Plan Review Details - Permit 02051637
Plan Review Stops For Permit 02051637
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-13 Cont ID  
Sent By dpalmer Date 2002-06-13 Time 06:00 Rev Time 0.00
Received By dpalmer Date 2002-06-13 Time 05:59 Sent To B
Notes
2002-06-13 00:00:00********** NOTE*********
  
 NOTE REDLINED FOR POSSIBLE DEATCHED
 STRUCTURE. PER 225-31 TO FEILD VERIFY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-06-11 Cont ID  
Sent By hmoser Date 2002-06-11 Time 19:32 Rev Time 0.50
Received By hmoser Date 2002-06-11 Time 19:31 Sent To  
Notes
2002-06-11 00:00:00PASS/PROVISO
 1) VARIFY TYPE OF VENTILATION USED FOR
 FRESH AIR NATURAL SECTION 402 FBC.OR
 MECHANICAL SECTION 403 FBC.
 2) CALCULATIONS FOR TYPE OF VEVTILATION
 USED
 3)REFER TO SECTION 304.4 PRIVATE GARAGES
 FBC.
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-06-04 Cont ID  
Sent By jleech Date 2002-06-04 Time 18:57 Rev Time 0.33
Received By jleech Date 2002-06-04 Time 18:57 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-06-18 Cont ID  
Sent By lhatten Date 2002-06-18 Time 14:48 Rev Time 2.50
Received By lhatten Date 2002-06-15 Time 14:47 Sent To  
Notes
2002-06-18 00:00:00REVIEW & STAMPED PLANS06/15/2002
 CALC. FEES & PRINT CARDS 06/18/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-29 Cont ID  
Sent By sgraham Date 2002-05-29 Time 16:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***