Plan Review Stops For Permit 02051829 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2004-02-26 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-02-26 |
Time |
10:34 |
Rev Time |
1.50 |
Received By |
alange |
Date |
2004-02-26 |
Time |
10:34 |
Sent To |
M |
|
Notes |
2004-02-26 00:00:00 | BUILDING OK PLANS STAMPED, NEEDS MECH | | REVIEW. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2004-02-19 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-02-19 |
Time |
08:38 |
Rev Time |
1.00 |
Received By |
alange |
Date |
2004-02-19 |
Time |
08:38 |
Sent To |
|
|
Notes |
2004-02-19 00:00:00 | NOT ABLE TO RESTAMP.REVISIONS HAVE | | BEEN MADE. SECOND SET OF DRAWINGS | | REQUIRED. | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2003-01-23 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-02-12 |
Time |
11:02 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2003-01-23 |
Time |
15:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-07-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-07-24 |
Time |
09:30 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2002-07-24 |
Time |
09:30 |
Sent To |
|
|
Notes |
2002-07-24 00:00:00 | | | BUILDING PLAN REVIEW | | PERMIT: 02051829 | | ADD: 477 S ROSEMARY AV # 330 | | CONT: | | TEL: (561)315-9515 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1) SUBMIT ORIGINAL PERMIT APPLICATION | | WITH RESUBMITTALS. | | | | 2) PLANS, SPECIFICATIONS,REPORTS OR | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | TO THE DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | ENGINEERS CALS COPIES, NOT ORIGINALS!!!! | | | | 3) THE RESIDENCY PART OF THIS UNIT IS TO | | COMPLY WITH FAIR HOUSING, THE COMMERCIAL | | STUDIO! IS TO COMPLY WITH FL. ACCESSIBIL | | ITY, 11-4.13.6 MANEUVERING CLEARENCES | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | AT DOORS THAT ARE NOT AUTOMATIC OR | | POWER-ASSISTED SHALL BE AS SHOWN IN | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | IN THE REQUIRED CLEARENCES SHALL BE | | CLEAR & LEVEL. | | | | 4) FL BLDG CODE CHAP 11 -4.1(1)A RAISED | | AREAS ARE REQUIRED TO BE HANDICAPPED | | ACCESSIBLE. | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | ON THE APPLICATION, PLANS, OR ATTACHED | | SEPARATELY. WHEN RESUBMITTING PLANS | | PLEASE CLEARLY INDICATE THE REVISION AND | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | ARY. A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A | | DESCRIPTION OF THE REVISION MADE, IDEN- | | TIFYING THE SHEET OR SPECIFICATION PAGE | | WHERE THE CHANGES CAN BE FOUND, WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | JIM WITMER | | PLAN REVIEW | | TEL: (561)659-8096 EX.8412 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2002-06-05 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-06-05 |
Time |
11:37 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-06-05 00:00:00 | PLEASE PROVIDE A DETAILED ENGINEERING | | ANALYSIS FOR THE ADDED FLOOR LOADING OF | | THE PROPOSED FOUR INCHES OF CONCRETE. | | SEE FBC 1601.2. | | | | THE RAISED AREAS ARE REQUIRED TO BE | | HANDICAP ACCESSIBLE.SEE FBC | | 11-4.1(1)(A) | | | | DOORS #4,#5,#6, AND #7 DO NOT HAVE THE | | MANEUVERING CLEARANCE REQUIED BY FBC | | 11-4.13.6 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2004-05-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-05-14 |
Time |
09:03 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-05-14 |
Time |
09:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2004-05-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-05-13 |
Time |
07:59 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-05-13 |
Time |
07:58 |
Sent To |
|
|
Notes |
2004-05-13 00:00:00 | *** UNSAT *** | | | | 1) NOTE : PLEASE SEE 61G15-23.002, | | PLEASE INCLUDE ALL INFORMATION ON TITLE | | BLOCK AS REQ'D. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-05-11 |
Time |
16:31 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2003-07-21 |
Time |
16:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2003-07-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-07-15 |
Time |
11:59 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2003-07-15 |
Time |
11:59 |
Sent To |
M |
|
Notes |
2003-07-15 00:00:00 | ***************** UNSAT**************** | | | | 1)NOTE: PLEASE SEE MISSING BLOCK FOR | | ENGINEER OF RECORD. REQ'D UNDER FAC | | 61G15-23.002 | | PLEASE INCLUDE ALL INFORMATION SET FORTH | | UNDER SEC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2003-02-05 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-14 |
Time |
15:01 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2003-02-05 |
Time |
13:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2003-01-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-23 |
Time |
06:41 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-01-23 |
Time |
06:41 |
Sent To |
|
|
Notes |
