Plan Review Details - Permit 02050775
Plan Review Stops For Permit 02050775
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-04 Time 05:41 Rev Time 0.00
Received By dpalmer Date 2002-06-04 Time 05:41 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-04 Cont ID  
Sent By btrobaug Date 2002-11-04 Time 18:43 Rev Time 0.00
Received By btrobaug Date 2002-11-04 Time 18:43 Sent To R
Notes
2002-11-04 00:00:00TO JULIO./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-11-21 Cont ID  
Sent By hmoser Date 2002-11-21 Time 16:54 Rev Time 0.33
Received By hmoser Date 2002-11-21 Time 16:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-12 Cont ID  
Sent By pkrauss Date 2002-08-12 Time 10:47 Rev Time 0.35
Received By pkrauss Date 2002-08-12 Time 10:39 Sent To R
Notes
2002-08-12 00:00:00PROVISO:MECHANICAL PERMIT 02050801
  
 PLEASE PROVIDE CALCULATION SHOWING
 COMPLIANCE WITH 2001 FBC(M) 402 AT TIME
 OF INSPECTION.
  
 AS PER 2001 FBC(M) 1108.1, REFRIGERANT
 LINES SHALL BE TESTED.TEST SHALL BE
 PERFORMED WITH AN INERT DRIED GAS
 INCLUDING, BUT NOT LIMITED TO, NITROGEN
 & CARBON DIOXIDE 2001 FBC(M) 1108.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-04 Time 05:41 Rev Time 0.35
Received By pkrauss Date 2002-06-04 Time 07:07 Sent To R
Notes
2002-06-04 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02050801
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STOBE OR AREA
 SMOKE DETECTORS. 2001 FBC(M) 606.4.1
  
 PLEASE NOTE PLANS SHEET MP-2 DRAWING -
 SECOND FLOOR MECH & PLUMBING PLAN.HVAC
 DETAIL INDICATES "GROUND FLOOR" INSTEAD
 OF SECOND FLOOR.
  
 DRYER VENT SHALL BE A MINIMUM OF 4". NO
 SIZE INDICATED ON PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-05-25 Cont ID  
Sent By kstevens Date 2002-05-25 Time 09:48 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 09:48 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2002-12-02 Cont ID  
Sent By jgomez Date 2002-12-02 Time 13:29 Rev Time 0.75
Received By jgomez Date 2002-12-02 Time 13:29 Sent To  
Notes
2002-12-02 00:00:00REVIEW OF PROVISO ITEMS.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-08-14 Cont ID  
Sent By btrobaug Date 2002-11-04 Time 18:43 Rev Time 0.00
Received By jgomez Date 2002-08-13 Time 18:36 Sent To  
Notes
2002-08-14 00:00:00BUILDING REVIEW APPROVED WITH PROVISO-
 (AS PER MEETING W/ CONTRACTOR, ARCHITECT
 AND PLAN REVIEWERS. 8-14-02):
 1-PROVIDE ENGINEER'GANALYSIS-CALCS
 FOR CLARIFICATION OF HOW THE MAIN WIND
 FORCE RESISTING SYSTEM (MWFRS) WAS
 DESIGNED TO RESIST AND TRANSFER ALL
 LOADS TO FLOOR AND CEILING DIAPHRAGMS
 CONSIDERING THE DOUBLE CEILING AREAS
 AND PARTIAL FLOOR DIAPHRAGM. SEE SEC.
 1606.2.4 FBC 2001.
 **PROVIDE ENGINEERING ANALYSIS/CALCS FOR
 CLARIFICATION OF MASONRY WALLS LATERAL
 STABILITY (SEC. 2105 FBC) AND LATERAL
 SUPPORT (SEC. 2107 FBC) CONSIDERING
 THE HIGH VOLUME AREA SHOWN ON PLANS.
 2-NEED FIREBLOCKING @ TOP OF STAIRS TOO.
