Plan Review Details - Permit 02051150
Plan Review Stops For Permit 02051150
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-04 Cont ID  
Sent By lmartine Date 2002-06-04 Time 13:45 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-06-04 00:00:00 
 ANY PENETRATIONS THRU FIRE RATED
 ASSEMBLYS WILL REQUIRE DESIGN
 SUBMITTALS AND APPROVALS BEFORE
 INSPECTIONS.
  
 L. MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 11:40 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2002-05-29 00:00:00NO BUILDING /ARCH SUBMITTED FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2002-06-04 Cont ID  
Sent By pkrauss Date 2002-06-04 Time 14:40 Rev Time 0.20
Received By pkrauss Date 2002-06-04 Time 14:40 Sent To  
Notes
2002-06-04 00:00:00ELECTRICAL PERMIT APPLIED FOR
 SEPERATELY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By pkrauss Date 2002-05-28 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2002-05-29 Time 11:48 Sent To  
Notes
2002-05-29 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT THERE WERE NO
 ELECTRICAL SHEETS SUBITTED FOR REVEIW.
 PLEASE ALSO NOTE THERE MAY BE COMMENTS
 FROM OTHER REVIEWERS ONCE MORE DETAIL/
 INFORMATION IS SUBMITTED FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2002-05-29 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 11:03 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2002-05-29 00:00:00NOTHING SUBMITTED FOR REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-08-22 Cont ID  
Sent By pkrauss Date 2002-08-22 Time 11:55 Rev Time 0.15
Received By pkrauss Date 2002-08-22 Time 11:55 Sent To  
Notes
2002-08-22 00:00:00MECH PERMIT 02051151 - SUBMITTAL FOR THE
 FIRE DAMPER INSTALLATION.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 07:10 Rev Time 0.35
Received By pkrauss Date 2002-06-22 Time 07:10 Sent To  
Notes
2002-06-22 00:00:00MECHANICAL PERMIT 02051151
  
 SUBMITTAL - DETAIL FOR CONDENSATE
 DRYWELL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-03 Cont ID  
Sent By pkrauss Date 2002-06-03 Time 14:34 Rev Time 0.50
Received By pkrauss Date 2002-06-03 Time 14:34 Sent To  
Notes
2002-06-03 00:00:00MECHANICAL PERMIT 02051151
  
 PLAN SHEET M2.2, SPOKE WITH RIC RAO ON
 6-3-02 REFERENCE SOUTH CORRIDOR FIRE
 RATING ENDS BETWEEN CLASSROOM 205 &
 204. (CORRIDOR OPEN TO COURTYARD)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-05-28 Cont ID  
Sent By pkrauss Date 2002-05-28 Time 12:26 Rev Time 2.00
Received By pkrauss Date 2002-05-28 Time 11:45 Sent To E
Notes
2002-05-28 00:00:00MECHANICAL PERMIT 02051151
  
 PLEASE NOTE - NO FIRE DAMPERS ARE
 INDICATED ON PLANS (EXISTING OR NEW).
 ARCHITECTERIAL DRAWINGS WERE NOT
 SUBMITTED.COULD NO DETERMINE IF ANY
 OF THE CORRIDOR WALLS, MECHANICAL ROOMS
 OR STORAGE ROOMS HAVE A FIRE RESISTANT
 RATING.FIRE DAMPERS NEW OR EXISTING
 SHALL BE LOCATED ON THE PLANS AS PER
 2001 FBC(M) 607.6.
  
 PLEASE INDICATE ALL DUCT SMOKE DETECTORS
 ON THE PLAN.
  
 PLEASE INDICATE CONDENSATE LINE SIZE AND
 DISPOSAL LOCATION. 2001 FBC(M) 307.2.1.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-05-29 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 10:29 Rev Time 0.00
Received By dpalmer Date 2002-05-29 Time 10:28 Sent To  
Notes
2002-05-29 00:00:00NO PLUMB WORK