Plan Review Details - Permit 02050736
Plan Review Stops For Permit 02050736
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-09-03 Cont ID  
Sent By hpiskura Date 2002-09-03 Time 13:52 Rev Time 0.00
Received By hpiskura Date 2002-08-27 Time 16:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-29 Cont ID  
Sent By hpiskura Date 2002-07-29 Time 07:48 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-29 00:00:00A RESIDENTIAL FIRE SPRINKLER SYSTEM,
 (13R), IS NOT A RECOGNIZED ALTERNATE
 FOR OTHER CODE REQUIREMENTS.SEE FBC
 903.2 AND FBC 903.7.5.
  
 THE STAIRS FROM THE SECOND FLOOR IN
 BLDGA ARE REQUIRED TO BE ENCLOSED IN
 FIRE RATED CONSTRUCTION AND TO PROVIDE
 A CONTINUOUS PROTECTED PATH TO THE
 OUTSIDE.SEE FBC 1006.1 AND FBC
 1010.1.1.
  
 THE FIRE PROTECTION DESIGN IS REQUIRED
 TO APPEAR ON THE PERMIT PLANS.SEE FBC
 104.1. (SPRINKLER & ALARM)
  
 IF TEST NOTICE OF ACCEPTANCE REPORTS ARE
 NOT INCLUDED WITH THE PERMIT PLANS FOR
 THE NEW AND OR RELOCATED DOORS AND
 WINDOWS, A SEPARATE PERMIT AND FEES FOR
 THAT WORK WILL BE REQUIRED.SEE
 ATTACHED "IMPLEMENTATION STANDARD"ALSO
 SHOW HOW HURRICANE MISSILE IMPACT
 RESISTANCE WILL BE ACCOMPLISHED.
  
 SHOW THE COMPONENT AND CLADDING DESIGN
 PRESSURES FOR THE OPENINGS.
  
 THE RG THOMAS LETTER DATED JULY 8, 2002,
 IN ITEM #3 DECLARES THAT THE SOUTH
 BUILDING WOULD NOT HAVE PUBLIC AREAS
 AND THEREFORE NEED NOT BE ACCESSIBLE.
 THE PLANS SHOW THREE BEDROOM SUITES AND
 A MANAGER'S APARTMENT.WILL THE SUITES
 NOT BE AVAILABLE TO THE PUBLIC?
  
 PROVIDE DETAILS FOR THE FISH POND SHOWN
 ON SHEET SP 1.
  
 SHOW THE FIRE RATED TENANT SEPARATION
 FOR THE SUITES IN ACCORDANCE WITH FBC
 704.3.
  
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 EXISTING PATIO TO BE ENCLOSED AT THE
 REAR OF BUILDING A, AND FOR THE FRONT
 PORCH AS WELL.
  
 AN 8.5 X 11 SHEET INCLUDED WITH THE
 PERMIT SUBMITTAL SHOWS TWO PARKING
 SPACES OFF THE ALLEY AT THE REAR OF
 BUILDING A.SHOW THE REQUIRED HC SPACE
 ON AN ACCESSIBLE ROUTE.
  
 SHOW THE SIGNAGE FOR THE HC ACCESSIBLE
 ENTRANCE WHICH WILL NOT BE AT THE MAIN
 PUBLIC ENTRANCE. SEE FBC 11-4.1.2 (7).
  
 SHEET A1, DECLARE THE INTENDED OCCUPANCY
 USE OF THE ROOMS ON THE FIRST FLOOR OF
 BLDG A SHOWN ON THE EAST AND WEST SIDES,
 AND ON THE SECOND FLOOR, THE ROOM IN
 THE SOUTH WEST CORNER.
  
 SHEET A2, BLDG B.WHAT WILL BE THE USE
 OF THE SECOND FLOOR?HOW WILL EGRESS
 AND ACCESS BE ACCOMPLISHED SUBSEQUENT
 TO THE DEMOLILTION OF THE STAIRS?SEE
 FBC 104.2.
  
 SHEET A2, WHERE ARE THE TOILET
 FACILITIES FOR BEDROOM SUITE #3?SEE
 FBC 1204.
  
 SHEET A2, THE NEW DOOR AT THE FRONT OF
 THE BUILDING IS NOT PERMITTED TO OPEN
 DIRECTLY ONTO A FLIGHT OF STAIRS.SEE
 FBC 1012.1.4.
  
 WHAT IS THE CONDITION OF THE DOOR SHOWN
 AS EXISTING FROM THE MANAGER'S ROOM,
 GIVEN THAT STAIRS ARE INDICATED ON THE
 FRONT AND REAR OF THE BUILDING?
  
 WHAT WILL THE PORCH INTENDED TO BE
 ENCLOSED BE USED FOR?
  
 SHEET SP1, WHAT DO THE CROSS HATCHED
 AREAS SHOWN EXTERIOR TO BOTH BUILDINGS
 INDICATE?
  
