Plan Review Details - Permit 02051829
Plan Review Stops For Permit 02051829
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-02-26 Cont ID  
Sent By alange Date 2004-02-26 Time 10:34 Rev Time 1.50
Received By alange Date 2004-02-26 Time 10:34 Sent To M
Notes
2004-02-26 00:00:00BUILDING OK PLANS STAMPED, NEEDS MECH
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-02-19 Cont ID  
Sent By alange Date 2004-02-19 Time 08:38 Rev Time 1.00
Received By alange Date 2004-02-19 Time 08:38 Sent To  
Notes
2004-02-19 00:00:00NOT ABLE TO RESTAMP.REVISIONS HAVE
 BEEN MADE. SECOND SET OF DRAWINGS
 REQUIRED.
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-01-23 Cont ID  
Sent By csiegber Date 2004-02-12 Time 11:02 Rev Time 0.55
Received By jwitmer Date 2003-01-23 Time 15:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-24 Cont ID  
Sent By jwitmer Date 2002-07-24 Time 09:30 Rev Time 1.00
Received By jwitmer Date 2002-07-24 Time 09:30 Sent To  
Notes
2002-07-24 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02051829
 ADD: 477 S ROSEMARY AV # 330
 CONT:
 TEL: (561)315-9515
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SUBMIT ORIGINAL PERMIT APPLICATION
 WITH RESUBMITTALS.
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 ENGINEERS CALS COPIES, NOT ORIGINALS!!!!
  
 3) THE RESIDENCY PART OF THIS UNIT IS TO
 COMPLY WITH FAIR HOUSING, THE COMMERCIAL
 STUDIO! IS TO COMPLY WITH FL. ACCESSIBIL
 ITY, 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 4) FL BLDG CODE CHAP 11 -4.1(1)A RAISED
 AREAS ARE REQUIRED TO BE HANDICAPPED
 ACCESSIBLE.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-05 Cont ID  
Sent By hpiskura Date 2002-06-05 Time 11:37 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-05 00:00:00PLEASE PROVIDE A DETAILED ENGINEERING
 ANALYSIS FOR THE ADDED FLOOR LOADING OF
 THE PROPOSED FOUR INCHES OF CONCRETE.
 SEE FBC 1601.2.
  
 THE RAISED AREAS ARE REQUIRED TO BE
 HANDICAP ACCESSIBLE.SEE FBC
 11-4.1(1)(A)
  
 DOORS #4,#5,#6, AND #7 DO NOT HAVE THE
 MANEUVERING CLEARANCE REQUIED BY FBC
 11-4.13.6

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-05-14 Cont ID  
Sent By dpalmer Date 2004-05-14 Time 09:03 Rev Time 0.33
Received By dpalmer Date 2004-05-14 Time 09:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-05-13 Cont ID  
Sent By dpalmer Date 2004-05-13 Time 07:59 Rev Time 0.33
Received By dpalmer Date 2004-05-13 Time 07:58 Sent To  
Notes
2004-05-13 00:00:00*** UNSAT ***
  
 1) NOTE : PLEASE SEE 61G15-23.002,
 PLEASE INCLUDE ALL INFORMATION ON TITLE
 BLOCK AS REQ'D.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-07-21 Cont ID  
Sent By csiegber Date 2004-05-11 Time 16:31 Rev Time 0.33
Received By dpalmer Date 2003-07-21 Time 16:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-07-15 Cont ID  
Sent By dpalmer Date 2003-07-15 Time 11:59 Rev Time 0.33
Received By dpalmer Date 2003-07-15 Time 11:59 Sent To M
Notes
2003-07-15 00:00:00***************** UNSAT****************
  
 1)NOTE: PLEASE SEE MISSING BLOCK FOR
 ENGINEER OF RECORD. REQ'D UNDER FAC
 61G15-23.002
 PLEASE INCLUDE ALL INFORMATION SET FORTH
 UNDER SEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-05 Cont ID  
Sent By shernand Date 2003-07-14 Time 15:01 Rev Time 0.75
Received By dpalmer Date 2003-02-05 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-01-28 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 06:41 Rev Time 0.50
Received By dpalmer Date 2003-01-23 Time 06:41 Sent To  
Notes
2003-01-23 00:00:00*********** UNSAT ****************
  
 PLEASE NOTE, PLANS HAVE BEEN REVISED
 FROM ORIG SUBMITTAL AND HAVE CHANGED
 ELECTRICAL RISER AND LAYOUT. PLEASE SEE
 THE FOLLOWING COMMENTS.
  
