Plan Review Details - Permit 02051561
Plan Review Stops For Permit 02051561
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-09-08 Cont ID  
Sent By jwitmer Date 2002-09-08 Time 15:22 Rev Time 0.55
Received By btrobaug Date   Time   Sent To  
Notes
2002-09-08 00:00:00PROVIDE COUNTY IMPACT FEE RECEIPT AND
 STAMPED PLANS!!!

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-08-15 Cont ID  
Sent By jwitmer Date 2002-08-15 Time 07:27 Rev Time 1.25
Received By jwitmer Date 2002-08-15 Time 07:27 Sent To  
Notes
2002-08-15 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02051561
 ADD: 900 BRANDYWINE ROAD
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SHEET S1.0 ALSO REQUIRES SOILS TEST.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) EXTERIOR SWING DOOR
 B) OVERHEAD GARAGE DOOR
 C) ROOFING ASSEMBLIES
  
 4) 1606.1.4. INDICATE PRESSURE ZONES ON
 ALL OPENINGS.
  
 5)1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 6)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 7)1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 8)MEANS OF EGRESS: A CONTINUOUS AND
 UNOBSTRUCTED WAY OF TRAVEL FROM ANY
 POINT IN A BUILDING OR STRUCTURE TO A
 PUBLIC WAY, CONSISTING OF THREE SEPERATE
 AND DISTINCT PARTS: (1) THE WAY OF THE
 EXIT ACCESS, (2) THE EXIT, AND (3) THE
 THE WAY OF OF THE EXIT DISCHARGE.
 A MEANS OF EGRESS COMPRISES THE VERTICAL
 AND HORIZONTAL WAYS OF TRAVEL AND
 INCLUDE THE INTERVENING ROOM SPACE,DOORS
 CORRIDORS,PASSAGEWAYS,BALCONIES, STAIRS,
 RAMPS, ENCLOSURES, LOBBIES, HORIZONTAL
 EXITS, COURTS AND YARDS.
 A FOLDING STAIRWAY IS NOT CONSIDERED
 A MEANS OF EGRESS FOR A LOFT STORAGE
 AREA! THIS IS A PUBLIC BUILDING NOT A
 PRIVATE RESIDENCE.
  
 9) 1027.1.1. STORAGE, SINGLE EXIT,
 (3) A SINGLE EXIT IS ALLOWABLE WHEN THE
 TRAVEL DISTANCE TO THE EXIT DOES NOT
 EXCEED 50 FT. IN A DIAGONAL FROM THE
 FURTHEST CORNER TO THE EXIT DOOR, 55 FT.
 WHEN VEHICLES ARE IN THE STALLS IT WILL
 BE FURTHER.
  
 10) 1016.3.1 EXIT SIGNAGE REQUIRED OVER
 EGRESS DOOR.
  
 11) DESIGNER OF RECORD TO APPROVE TRUSS
 PLANS PRIOR TO INSTALLATION, SUBMIT TO
 CITY VIA FIELD INSPECTOR AFTER ROOF
 FRAMING INSPECTION.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-25 Cont ID  
Sent By bstaples Date 2002-06-25 Time 14:23 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2002-06-25 00:00:00PLAN REVIEW NOTES 6/25/02.
 1. SUBMIT TO PLAM BEACH COUNTY FOR
 DETERMINATION ON IMPACT FEES DUE.
 2. PROVIDE PRODUCT APPROVAL INFORMATION
 FOR DOORS, GARAGE AND MAN.
 3. STORAGE IN ATTIC PROVIDE ENGINEERING
 FOR LIGHT OR HEAVY SEE TABLE 1604.1.
 4. PULL DOWN STAIR NOT PERMITTED FOR
 ACCESS TO STORAGE AREA SEE CHAPTER 10
 FBC FOR ALLOWABLE DESIGNS.
 5. PROVIDE ENGINEERING DETAILS FOR
 ANCHORING OF DOORS UNLESS SPECIFIED ON
 PRODUCT APPROVALS.
 6. PROVIDE PRESSURE VALUSE FOR OPENINGS
 TO COMPAIR TO PRODUCT SUBMITTAL FOR
 DOORS.
 7. PROVIDE SOIL TEST REPORT.
 8. FLOOD ZONE IS A-8 ELEVATION 16
 PROVIDE FLOOD CERTIFICATION.
 9. SUBMIT PALNS TO HEALTH DEPARTMENT FOR
 APPROVAL OF PUBLIC SHOWERS.
 10. DESIGNER OF RECORD TO APPROVE TRUSS
 PLANS PRIOR TO INSTALLATION, SUBMIT TO
 CITY FOR FILE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-09-10 Cont ID  
Sent By dpalmer Date 2002-09-10 Time 15:09 Rev Time 0.25
Received By dpalmer Date 2002-09-10 Time 15:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-02 Cont ID  
Sent By dpalmer Date 2002-08-02 Time 06:15 Rev Time 0.00
Received By dpalmer Date 2002-08-02 Time 06:15 Sent To  
Notes
2002-08-02 00:00:00OK

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-06-26 Cont ID  
Sent By dpalmer Date 2002-06-26 Time 06:47 Rev Time 0.00
Received By dpalmer Date 2002-06-26 Time 06:47 Sent To  
Notes
2002-06-26 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE NO INFORMATION IS
 SHOWN FOR NEW PANEL. SIZE??
  