2003-01-23 00:00:00 | *********** UNSAT **************** | | | | PLEASE NOTE, PLANS HAVE BEEN REVISED | | FROM ORIG SUBMITTAL AND HAVE CHANGED | | ELECTRICAL RISER AND LAYOUT. PLEASE SEE | | THE FOLLOWING COMMENTS. | | | | 1)NOTE: PLEASE SEE FLOOR PLAN, SHOWS | | PANELS "A" AND "T",PLEASE SEE RISER | | DIAGRAM, SHOWS "LA" & "LB? PLEASE SEE | | PANEL SCHEDULES SUBMITTED, SHOWS "LA" | | "T" AND "M"?? PLEASE CORRELATE. | | | | 2)NOTE: PLEASE SEE 384-16 FOR MCB REQ`D | | ON SECCONDARY SIDE OF TRANSFORMER FOR | | LIGHTING/APPL PANEL. | | | | 3)NOTE: PLEASE SHOW TRACK LIGHTING PER | | 220-12B. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-06-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-06-06 |
Time |
05:47 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-06-05 |
Time |
16:50 |
Sent To |
|
|
Notes |
2002-06-06 00:00:00 | ********** NOTE***** | | | | PLAN REDLINED FOR GROUNDING OF TRANS- | | -FORMER. 250-30 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2002-06-11 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-11 |
Time |
10:26 |
Rev Time |
0.05 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2003-01-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-01-17 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-01-17 |
Time |
16:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-05-31 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-31 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-31 |
Time |
12:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2004-05-11 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-05-11 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-05-11 |
Time |
16:31 |
Sent To |
E |
|
Notes |
2004-05-11 00:00:00 | TO DP DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2004-02-26 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-02-26 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2004-02-26 |
Time |
09:16 |
Sent To |
|
|
Notes |
2004-02-26 00:00:00 | TO ART L DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-02-12 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-02-12 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-02-12 |
Time |
11:02 |
Sent To |
B |
|
Notes |
2004-02-12 00:00:00 | TO JW DESK/RESTAMP PLANS DUP PERMIT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2004-01-12 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-01-12 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-01-12 |
Time |
09:53 |
Sent To |
M |
|
Notes |
2004-01-12 00:00:00 | TO HM DESK/PER REQUEST |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-07-14 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-07-14 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-07-14 |
Time |
15:00 |
Sent To |
E |
|
Notes |
2003-07-14 00:00:00 | DP DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-01-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-09 |
Time |
18:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-01-09 |
Time |
18:37 |
Sent To |
|
|
Notes |
2003-01-09 00:00:00 | TO COMM BOARD #22 B>F>E>M | | TRADES ABOVE DUE TO NEW SHEETS FOR E>M |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2004-03-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-03-01 |
Time |
14:27 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2004-03-01 |
Time |
14:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2004-01-12 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2004-02-26 |
Time |
10:47 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2004-01-12 |
Time |
15:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2003-07-16 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-01-12 |
Time |
09:53 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2003-07-16 |
Time |
11:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2003-01-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-07-15 |
Time |
12:00 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2003-01-22 |
Time |
09:24 |
Sent To |
|
|
Notes |
2003-01-22 00:00:00 | PROVISO: | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | IN NORMALLY OCCUPIED AREAS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-07-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-07-31 |
Time |
07:14 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2002-07-24 |
Time |
07:15 |
Sent To |
|
|
Notes |
2002-07-31 00:00:00 | PROVISO ON PLAN |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-06-11 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-06-11 |
Time |
10:06 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2002-06-11 |
Time |
09:57 |
Sent To |
|
|
Notes |
2002-06-11 00:00:00 | *******************DENIED*************** | | | | PLEASE PROVIDE OUTSIDE ARE CALCUALTIONS | | AS PER 2001 FBC(M) TABLE 403.3 OR | | ASHRAE 62-89. | | | | PROVIDE MANUFACTURER INSTALLATION DATA | | FOR THE CONDENSER UNIT STANDS OR | | ENGINEERED DETAIL. | | | | WHERE EQUIPMENT & APPLIANCES REQUIRING | | ACCESS ARE INSTALLED ON ROOFS AT A | | HEIGHT EXCEEDING 16 FT SHALL HAVE A | | PERMANENT MEANS OF ACCESS.2001 FBC(M) | | 306.5. | | | | INDICATE ALL NEW OR EXISTING FIRE | | DAMPERS ON PLAN AS PER 2001 FBC(M) | | 607.6. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|