 SEC. 2305.1.4 FBC. SPECIFY MATERIAL &
 SIZE.
 3-PROVIDE SOIL TEST REPORT.
 4-PROVIDE COMPLETE INFORMATION WITH
 UPDATED PRODUCT APPROVAL FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT,
 SINCE COMPLETE/RIGHT INFORMATION WAS
 NOT SUBMITTED WITH PLANS. SEE CITY
 IMPLEMENTATION STANDARD FOR HURRICANE
 MISSILE IMPACT PROTECTION.
 5-PROVIDE LEGIBLE PRODUCT APPROVAL FOR
 DOORS, WINDOWS AND MULLIONS TO BE USED
 **NOTE: SEE ARCHITECTURAL PLANS FOR
 RIGHT SIZE, SHAPE AND DESIGN PRESSURES
 **ALSO, VERIFY THAT DRAWINGS IN PRODUCT
 APPROVAL MATCH THEIR REPORTS.
 6-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 ARCHED WINDOWS AS REQUIRED BY THE
 PRODUCT APPROVAL.
 **NOTE: NEED DETAIL FOR FRAMED ARCH AND
 FOR MASONRY ATTACHMENT.
 7-NOTE 2 SHEET A-1: PROVIDE DETAIL THAT
 SHOWS WINDOW RECESSED 4.5" FOR THE
 INSTALLATION OF STORM SHUTTERS.
 **NOTE: SEE PRODUCT APPROVAL FOR
 TRACK USED AND CONSIDER THE GLASS
 SEPARATION AND EDGE DISTANCE.
 8-SEE PRODUCT APPROVAL FOR GARAGE DOORS
 FOR STRUCTURAL BUCK SPECS AND REVISE
 DETAIL AS REQUIRED.
 9--SPECIFY FIREBLOCKING IN WALL SECTIONS
 AND PROVIDE GENERAL SPECIFICATIONS FOR
 REQUIRED FIREBLOCKING AT ALL CONCEALED
 SPACES. SEC. 2305.1.4
 10-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL DETAILS AS WELL.
 SEC. 2305.4 FBC.
 11-STAIR FLOOR PLAN: CLARIFY NOTE #13.
 REVISE STAIR DETAILS. REMEMBER THAT
 WOOD COLUMN WILL BE CHANGED FOR STEEL
 COLUMN. ALSO, VERIFY THAT KEY NOTES
 FOR STAIRS MATCH STAIR DETAILS.
 CLARIFY/REVISE STAIR RATIO CALCS.
 12-SPECIFY SPACING FOR WWM SUPPORTS. SEE
 SEC. 1909.3 FBC 2001.
 13-SHEET S-1: SOME DETAILS AND NOTES ARE
 OVERLAPPING OR DETAILS NOT SHOWN.
 CLARIFY/REVISE ASSIGNED DETAIL NUMBER
 AND SHEET # ASSIGNED FOR THE PRIVACY
 WALLS.
 14-SHEET S-2: UPDATE NOTE #2. SEMCO IS
 OUT OF BUSINESS. UPDATE AS REQUIRED.
 15-SHEET S-3: IDENTIFY ROOF ZONE 3 FOR
 NAILING DIAPHRAGM.
 **NOTE: ZONE 3 DOESN'T REFER TO GABLE
 ENDS ONLY. ALL CORNER ARE INCLUDED TOO
 **REVISE TRUSS CONNECTOR SCHEDULE:
 NUMBER OF FASTENERS SPECIFIED AND
 ALLOWABLE UPLIFT DON'T MATCH. SEE USP
 CATALOGUE. PROVIDE ENGINEERED CALCS
 FOR UPLIFT LOADS DIFFERENT THAN THOSE
 SPECIFIED ON CATALOGUE.
 16-PROVIDE ATTIC ACCESS ABOVE GARAGE AND
 MORNING ROOMIF CLEAR HEIGHT IS MORE
 THAN 24". SEC. 2309.6 FBC 2001.
