Plan Review Stops For Permit 02050855 |
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2002-05-16 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2002-05-16 |
Time |
09:13 |
Rev Time |
3.00 |
Received By |
mamini |
Date |
2002-05-16 |
Time |
09:13 |
Sent To |
|
|
Notes |
2002-05-16 00:00:00 | PASSED: | | 1. CIVIL /SITE WORK PLANS WERE REVIEWED | | UNDER BUILDING PERMIT # 01101288. | | RESPONSES TO THE REVIEW COMMENTS | | SATISFACTORY. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2002-05-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-17 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-17 |
Time |
09:42 |
Sent To |
|
|
Notes |
2002-05-17 00:00:00 | 1) CLEARANCES TO FIRE HYDRANTS MUST BE | | AT LEAST SEVEN AND HALF FEET TO THE | | FRONT AND SIDES OF THEM. FOUR FEET | | CLEARANCE IS TO BE PROVIDED TO THE | | REAR OF THEM. RE: FFPC 3-5.6.2.1 | | | | 2) THE ABOVE CLEARANCES ARE TO BE | | PROVIDED TO FIRE PROTECTION APPLIANCES. | | | | 3) APPROPRIATE SIGNAGE IS TO BE PROVIDED | | "NO PARKING, FIRE DEPARTMENT CONNECTION" | | IN ACCORDANCE WITH DOT STANDARDS FOR | | INFORMATION SIGNAGE. RE: FFPC 3-5.6.2.3 | | | | 4) ELECTRONIC SWITCHES WILL BE REQUIRED | | ON FIRE LINE BACKFLOW DEVICES. | | | | 5) WET FIRE HDYRANTS ARE REQUIRED PRIOR | | TO, DURING AND AFTER CONSTRUCTION. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
|