Plan Review Details - Permit 02051730
Plan Review Stops For Permit 02051730
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-31 Cont ID  
Sent By pkrauss Date 2002-05-31 Time 10:27 Rev Time 0.35
Received By pkrauss Date 2002-05-31 Time 10:24 Sent To  
Notes
2002-05-31 00:00:00PROVISO:
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.