 SHEET A3, SECTION 1A3. A GUARDRAIL AS
 WELL AS HANDRAILS ARE REQUIRED FOR THE
 DECK.WHAT IS THE RISE AND RUN OF THE
 STAIRS?CONSTRUCTION DETAIL?
  
 AS PREVIOUSLY NOTED IMPACT FEES MUST BE
 PAID TO THE COUNTY BEFORE A PERMIT MAY
 BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-06-11 Cont ID  
Sent By hpiskura Date 2002-06-11 Time 11:20 Rev Time 0.00
Received By hpiskura Date   Time   Sent To FIRE
Notes
2002-06-11 00:00:00THE CONVERSION FROM A SINGLE FAMILY
 RESIDENCE (R3 OCCUPANCY) TO A BED AND
 BREAKFAST INN (R1 OCCUPANCY) IS SUBJECT
 TO IMPACT FEES COLLECTED BY PALM BEACH
 COUNTY. THE PERMIT PLANS MUST BE
 STAMPED BY THAT OFFICE AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
  
 THE PLANS, BOTH SHEETS NUMBERED A1 ARE
 NOT CLEAR.SEE FBC 104.3.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR BUILDINGS, AND
 ADDRESS THE PERTINENT ITEMS LISTED
 THERE.
  
 SHOW THE REQUIRED HANDICAP
 ACCESSIBILITY REQUIREMENTS FOR FBC
 11-9.1 ACCESSIBLE TRANSIENT LODGING.
  
 SHOW COMPLIANCE WITH FBC 425.
  
 PROVIDE DETAILS FOR THE EMERGENCY ESCAPE
 OPENINGS REQUIRED BY FBC 1005.4.1.
  
 PROVIDE A STAIR ENCLOSURE IN ACCORDANCE
 WITH FBC 1006.1.1, SEE ALSO FBC 1010.1.1
  
 IN THE ABSENCE OF THE ABOVE REQUESTED
 INFORMATION, A COMPLETE PLAN REVIEW IS
 NOT POSSIBLE AT THIS TIME AND
 ADDITIONAL BUILDING, FIRE, LIFE SAFETY
 OR OTHER CODES MAY BE APPLICABLE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-05-05 Cont ID  
Sent By btrobaug Date 2003-05-05 Time 15:49 Rev Time 0.50
Received By btrobaug Date 2003-05-05 Time 14:50 Sent To  
Notes
2003-05-05 00:00:00 
 TOLD CONTRACTOR THERE IS NO L/V ON THE
 PLANS AND THERE NEEDS TO BE A SEPERATE
 PERMIT FOR SAME./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-05-05 Time 09:53 Rev Time 1.00
Received By btrobaug Date 2003-04-08 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-29 Cont ID  
Sent By shernand Date 2003-04-07 Time 13:43 Rev Time 0.00
Received By dpalmer Date 2002-07-29 Time 06:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-05-15 Cont ID  
Sent By btrobaug Date 2002-05-15 Time 14:20 Rev Time 0.00
Received By btrobaug Date 2002-05-15 Time 13:52 Sent To P
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-19 Cont ID  
Sent By mcarsill Date 2002-07-19 Time 17:35 Rev Time 0.00
Received By mamini Date 2002-07-19 Time 17:35 Sent To  
Notes
2002-07-19 00:00:001) ADDRESS REQUIRED ON BUILDING.
  
 2) PLANS INDICATE THAT THE INTERIOR
 IS TO BE LATH AND PLASTER. THE INTERIOR
 FINISH CLASSIFICATION IS TO MEET
 EITHER CLASS A, B, OR C IN OCCUPIED
 AREAS.
  
 3) RECENTLY THE FIRE SPRINKLER DRAWINGS
 WERE APPROVED WITH SOME AREAS ON THE
 SECOND FLOOR BEING IDENTIFIED AS DEAD
 SPACES. THE ARCHITECTURAL PLANS INDICATE
 THAT THESE AREAS WILL BE STORAGE AND
 ATTIC STORAGE. SUITABLE FIRE SPRINKLER
 PROTECTION WILL BE REQUIRED.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE REQUIRED FIRE ALARM SYSTEM.
  
 5) ALL NEW STAIRS AND RAMPS ARE
 REQUIRED TO HAVE HANDRAILS.
  
 6) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-06-18 Cont ID  
Sent By hpiskura Date 2002-06-11 Time 11:34 Rev Time 0.00
Received By mcarsill Date 2002-06-18 Time 11:16 Sent To  
Notes
2002-06-18 00:00:001) SINCE BUILDING WILL BE CONSIDERED
 A NEW ROOMOING HOUSE, A COMPLETE FIRE
 SPRINKLER SYSTEM WILL BE REQUIRED.
 SEPARATE PLANS AND PERMITS WILL BE
 REQUIRED.
  
 2) AT LEAST TWO SEPARATE EXITS ARE
 REQUIRED FROM EVERY FLOOR. PLEASE
 SHOW THE REQUIRED NUMBER OF EXITS FOR
 BOTH FLOORS.
  