 1)NOTE: PLEASE SEE FLOOR PLAN, SHOWS
 PANELS "A" AND "T",PLEASE SEE RISER
 DIAGRAM, SHOWS "LA" & "LB? PLEASE SEE
 PANEL SCHEDULES SUBMITTED, SHOWS "LA"
 "T" AND "M"?? PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE 384-16 FOR MCB REQ`D
 ON SECCONDARY SIDE OF TRANSFORMER FOR
 LIGHTING/APPL PANEL.
  
 3)NOTE: PLEASE SHOW TRACK LIGHTING PER
 220-12B.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-06 Cont ID  
Sent By dpalmer Date 2002-06-06 Time 05:47 Rev Time 0.00
Received By dpalmer Date 2002-06-05 Time 16:50 Sent To  
Notes
2002-06-06 00:00:00********** NOTE*****
  
 PLAN REDLINED FOR GROUNDING OF TRANS-
 -FORMER. 250-30

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 10:26 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-01-17 Cont ID  
Sent By mcarsill Date 2003-01-17 Time 16:36 Rev Time 0.00
Received By mcarsill Date 2003-01-17 Time 16:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-31 Cont ID  
Sent By mcarsill Date 2002-05-31 Time 12:46 Rev Time 0.00
Received By mcarsill Date 2002-05-31 Time 12:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-05-11 Time 16:31 Rev Time 0.00
Received By csiegber Date 2004-05-11 Time 16:31 Sent To E
Notes
2004-05-11 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-26 Cont ID  
Sent By alange Date 2004-02-26 Time 09:16 Rev Time 0.00
Received By alange Date 2004-02-26 Time 09:16 Sent To  
Notes
2004-02-26 00:00:00TO ART L DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 11:02 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 11:02 Sent To B
Notes
2004-02-12 00:00:00TO JW DESK/RESTAMP PLANS DUP PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-12 Time 09:53 Rev Time 0.00
Received By csiegber Date 2004-01-12 Time 09:53 Sent To M
Notes
2004-01-12 00:00:00TO HM DESK/PER REQUEST

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-14 Cont ID  
Sent By shernand Date 2003-07-14 Time 15:01 Rev Time 0.00
Received By shernand Date 2003-07-14 Time 15:00 Sent To E
Notes
2003-07-14 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-09 Cont ID  
Sent By dpalmer Date 2003-01-09 Time 18:37 Rev Time 0.00
Received By dpalmer Date 2003-01-09 Time 18:37 Sent To  
Notes
2003-01-09 00:00:00TO COMM BOARD #22 B>F>E>M
 TRADES ABOVE DUE TO NEW SHEETS FOR E>M

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2004-03-01 Cont ID  
Sent By pkrauss Date 2004-03-01 Time 14:27 Rev Time 0.40
Received By pkrauss Date 2004-03-01 Time 14:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-01-12 Cont ID  
Sent By alange Date 2004-02-26 Time 10:47 Rev Time 0.50
Received By hmoser Date 2004-01-12 Time 15:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-07-16 Cont ID  
Sent By csiegber Date 2004-01-12 Time 09:53 Rev Time 0.45
Received By pkrauss Date 2003-07-16 Time 11:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-01-22 Cont ID  
Sent By dpalmer Date 2003-07-15 Time 12:00 Rev Time 0.50
Received By pkrauss Date 2003-01-22 Time 09:24 Sent To  
Notes
2003-01-22 00:00:00PROVISO:
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-24 Cont ID  
Sent By pkrauss Date 2002-07-31 Time 07:14 Rev Time 0.00
Received By pkrauss Date 2002-07-24 Time 07:15 Sent To  
Notes
2002-07-31 00:00:00PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 10:06 Rev Time 0.45
Received By pkrauss Date 2002-06-11 Time 09:57 Sent To  
Notes
2002-06-11 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE OUTSIDE ARE CALCUALTIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 PROVIDE MANUFACTURER INSTALLATION DATA
 FOR THE CONDENSER UNIT STANDS OR
 ENGINEERED DETAIL.
  
 WHERE EQUIPMENT & APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS AT A
 HEIGHT EXCEEDING 16 FT SHALL HAVE A
 PERMANENT MEANS OF ACCESS.2001 FBC(M)
 306.5.
  
 INDICATE ALL NEW OR EXISTING FIRE
 DAMPERS ON PLAN AS PER 2001 FBC(M)
 607.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.