 17-IF PROVIDING MASONRY LETTER, THEN IT
 NEEDS TO BE UPDATED & ADDRESSED TO THE
 CITY OF WPB & CONTRACTOR AND IDENTIFY
 SPECIFIC PROJECT.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-08-01 Cont ID  
Sent By pkrauss Date 2002-08-12 Time 11:09 Rev Time 0.00
Received By jgomez Date 2002-08-01 Time 11:26 Sent To  
Notes
2002-08-01 00:00:00DRAWINGS WERE NOT REVISED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-06-17 Cont ID  
Sent By pkrauss Date 2002-06-04 Time 09:00 Rev Time 4.00
Received By jgomez Date 2002-06-17 Time 18:49 Sent To  
Notes
2002-06-17 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-REVISE SIZE OF ATTIC ACCESS. KEY NOTE
 #7.36" MIN. SIZE. SEC 2309.6 FBC.
 3-CLARIFY SIZE OF EGRESS WINDOWS. 34SH
 WINDOWS ARE 48" TYPICALLY 48" HIGH AND
 WILL NOT HAVE 24" CLEAR HEIGHT OPENING
 AS REQ'D BY SECTION 1005.4.4 FBC 2001.
 4-REVISE STAIRS RATIO. SEE SECTION
 1007.3.1 (EXCEPTION #1).
 5-SEE COMMENTS ON PLANS AND BRING BACK
 REVIEWED SET AFTER CORRECTIONS ARE
 DONE TO ORIGINAL DRAWINGS.
 6-PROVIDE ATTIC ACCESS AT FRONT PART OF
 GARAGE ROOF AND AT MORNING ROOF IF
 THERE IS A CLEAR ATTIC SPACE NOT LESS
 THAN 24" SEC. 2309.6 FBC 2001.
 7-SPECIFY FIREBLOCKING MATERIALS AND
 LOCATION AT STAIRS. SEC. 2305.1.4 FBC.
 8-SPECIFY DRAFSTOPPING LOCATION AND
 MATERIAL AT 2ND FL. FRAMNG PLAN AS
 REQUIRED BY SEC. 2305.2.2 FBC 2001.
 9-SPECIFY FIRECUTS AT MASONRY WALL AS
 REQUIRED BY SEC. 2305.4 FBC 2001.
 10-PROVIDE SPECIFICATIONS FOR SOIL AND
 FOOTING PROTECTION WHEN IMPACTED BY
 WATER FROM ROOF VALLEYS. SEE SECTION
 1804.1.6 FBC 2001.
 11-PROVIDE SOIL TEST REPORT.
 12-DESIGN JOINTS AT CONCRETE SLAB. SEC.
 1909.3 FBC 2001. (OR SPECIFY SUPPORTS)
 13-STORM SHUTTERS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 & KEY PLAN. SEE CITY SAMPLE.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS & ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, MEAN ROOF HEIGHT,
 EDGE DISTANCE, CONNECTION TYPE, PANEL
 SPAN & STRUCTURE TO BE ATTACHED TO.
 14-PROVIDE PRODUCT APPROVAL FOR:
 A)DOUBLE ENTRY DOORS AS SHOWN ON PLANS.
 B)COMPLETE PAN AMERICAN WINDOW MULLION
 PRODUCT APPROVAL (NOT LAWSON, SINCE
 WINDOWS USED ARE BY PAN AMERICAN)
 C)ARCHED WINDOWS NEED LEGIBLE DRAWINGS.
 15-PROVIDE UPDATED ORIGINAL LETTER OF
 MASONRY TYPE TO BE USED. LETTER TO
 BE ADDRESSED TO THE CITY OF WEST PALM
 BEACH AND ADDRESSING SPECIFIC JOB.
 16-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 FIXED WINDOWS AS REQ'D ON PRODUCT
 APPROVAL SUBMITTED.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-05-17 Cont ID  
Sent By sgraham Date 2002-05-17 Time 12:12 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***