 3) A FIRE ALARM SYSTEM WILL BE REQUIRED.
 SEPARATE PLANS AND PERMITS ARE REQUIRED
 PRIOR TO INSTALLATION.
  
 4) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR WALLS AND CEILINGS.
  
 5) ALL SLEEPING ROOM DOORS ARE TO BE
 SMOKE RESISTANT.
  
 6) ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 09:52 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 09:52 Sent To E
Notes
2003-05-05 00:00:00REVISION.BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-07 Cont ID  
Sent By shernand Date 2003-04-07 Time 13:43 Rev Time 0.00
Received By shernand Date 2003-04-07 Time 13:43 Sent To E
Notes
2003-04-07 00:00:00BT DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-05-28 Cont ID  
Sent By kstevens Date 2002-05-24 Time 10:31 Rev Time 0.25
Received By pkrauss Date 2002-05-28 Time 11:17 Sent To FIRE
Notes
2002-05-28 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-09-04 Cont ID  
Sent By kstevens Date 2002-09-04 Time 11:22 Rev Time 0.00
Received By kstevens Date 2002-09-04 Time 14:04 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-07-30 Cont ID  
Sent By kstevens Date 2002-07-30 Time 11:30 Rev Time 0.00
Received By kstevens Date 2002-07-29 Time 19:56 Sent To  
Notes
2002-07-30 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SANITARY RISER DIAGRAM NOT TO CODE.
 BATHROOMS FROM 2ND FLOOR SHALL NOT DRAIN
 INTO VENT STACK FOR 1ST FLOOR BATHROOM.
 MOP SINK NOT SHOWN ON RISER DIAGRAM.
 2) FROM PREVIOUS REVIEW: (#4), CLEAR
 FLOOR SPACE NOT SHOWN. LAV CABINET CAN
 NOT INTRUDE INTO 5' TURNING RADIUS. LAV
 SHALL BE 15" OFF WALL TO CENTER OF FIX-
 TURE. (CENTERED IN CLEAR FLOOR SPACE)
 11-4.19.3. HEIGHT FOR LAV 11-4.19.2.
 W/C SHALL BE 1'6" OFF WALL TO CENTER OF
 FIXTURE. SHOW DETAILS FOR SHOWER STALL,
 SEC 11-4.21 AND ALL SUBSECTIONS. SEE
 FIG'S 35 & 37(B). PLEASE SHOW CLEAR DE-
 TAILS FOR ALL FIXTURES IN ACCESSIBLE
 BATHROOM.
 3) WHERE IS BATHROOM FOR BEDROOM #3 IN
 BLDG "B".
 4) SHT A-3 HDCP BATHROOM REQUIREMENTS,
 TOILET HEIGHT SHALL READ 17"-19". LAV
 34" TO LAV/COUNTER TOP.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-23 Cont ID  
Sent By btrobaug Date 2002-05-15 Time 14:20 Rev Time 0.00
Received By kstevens Date 2002-05-23 Time 15:02 Sent To M
Notes
2002-05-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM FOR ALL PIPING PROPOSED FOR BATH
 ROOMS.
 2) APPLICATION SAYS REMODEL EXISTING
 EXISTING BATHROOMS 1ST FLOOR, ADD POWDER
 ROOM, REMODEL 2ND FLOOR BATHROOM, AND
 ADD 2 NEW BATHROOMS ON 2ND FLOOR, BUT
 SAYS NOTHING OF WORK BEING DONE IN A
 COTTAGE. PLEASE SUPPLY A PLOT PLAN SHOW-
 ING ALL BLDGS ON PROPERTY.
 3) SEPARATE GAS PERMIT REQUIRED FOR GAS
 WORK BEING DONE. PLEASE SUBMIT INFORMAT-
 ION REQUIRED FOR GAS PERMIT AS FOLLOWS:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS CODE.
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE.
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE. IF NATURAL
 GAS SPECIFY .5 PSI OR 2 PSI.
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 4) HC BATH #6 PLEASE SHOW DETAILS FOR
 HDCP BATH. SHOW CLEAR FLOOR SPACE FOR
 ALL FIXTURES. LAV TO BE 15" OFF THE WALL
 CENTERED IN CLEAR FLOOR SPACE 11-4.19.3,
 HEIGHT FOR LAV 4.19.2. W/C SHALL BE 1'6"
 TO CENTER OFF WALL, HEIGHT 4.16.3, DOOR
 SHALL NOT SWING INTO CLEAR FLOOR SPACE
 REQUIRED FOR ANY FIXTURE, 4.22.2, SHOWER
 STALLS 4.21 AND ALL SUBSECTIONS. PLEASE
 SHOW CLEAR DETAILS FOR ALL FIXTURES IN
 HDCP BATHROOM.
 5) PLEASE INDICATE ROOM SIZE FOR ALL
 BATHROOMS.
 6) ALL DEMO WORK SHALL BE LEFT EXPOSED
 FOR INSPECTION PRIOR TO COVERING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-09-05 Cont ID  
Sent By kstevens Date 2002-09-04 Time 17:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***