Plan Review Stops For Permit 02051001 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-05-21 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-05-21 |
Time |
12:50 |
Sent To |
|
|
Notes |
2002-05-21 00:00:00 | UNSAT! | | ~~~~~~ | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2} PLEASE INDICATE THE SIZE AND TYPE OF | | THE SERVICE ENTRANCE CONDUCTORS IN THE | | RISER,ALSO IN THE NIPPLE TO THE | | DISCONNECT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT. 88392 |
|
|
|