 2)NOTE: PLEASE NOTE MEANS OF DISC FOR
 DETACHED STRUCTURE PER 225-31
 DISC? MCB?
  
 3)NOTE: PLEASE CLARIFY GROUNDING OF NEW
 TRANSFORMER PER 250-30
  
 4)NOTE: PLEASE ALSO NOTE COLD WATER PIPE
 AT DETACHED BLDG TO BE BONDED. PLEASE
 SHOW. 250-32
  
 5)NOTE: PLEASE NOTE PLANS MENTIONS SEE
 NOTE "F" AND NO NOTE "F" IS SHOWN?
 PLEASE CLARIFY.
  
 6)NOTE: PLEASE VERIFY 240-21-C-4
 MUST MEET ALL EXPT.
  
 7)NOTE: PLEASE VERIFY USE OF GARAGE/
 USED FOR STORAGE OF VEHICLES ONLY?
 NO WORKING ON VEHICLES? NEC 511-2
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THEREARE ANY QUESTINS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-06-25 Cont ID  
Sent By mamini Date 2002-06-25 Time 16:09 Rev Time 0.00
Received By mamini Date 2002-06-25 Time 16:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-09-12 Cont ID  
Sent By mcarsill Date 2002-09-12 Time 11:57 Rev Time 0.00
Received By mcarsill Date 2002-09-12 Time 11:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-08-06 Cont ID  
Sent By mcarsill Date 2002-08-06 Time 14:54 Rev Time 0.00
Received By mcarsill Date 2002-08-06 Time 14:54 Sent To  
Notes
2002-08-06 00:00:00PLEASE SEE PREVIOUS PLAN REVIEW COMMENTS
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-21 Cont ID  
Sent By mcarsill Date 2002-06-21 Time 16:00 Rev Time 0.00
Received By mcarsill Date 2002-06-21 Time 16:00 Sent To  
Notes
2002-06-21 00:00:001) ONLY A SINGLE MEANS OF EGRESS
 PROVIDED FROM STORAGE GARAGE. AT LEAST
 TWO MEANS OF EGRESS ARE TO BE PROVIDED
 IF NOT A LOW HAZARD OCCUPANCY. LOW
 HAZARD OCCUPANCY IS DEFINED AS "LOW
 COMBUSTIBILITY THAT NO SELF-PROPAGATING
 FIRE THEREIN CAN OCCUR".
  
 2) SINCE NO WINDOWS APPEAR TO BE
 PRESENT, EXIT SIGN(S) WILL BE
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-24 Cont ID  
Sent By pkrauss Date 2002-09-24 Time 11:16 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-08-12 Cont ID  
Sent By pkrauss Date 2002-08-12 Time 12:56 Rev Time 0.45
Received By pkrauss Date 2002-08-12 Time 12:24 Sent To  
Notes
2002-08-12 00:00:00PLEASE INDICATE IF THE FAN FOR THE
 GARAGE WILL BE RUN CONTINUOUSLY.
  
 THE STORAGE AREAS DO NOT SHOW ANY TYPE
 OF VENTILATION, ARE THESE AREAS NEW OR
 EXISTING?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-08-13 Cont ID  
Sent By kstevens Date 2002-08-13 Time 14:28 Rev Time 0.00
Received By kstevens Date 2002-08-13 Time 14:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-06-28 Cont ID  
Sent By kstevens Date 2002-06-28 Time 17:10 Rev Time 0.00
Received By kstevens Date 2002-06-28 Time 17:10 Sent To Z
Notes
2002-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) WHERE ARE THE TOILET FACILITIES FOR
 PERSONS WORKING IN THE GARAGE?
 2) WHAT IS THE REASON FOR THE SHOWERS?
 OUTSIDE SHOWERS ARE NOT ALLOWED TO DRAIN
 INTO THE SANITARY SYSTEM.
 3) PLEASE INDICATE WHAT TYPE OF WORK
 WILL BE DONE IN THE GARAGE. (SHT A2.0
 SHOWS WORK BENCHES)
 4) PLEASE INDICATE THE NATURE OF MATER-
 IALS BEING STORED.
 5) DEPENDING ON INFORMATION RECIEVED, AN
 OIL OR OIL/SAND INTERCEPTOR MIGHT BE RE-
 QUIRED. IF SO IT SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 MANAGER, (561) 837-4074
 6) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-07-01 Cont ID  
Sent By kstevens Date 2002-06-28 Time 17:33 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***