Plan Review Details - Permit 02050855
Plan Review Stops For Permit 02050855
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-05-16 Cont ID  
Sent By mamini Date 2002-05-16 Time 09:13 Rev Time 3.00
Received By mamini Date 2002-05-16 Time 09:13 Sent To  
Notes
2002-05-16 00:00:00PASSED:
 1. CIVIL /SITE WORK PLANS WERE REVIEWED
 UNDER BUILDING PERMIT # 01101288.
 RESPONSES TO THE REVIEW COMMENTS
 SATISFACTORY.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 09:42 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 09:42 Sent To  
Notes
2002-05-17 00:00:001) CLEARANCES TO FIRE HYDRANTS MUST BE
 AT LEAST SEVEN AND HALF FEET TO THE
 FRONT AND SIDES OF THEM. FOUR FEET
 CLEARANCE IS TO BE PROVIDED TO THE
 REAR OF THEM. RE: FFPC 3-5.6.2.1
  
 2) THE ABOVE CLEARANCES ARE TO BE
 PROVIDED TO FIRE PROTECTION APPLIANCES.
  
 3) APPROPRIATE SIGNAGE IS TO BE PROVIDED
 "NO PARKING, FIRE DEPARTMENT CONNECTION"
 IN ACCORDANCE WITH DOT STANDARDS FOR
 INFORMATION SIGNAGE. RE: FFPC 3-5.6.2.3
  
 4) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON FIRE LINE BACKFLOW DEVICES.
  
 5) WET FIRE HDYRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910