2309.6ACCESS TO THE ATTIC.
 AN INTERIOR ACCESS OPENING NOT LESS THAN
 20X36 INCHES SHALL BE PROVIDED.
  
 11) FBC 2309.7VENTILATION OF ATTIC
 SPACE.PROVIDE CROSS VENTILATION USING
 SCREENED VENTS WITH A TOTAL AREA NOT
 LESS THAN 1/150 OF THE CEILING AREA.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-13 Cont ID  
Sent By btrobaug Date 2003-11-13 Time 15:53 Rev Time 0.50
Received By btrobaug Date 2003-11-13 Time 15:43 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-09-12 Cont ID  
Sent By btrobaug Date 2002-09-12 Time 17:21 Rev Time 0.00
Received By btrobaug Date 2002-09-12 Time 16:37 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-08-14 Cont ID  
Sent By btrobaug Date 2002-08-14 Time 15:37 Rev Time 0.00
Received By btrobaug Date 2002-08-14 Time 15:07 Sent To M
Notes
2002-08-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION, MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.NO OTHER
 RECEPTACLES OUTSIDE THE ROOM.
  
 3} PLEASE NOTE THAT AN EQUIPMENT
 GROUNDING CONDUCTOR IS REQUIRED FROM
 THE DISCONNECT TO THE PANEL UNLESS THE
 CONDUIT IS METAL AND BONDED.
  
 4} PLEASE INDICATE THE LOCATION OF THE
 SERVICE ON THE DRAWING.
  
 5} NOTE THAT A RECEPTACLE IS REQUIRED
 IN BEDROOM #2 TO COMPLY WITH
 210-52(A)(1)(A).
  
 6} PLEASE NOTE THAT ALL KITCHEN
 COUNTERTOP RECEPTACLES MUST BE
 GFI'S.(ONE NOT LABLED )
  
 7} PLEASE CHECK THE CLEARANCE BETWEEN
 THE PANEL AND THE WATER HEATER TO
 COMPLY WITH 110-26.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-12 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:11 Rev Time 0.00
Received By csiegber Date 2003-11-12 Time 14:48 Sent To  
Notes
2003-11-12 00:00:00TO BT DESK/REV

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-20 Cont ID  
Sent By pkrauss Date 2003-11-20 Time 08:41 Rev Time 0.45
Received By pkrauss Date 2003-11-20 Time 08:07 Sent To  
Notes
2003-11-20 00:00:00PROVISO:
 EMERGENCY DRAIN SHALL TERMINATE AT A
 CONSPICUOUS POINT PER 2001 FBC(M)307.2.3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-14 Cont ID  
Sent By btrobaug Date 2003-11-13 Time 15:53 Rev Time 0.35
Received By pkrauss Date 2002-08-14 Time 15:20 Sent To P
Notes
2002-08-14 00:00:00PROVISO:MECHANICAL PERMIT 02060044
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-14 Cont ID  
Sent By pkrauss Date 2002-08-14 Time 16:19 Rev Time 0.00
Received By kstevens Date 2002-08-14 Time 18:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-14 Cont ID  
Sent By sgraham Date 2002-08-14 Time 14:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***